| 2008-10-22 12:26:39 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | |
| | 1) MECHANICAL PLANS M-1 AND M-2 ARE SHOWING DUCTS |
| | PENETRATING THE 1-HR RATED EGRESS CORRIDOR (SEE PLAN |
| | LS.01), AT THE WEST SIDE OF THE BUILDING. PER 2004 FBC |
| | 607.5.4 CORRIDORS/SMOKE BARRIERS. A LISTED SMOKE DAMPER |
| | DESIGNED TO RESIST THE PASSAGE OF SMOKE SHALL BE |
| | PROVIDED AT EACH POINT A DUCT OR AIR TRANSFER OPENING |
| | PENETRATES A SMOKE BARRIER WALL OR A CORRIDOR ENCLOSURE |
| | REQUIRED TO HAVE SMOKE AND DRAFT CONTROL DOORS IN |
| | ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING. |
| | SMOKE DAMPERS AND SMOKE DAMPER ACTUATION METHODS SHALL |
| | COMPLY WITH SECTION 607.5.4.1. ALSO SEE 2004 FBC |
| | 715.3.3. |
| | |
| | 2) PLANS SHOW THE DUCTS ALSO PENETRATE FIRE PARTITIONS, |
| | PLEASE SHOW ON PLANS HOW THE PENETRATIONS ARE BEING |
| | PROTECTED, PER 2004 FBC/M 607.5.3. |
| | |
| | 3) PLEASE PROVIDE FOR RETURN AIR TO THE FIRST AID ROOM |
| | AND BRAKE ROOM ON PLAN M-2, PER 2004 FBC/M 601.4. |
| | |
| | 4) PLEASE SHOW ON PLANS HOW THE ZAMBONI STORAGE ROOM |
| | WILL COMPLY WITH 2004 FBC/M 404 ENCLOSED PARKING |
| | GARAGES. |
| | |
| | 5) SHOW ON PLANS FOR EQUIPMENT ROOM, COMPLIANCE WITH |
| | 2004 FBC/M 1104.2, 1105 MACHINERY ROOM AND 1106. |
| | |
| | 6) THE TWO CARRIER A/C SYSTEM MODEL NUMBERS LISTED ON |
| | THE A/C EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE |
| | ARI DIRECTORY WEB-SITE, PLEASE CORRECT, SUBMIT AN ARI |
| | CERTIFICATE OR MANUFACTURE SPEC. SHEETS, PER 2004 FBC |
| | 13-407.1.ABC.3.1.1 OR 13-607.1.ABC.3.1.1. |
| | |
| | 7) ONLY ONE OF THE CARRIER A/C SPLIT SYSTEMS ARE LISTED |
| | ON THE ENERGY CAL'S. PLEASE CORRECT PER 2004 FBC |
| | 13-103.3. |
| | |
| | 8) THE ARCHITECT OR ENGINEER OF RECORD NEED TO REVIEW |
| | AND APPROVE THE SHOP DRAWINGS FROM BRR TECHNOLOGIES (A |
| | SHOP REVIEW STAMP AND SIGNATURE WILL MEET THIS |
| | REQUIREMENT), SEE 2004 WPB AMEND. 106.3. |
| | |
| | 9) PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR RUSKIN |
| | LOUVERS, SEE FS 553.842(1) AND FAC RULE 9B-72, |
| | 9B-72.005, AND FAC 9B-72.010(31)(H). |
| | |
| | **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG. |
| | |
| | *** PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW STAMP AND |
| | SIGNATURE WILL MEET THIS REQUIREMENT). SEE W.P.B. |
| | AMEND. 106.3. |
| | |