Plan Review Notes
Plan Review Notes For Permit 08090611
Permit Number 08090611
Review Stop P
Sequence Number 1
Notes
Date Text
2008-10-01 14:16:35DENIED
 REFERENCE: FBC-2004 PLUMBIING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB MUNICIPAL CODE
  
 1. ALL SHEETS WITH ARCHITECTURAL TITLE BLOCK SHALL
 INCLUDE THE ADDRESS AND FIRM LICENSE NUMBER,
 (CERTIFICATE OF AUTHORIZATION NUMBER), AS REQUIRED IN
 FAC 61G1-16.004(1)(2) & FS 481.219, 481.2055. (SEE
 ATTACHED SHEET).
  
 2. SHT CV.01 STATES "INTENDED TO BE USED AS A PRIVATE
 ENTERTAINMENT FACILITY". PLEASE CLARIFY. ENTERTAINMENT
 FOR WHO? IS THIS A SELECT GROUP OF PEOPLE? IS THIS TO
 BE A TRAINING FACILITY? SECTION 106.1.2 & TABLES
 1004.1.2 & 403.1.
  
 3. THE APPLICATION FOR PERMIT ASKS FOR GROSS SQUARE
 FOOTAGE AND WHETHER OR NOT THIS IS A CHANGE OF
 OCCUPANCY. PLEASE INDICATE BOTH ON THE APPLICATION.
 SECTION 105.1.
  
 4. THE ADDRESS ON THE APPLICATION & IN THE CITY WEBSITE
 IS SHOWN AS 1600 FLORIDA MANGO ROAD, BUT THE PLANS SHOW
 THE ADDRESS AS 1590 FLORIDA MANGO ROAD. THE CORRECT
 ADDRESS SHALL BE INDICATED ON EACH SHEET PER SECTIONS
 106.1.1 & 106.1.3.
  
 5. SUBMIT CALCULATIONS FOR MINIMUM FACILITIES PER
 TABLES 1004.1.2 & 403.1. PER TABLE 1004.1.2 THE RINK IS
 50 GROSS. (SHOW GROSS SQUARE FOOTAGE FOR THE RINK.
 PLEASE INDICATE CALCULATIONS FOR OTHER OCCUPANCIES SUCH
 AS BUSINESS & STORAGE. INDICATE THE SQUARE FOOTAGE OF
 EACH AREA ON THE FLOOR PLAN AS WELL AS THE DECK AREA
 AROUND THE RINK.
  
 6. SHT LP-1 IS NOT SIGNED, SEALED & DATED AS REQUIRED
 IN SECTION 106.1 & FLORIDA STATUTES.
  
 7. SHT A.01 NOTE STATES "DEMO PLAN SUBMITTED UNDER
 SEPARATE PERMIT". DEMO PERMIT NOT FOUND. PLEASE
 INDICATE THE DEMO PERMIT NUMBER FOR REFERENCE. SECTION
 106.1.2 & SECTION 704.5.
  
 8. SHTS A.01.1 & A.09 (DETAILS B/A.09 & C/A.09). SHOW
 THE 5 FOOT TURNING AREA, BACKING FOR THE GRAB BARS AT
 THE W/C AND SHOWER, INDICATE THE LOCATION OF THE
 CONTROLS IN THE SHOWER & SUBMIT A DETAIL FOR THE SHOWER
 CURB, (MAX 1/2" IF INSTALLED, NO CURB REQUIRED).
 SECTIONS 11-4.1.3(11), 11-4.16.4, 11-4.21.4, 11-4.21.5
 & 11-4.21.7.
  
 9. SHT A.01.1 & A.09 (DETAILS A/A.09, E/A.09, 1/A.09,
 2/A.09, 3/A.09 & 4/A.09). SHOW COMPLIANCE WITH THE
 FOLLOWING:
  
 ___FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.4 GRAB BARS (INDICATED AS 3'6" AFF IN
 DETAILS 2 & 4.
 C. 11-4.16.5 FLUSH CONTROLS
  
 ___FOR LAVS:
 A. 11-4.19.2 CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
  
 10. SHT A.01.1 & A.09 (DETAILS D/A.09, 8/A.09 &
 9/A.09). THE BATHROOM SHALL BE ACCESSIBLE. PLEASE SHOW
 COMPLIANCE WITH THE FOLLOWING:
  
 ___FOR W/C:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS
 D. 11-4.16.5 FLUSH CONTROLS
 E. 11-4.16.6 DISPENSERS
  
 ___FOR LAV:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE - FORWARD APPROACH
 REQUIRED (FIG 32)
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
 E. 11-4.19.6 MIRRORS
  
 ___FOR SHOWER:
 A. 11-4.21.2 SIZE & CLEARANCES
 B. 11-4.21.3 SEAT
 C. 11-4.21.4 GRAB BARS
 D. 11-4.21.5 CONTROLS
 E. 11-4.21.6 SHOWER UNIT
 F. 11-4.21.7 CURBS
  
 11. SHTS A.01 & P.11 (DETAILS 3/A.11 & A/A.11). TOILET
 ROOM SHALL BE ACCESSIBLE. PLEASE SHOW COMPLIANCE WITH
 THE FOLLOWING:
  
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH
 REQUIRED - CABINET DOORS NOT APPROVED)
 C. 11-4.24.7 FAUCET
  
 12. ALL SHEETS WITH ROCAMAR ENGINEERING SERVICES INC.
 TITLE BLOCK. THE ADDRESS ON THE TITLE BLOCK DOES NOT
 REFLECT THE ADDRESS OF RECORD ON THE STATE OF FLORIDA
 DBPR WEBSITE. (SEE ATTACHED SHEET). PLEASE UPDATE THE
 TITLE BLOCKS OR THE DBPR WEBSITE PRIOR TO RESUBMITTING
 FOR REVIEW SO THE ADDRESS CORRELATES. FAC
 61G15-23.002(2) & FS 471.025.
  
 13. SHT P-1 MACERATING UNIT. SUBMIT MANUF
 SPECIFICATIONS & INSTALLATION INSTRUCTIONS. NOTE
 INDICATES SEE DETAIL ON SHEET P-3, BUT THE DETAIL JUST
 SHOWS A WEBSITE AND THE WEBSITE WILL NOT OPEN. SECTIONS
 106.1.2 & 712.4.1.
  
 14. SHT P-1 SHOWS AN OIL INTERCEPTOR. THE OIL
 INTERCEPTOR SHALL BE SIZED BY THE UTILITY DEPT.
 INDUSTRIAL PRETREATMENT. PLEASE CONTACT HOLLY MCGRATH
 LABORATORY SUPERVISOR BY PHONE, (561) 822-2271 - OR
 FAX, (561) 822-2279 - OR E-MAIL, [email protected].
 ARTICLE III SECTION 90-124(7).
  
 15. SHT P-1 SHOWS THE GAS LINE TO THE EMERGENCY
 GENERATOR. THE NOTE INDICATES 20 PSI REQUIRED. PLEASE
 CLARIFY. SUBMIT MANUF. SPECIFICATION SHEETS AS WELL AS
 INSTALLATION SHEETS FOR THE GENERATOR SHOWING A LISTING
 FOR THE GENERATOR, INLET PRESSURE & BTU LOAD FOR THE
 GENERATOR. SEPARATE GENERATOR PERMIT REQUIRED. FBC-2004
 FUEL GAS DOES NOT HAVE A TABLE FOR 20 PSI. PLEASE
 SUBMIT AN APPROVED GAS PIPE SIZING TABLE FOR 20 PSI.
 SECTION 402.
  
 16. SHT P-1 CLEANOUTS ARE REQUIRED PER SECTION 708.3.2,
 NOT MORE THAN 100 FEET IN BUILDING SEWERS AND PER
 SECTION 708.3.5 NEAR THE JUNCTION OF THE BUILDING DRAIN
 AND THE BUILDING SEWER. PLEASE SHOW ON THE FLOOR PLAN
 AND ON THE SANITARY RISER DIAGRAM.
  
 17. SHT P-1 SHOWS 1-1/2" MAKE UP WATER TO THE 2ND FLOOR
 MECHANICAL, 1-1/2" MAKE UP WATER FOR SYSTEM FILLING &
 1" HOT WATER FOR ICE MELTING. PLEASE INDICATE THE
 METHOD OF BACKFLOW PROTECTION OF EACH SUPPLY LINE PER
 SECTIONS 608.1 & 608.3. ALSO AN RPZV BACKFLOW IS
 REQUIRED ON THE WATER SERVICE TO THE BUILDING PER
 SECTION 608.13.2. PLEASE INDICATE ON THE PLANS AND ON
 THE WATER ISOMETRIC RISER DIAGRAM SHEET P-7.
  
 18. SHT P-2 PIPING ARRANGEMENT AT THE WATER HEATER.
 PLEASE INDICATE WHERE THE T&P RELIEF VALVE TERMINATES.
 SECTION 504.6.1 -- INDICATE THE MANUFACTURE AND MODEL
 NUMBER FOR THE EXPANSION TANK. SUBMIT CALCULATIONS OR
 MANUF. CHART FOR SIZING THE EXPANSION TANK. SECTION
 607.3.2.
  
 19. SHT P-3 ICE MELTING PIT DRAINAGE DETAIL. PER
 SECTION 712.2 A FULL OPEN VALVE IS REQUIRED ON THE
 DISCHARGE SIDE OF THE CHECK VALVE. -- THE DETAIL
 APPEARS TO SHOW A REDUCTION IN PIPE SIZE IN THE
 DIRECTION OF FLOW. THIS IS NOT APPROVED PER SECTION
 704.2. PLEASE CLARIFY.
  
 20. SHT P-5 INDICATE THE MANUFACTURE AND MODEL NUMBER
 FOR THE EXPANSION TANK. SUBMIT CALCULATIONS OR MANUF.
 CHART FOR SIZING THE EXPANSION TANK. SECTION 607.3.2.
  
 21. SHT P-5 THE GAS PIPING, (1-1/2") TO THE GENERATOR
 DOES NOT REFLECT THE GAS PIPING SIZE INDICATED ON SHT
 P-1, (1"). PLEASE CORRELATE. SECTION 402.
  
 22. SHT P-5 SEPARATE GAS PERMIT IS REQUIRED. PLEASE
 SUBMIT THE FOLLOWING INFORMATION FOR EACH GAS SYSTEM:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. (PIPE LENGTHS NOT INDICATED).
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. (20 PSI ON SHT P-1
 BUT .5 PSI ON SHT P-5) CLARIFY EACH SYSTEM.
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 **PLEASE SHOW "GAS PIPING SIZED ON FOLLOWING" FOR EACH
 METER/SYSTEM.
  
 23. SHT P-7 PLUMBING WATER ISOMETRIC RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. THE WATER SUPPLY PIPING TO
 W/C & LAV IN THE TOILET ROOM BY THE ICE PIT ARE NOT
 SHOWN ON THE ISOMETRIC. PLEASE CORRELATE. SECTIONS
 106.1.1 & 604. -- A SHUT OFF VALVE IS REQUIRED ON THE
 SUPPLY LINE TO THE HOSE BIBB BY THE EQUIPMENT ROOM.
 SECTION 606.2(2).
  
 24. SHT P-7 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM.
 THE FLOOR DRAIN IN THE ROOM ADJACENT TO THE MOP SINK
 ROOM SHALL HAVE A TRAP PRIMER. SECTION 1002.4.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  