2008-10-01 14:22:54DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS WITH ROCAMAR ENGINEERING SERVICES INC.
 TITLE BLOCK. THE ADDRESS ON THE TITLE BLOCK DOES NOT
 REFLECT THE ADDRESS OF RECORD ON THE STATE OF FLORIDA
 DBPR WEBSITE. (SEE ATTACHED SHEET). PLEASE UPDATE THE
 TITLE BLOCKS OR THE DBPR WEBSITE PRIOR TO RESUBMITTING
 FOR REVIEW SO THE ADDRESS CORRELATES. FAC
 61G15-23.002(2) & FS 471.025.
  
 2. SHT P-1 SHOWS THE GAS LINE TO THE EMERGENCY
 GENERATOR. THE NOTE INDICATES 20 PSI REQUIRED. PLEASE
 CLARIFY. SUBMIT MANUF. SPECIFICATION SHEETS AS WELL AS
 INSTALLATION SHEETS FOR THE GENERATOR SHOWING A LISTING
 FOR THE GENERATOR, INLET PRESSURE & BTU LOAD FOR THE
 GENERATOR. SEPARATE GENERATOR PERMIT REQUIRED. FBC-2004
 FUEL GAS DOES NOT HAVE A TABLE FOR 20 PSI. PLEASE
 SUBMIT AN APPROVED GAS PIPE SIZING TABLE FOR 20 PSI.
 SECTION 402.
  
 3. SHT P-5 THE GAS PIPING, (1-1/2") TO THE GENERATOR
 DOES NOT REFLECT THE GAS PIPING SIZE INDICATED ON SHT
 P-1, (1"). PLEASE CORRELATE. SECTION 402.
  
 4. SHT P-5 SEPARATE GAS PERMIT IS REQUIRED. PLEASE
 SUBMIT THE FOLLOWING INFORMATION FOR EACH GAS SYSTEM:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. (PIPE LENGTHS NOT INDICATED).
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. (20 PSI ON SHT P-1
 BUT .5 PSI ON SHT P-5) CLARIFY EACH SYSTEM.
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 **PLEASE SHOW "GAS PIPING SIZED ON FOLLOWING" FOR EACH
 METER/SYSTEM.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  