| 2008-10-01 14:16:35 | DENIED |
| | REFERENCE: FBC-2004 PLUMBIING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | CITY WPB MUNICIPAL CODE |
| | |
| | 1. ALL SHEETS WITH ARCHITECTURAL TITLE BLOCK SHALL |
| | INCLUDE THE ADDRESS AND FIRM LICENSE NUMBER, |
| | (CERTIFICATE OF AUTHORIZATION NUMBER), AS REQUIRED IN |
| | FAC 61G1-16.004(1)(2) & FS 481.219, 481.2055. (SEE |
| | ATTACHED SHEET). |
| | |
| | 2. SHT CV.01 STATES "INTENDED TO BE USED AS A PRIVATE |
| | ENTERTAINMENT FACILITY". PLEASE CLARIFY. ENTERTAINMENT |
| | FOR WHO? IS THIS A SELECT GROUP OF PEOPLE? IS THIS TO |
| | BE A TRAINING FACILITY? SECTION 106.1.2 & TABLES |
| | 1004.1.2 & 403.1. |
| | |
| | 3. THE APPLICATION FOR PERMIT ASKS FOR GROSS SQUARE |
| | FOOTAGE AND WHETHER OR NOT THIS IS A CHANGE OF |
| | OCCUPANCY. PLEASE INDICATE BOTH ON THE APPLICATION. |
| | SECTION 105.1. |
| | |
| | 4. THE ADDRESS ON THE APPLICATION & IN THE CITY WEBSITE |
| | IS SHOWN AS 1600 FLORIDA MANGO ROAD, BUT THE PLANS SHOW |
| | THE ADDRESS AS 1590 FLORIDA MANGO ROAD. THE CORRECT |
| | ADDRESS SHALL BE INDICATED ON EACH SHEET PER SECTIONS |
| | 106.1.1 & 106.1.3. |
| | |
| | 5. SUBMIT CALCULATIONS FOR MINIMUM FACILITIES PER |
| | TABLES 1004.1.2 & 403.1. PER TABLE 1004.1.2 THE RINK IS |
| | 50 GROSS. (SHOW GROSS SQUARE FOOTAGE FOR THE RINK. |
| | PLEASE INDICATE CALCULATIONS FOR OTHER OCCUPANCIES SUCH |
| | AS BUSINESS & STORAGE. INDICATE THE SQUARE FOOTAGE OF |
| | EACH AREA ON THE FLOOR PLAN AS WELL AS THE DECK AREA |
| | AROUND THE RINK. |
| | |
| | 6. SHT LP-1 IS NOT SIGNED, SEALED & DATED AS REQUIRED |
| | IN SECTION 106.1 & FLORIDA STATUTES. |
| | |
| | 7. SHT A.01 NOTE STATES "DEMO PLAN SUBMITTED UNDER |
| | SEPARATE PERMIT". DEMO PERMIT NOT FOUND. PLEASE |
| | INDICATE THE DEMO PERMIT NUMBER FOR REFERENCE. SECTION |
| | 106.1.2 & SECTION 704.5. |
| | |
| | 8. SHTS A.01.1 & A.09 (DETAILS B/A.09 & C/A.09). SHOW |
| | THE 5 FOOT TURNING AREA, BACKING FOR THE GRAB BARS AT |
| | THE W/C AND SHOWER, INDICATE THE LOCATION OF THE |
| | CONTROLS IN THE SHOWER & SUBMIT A DETAIL FOR THE SHOWER |
| | CURB, (MAX 1/2" IF INSTALLED, NO CURB REQUIRED). |
| | SECTIONS 11-4.1.3(11), 11-4.16.4, 11-4.21.4, 11-4.21.5 |
| | & 11-4.21.7. |
| | |
| | 9. SHT A.01.1 & A.09 (DETAILS A/A.09, E/A.09, 1/A.09, |
| | 2/A.09, 3/A.09 & 4/A.09). SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | |
| | ___FOR W/C'S: |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.16.4 GRAB BARS (INDICATED AS 3'6" AFF IN |
| | DETAILS 2 & 4. |
| | C. 11-4.16.5 FLUSH CONTROLS |
| | |
| | ___FOR LAVS: |
| | A. 11-4.19.2 CLEARANCES |
| | B. 11-4.19.3 CLEAR FLOOR SPACE |
| | C. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | D. 11-4.19.5 FAUCETS |
| | |
| | 10. SHT A.01.1 & A.09 (DETAILS D/A.09, 8/A.09 & |
| | 9/A.09). THE BATHROOM SHALL BE ACCESSIBLE. PLEASE SHOW |
| | COMPLIANCE WITH THE FOLLOWING: |
| | |
| | ___FOR W/C: |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.16.3 HEIGHT |
| | C. 11-4.16.4 GRAB BARS |
| | D. 11-4.16.5 FLUSH CONTROLS |
| | E. 11-4.16.6 DISPENSERS |
| | |
| | ___FOR LAV: |
| | A. 11-4.19.2 HEIGHT & CLEARANCES |
| | B. 11-4.19.3 CLEAR FLOOR SPACE - FORWARD APPROACH |
| | REQUIRED (FIG 32) |
| | C. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | D. 11-4.19.5 FAUCETS |
| | E. 11-4.19.6 MIRRORS |
| | |
| | ___FOR SHOWER: |
| | A. 11-4.21.2 SIZE & CLEARANCES |
| | B. 11-4.21.3 SEAT |
| | C. 11-4.21.4 GRAB BARS |
| | D. 11-4.21.5 CONTROLS |
| | E. 11-4.21.6 SHOWER UNIT |
| | F. 11-4.21.7 CURBS |
| | |
| | 11. SHTS A.01 & P.11 (DETAILS 3/A.11 & A/A.11). TOILET |
| | ROOM SHALL BE ACCESSIBLE. PLEASE SHOW COMPLIANCE WITH |
| | THE FOLLOWING: |
| | |
| | A. 11-4.24.4 SINK DEPTH |
| | B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH |
| | REQUIRED - CABINET DOORS NOT APPROVED) |
| | C. 11-4.24.7 FAUCET |
| | |
| | 12. ALL SHEETS WITH ROCAMAR ENGINEERING SERVICES INC. |
| | TITLE BLOCK. THE ADDRESS ON THE TITLE BLOCK DOES NOT |
| | REFLECT THE ADDRESS OF RECORD ON THE STATE OF FLORIDA |
| | DBPR WEBSITE. (SEE ATTACHED SHEET). PLEASE UPDATE THE |
| | TITLE BLOCKS OR THE DBPR WEBSITE PRIOR TO RESUBMITTING |
| | FOR REVIEW SO THE ADDRESS CORRELATES. FAC |
| | 61G15-23.002(2) & FS 471.025. |
| | |
| | 13. SHT P-1 MACERATING UNIT. SUBMIT MANUF |
| | SPECIFICATIONS & INSTALLATION INSTRUCTIONS. NOTE |
| | INDICATES SEE DETAIL ON SHEET P-3, BUT THE DETAIL JUST |
| | SHOWS A WEBSITE AND THE WEBSITE WILL NOT OPEN. SECTIONS |
| | 106.1.2 & 712.4.1. |
| | |
| | 14. SHT P-1 SHOWS AN OIL INTERCEPTOR. THE OIL |
| | INTERCEPTOR SHALL BE SIZED BY THE UTILITY DEPT. |
| | INDUSTRIAL PRETREATMENT. PLEASE CONTACT HOLLY MCGRATH |
| | LABORATORY SUPERVISOR BY PHONE, (561) 822-2271 - OR |
| | FAX, (561) 822-2279 - OR E-MAIL, [email protected]. |
| | ARTICLE III SECTION 90-124(7). |
| | |
| | 15. SHT P-1 SHOWS THE GAS LINE TO THE EMERGENCY |
| | GENERATOR. THE NOTE INDICATES 20 PSI REQUIRED. PLEASE |
| | CLARIFY. SUBMIT MANUF. SPECIFICATION SHEETS AS WELL AS |
| | INSTALLATION SHEETS FOR THE GENERATOR SHOWING A LISTING |
| | FOR THE GENERATOR, INLET PRESSURE & BTU LOAD FOR THE |
| | GENERATOR. SEPARATE GENERATOR PERMIT REQUIRED. FBC-2004 |
| | FUEL GAS DOES NOT HAVE A TABLE FOR 20 PSI. PLEASE |
| | SUBMIT AN APPROVED GAS PIPE SIZING TABLE FOR 20 PSI. |
| | SECTION 402. |
| | |
| | 16. SHT P-1 CLEANOUTS ARE REQUIRED PER SECTION 708.3.2, |
| | NOT MORE THAN 100 FEET IN BUILDING SEWERS AND PER |
| | SECTION 708.3.5 NEAR THE JUNCTION OF THE BUILDING DRAIN |
| | AND THE BUILDING SEWER. PLEASE SHOW ON THE FLOOR PLAN |
| | AND ON THE SANITARY RISER DIAGRAM. |
| | |
| | 17. SHT P-1 SHOWS 1-1/2" MAKE UP WATER TO THE 2ND FLOOR |
| | MECHANICAL, 1-1/2" MAKE UP WATER FOR SYSTEM FILLING & |
| | 1" HOT WATER FOR ICE MELTING. PLEASE INDICATE THE |
| | METHOD OF BACKFLOW PROTECTION OF EACH SUPPLY LINE PER |
| | SECTIONS 608.1 & 608.3. ALSO AN RPZV BACKFLOW IS |
| | REQUIRED ON THE WATER SERVICE TO THE BUILDING PER |
| | SECTION 608.13.2. PLEASE INDICATE ON THE PLANS AND ON |
| | THE WATER ISOMETRIC RISER DIAGRAM SHEET P-7. |
| | |
| | 18. SHT P-2 PIPING ARRANGEMENT AT THE WATER HEATER. |
| | PLEASE INDICATE WHERE THE T&P RELIEF VALVE TERMINATES. |
| | SECTION 504.6.1 -- INDICATE THE MANUFACTURE AND MODEL |
| | NUMBER FOR THE EXPANSION TANK. SUBMIT CALCULATIONS OR |
| | MANUF. CHART FOR SIZING THE EXPANSION TANK. SECTION |
| | 607.3.2. |
| | |
| | 19. SHT P-3 ICE MELTING PIT DRAINAGE DETAIL. PER |
| | SECTION 712.2 A FULL OPEN VALVE IS REQUIRED ON THE |
| | DISCHARGE SIDE OF THE CHECK VALVE. -- THE DETAIL |
| | APPEARS TO SHOW A REDUCTION IN PIPE SIZE IN THE |
| | DIRECTION OF FLOW. THIS IS NOT APPROVED PER SECTION |
| | 704.2. PLEASE CLARIFY. |
| | |
| | 20. SHT P-5 INDICATE THE MANUFACTURE AND MODEL NUMBER |
| | FOR THE EXPANSION TANK. SUBMIT CALCULATIONS OR MANUF. |
| | CHART FOR SIZING THE EXPANSION TANK. SECTION 607.3.2. |
| | |
| | 21. SHT P-5 THE GAS PIPING, (1-1/2") TO THE GENERATOR |
| | DOES NOT REFLECT THE GAS PIPING SIZE INDICATED ON SHT |
| | P-1, (1"). PLEASE CORRELATE. SECTION 402. |
| | |
| | 22. SHT P-5 SEPARATE GAS PERMIT IS REQUIRED. PLEASE |
| | SUBMIT THE FOLLOWING INFORMATION FOR EACH GAS SYSTEM: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. (PIPE LENGTHS NOT INDICATED). |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | C. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | D. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. (20 PSI ON SHT P-1 |
| | BUT .5 PSI ON SHT P-5) CLARIFY EACH SYSTEM. |
| | |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | **PLEASE SHOW "GAS PIPING SIZED ON FOLLOWING" FOR EACH |
| | METER/SYSTEM. |
| | |
| | 23. SHT P-7 PLUMBING WATER ISOMETRIC RISER DIAGRAM DOES |
| | NOT REFLECT THE FLOOR PLAN. THE WATER SUPPLY PIPING TO |
| | W/C & LAV IN THE TOILET ROOM BY THE ICE PIT ARE NOT |
| | SHOWN ON THE ISOMETRIC. PLEASE CORRELATE. SECTIONS |
| | 106.1.1 & 604. -- A SHUT OFF VALVE IS REQUIRED ON THE |
| | SUPPLY LINE TO THE HOSE BIBB BY THE EQUIPMENT ROOM. |
| | SECTION 606.2(2). |
| | |
| | 24. SHT P-7 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM. |
| | THE FLOOR DRAIN IN THE ROOM ADJACENT TO THE MOP SINK |
| | ROOM SHALL HAVE A TRAP PRIMER. SECTION 1002.4. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |