Plan Review Notes
Plan Review Notes For Permit 08090611
Permit Number 08090611
Review Stop M
Sequence Number 1
Notes
Date Text
2008-10-22 12:26:39PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) MECHANICAL PLANS M-1 AND M-2 ARE SHOWING DUCTS
 PENETRATING THE 1-HR RATED EGRESS CORRIDOR (SEE PLAN
 LS.01), AT THE WEST SIDE OF THE BUILDING. PER 2004 FBC
 607.5.4 CORRIDORS/SMOKE BARRIERS. A LISTED SMOKE DAMPER
 DESIGNED TO RESIST THE PASSAGE OF SMOKE SHALL BE
 PROVIDED AT EACH POINT A DUCT OR AIR TRANSFER OPENING
 PENETRATES A SMOKE BARRIER WALL OR A CORRIDOR ENCLOSURE
 REQUIRED TO HAVE SMOKE AND DRAFT CONTROL DOORS IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING.
 SMOKE DAMPERS AND SMOKE DAMPER ACTUATION METHODS SHALL
 COMPLY WITH SECTION 607.5.4.1. ALSO SEE 2004 FBC
 715.3.3.
  
 2) PLANS SHOW THE DUCTS ALSO PENETRATE FIRE PARTITIONS,
 PLEASE SHOW ON PLANS HOW THE PENETRATIONS ARE BEING
 PROTECTED, PER 2004 FBC/M 607.5.3.
  
 3) PLEASE PROVIDE FOR RETURN AIR TO THE FIRST AID ROOM
 AND BRAKE ROOM ON PLAN M-2, PER 2004 FBC/M 601.4.
  
 4) PLEASE SHOW ON PLANS HOW THE ZAMBONI STORAGE ROOM
 WILL COMPLY WITH 2004 FBC/M 404 ENCLOSED PARKING
 GARAGES.
  
 5) SHOW ON PLANS FOR EQUIPMENT ROOM, COMPLIANCE WITH
 2004 FBC/M 1104.2, 1105 MACHINERY ROOM AND 1106.
  
 6) THE TWO CARRIER A/C SYSTEM MODEL NUMBERS LISTED ON
 THE A/C EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE
 ARI DIRECTORY WEB-SITE, PLEASE CORRECT, SUBMIT AN ARI
 CERTIFICATE OR MANUFACTURE SPEC. SHEETS, PER 2004 FBC
 13-407.1.ABC.3.1.1 OR 13-607.1.ABC.3.1.1.
  
 7) ONLY ONE OF THE CARRIER A/C SPLIT SYSTEMS ARE LISTED
 ON THE ENERGY CAL'S. PLEASE CORRECT PER 2004 FBC
 13-103.3.
  
 8) THE ARCHITECT OR ENGINEER OF RECORD NEED TO REVIEW
 AND APPROVE THE SHOP DRAWINGS FROM BRR TECHNOLOGIES (A
 SHOP REVIEW STAMP AND SIGNATURE WILL MEET THIS
 REQUIREMENT), SEE 2004 WPB AMEND. 106.3.
  
 9) PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR RUSKIN
 LOUVERS, SEE FS 553.842(1) AND FAC RULE 9B-72,
 9B-72.005, AND FAC 9B-72.010(31)(H).
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 *** PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW STAMP AND
 SIGNATURE WILL MEET THIS REQUIREMENT). SEE W.P.B.
 AMEND. 106.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]