| 2008-10-28 19:47:34 | *****DENIED***** |
| | |
| | 01. THE ADDRESS NUMBER (1590) SHOWN IN THE THE TILE |
| | BLOCK OF EACH SUBMITTED PLAN SHEET DOES NOT CORRELATE |
| | WITH THE ADDRESS NUMBER (1600) AS LISTED ON YOUR |
| | APPLICATION OR IN OUR SYSTEM. |
| | |
| | 02. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 03. THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE |
| | WITH EMERGENCY ACCESS TO THE SAID PROPERTY OR THE |
| | VIOCINITY THEREOF INCLUDING STREETS, ALLEYS, FIRE |
| | LANES, ETC. |
| | |
| | 04. ONLY ONE FIRE HYDRANT IS SHOWN ON SHEET LP-1, SRE |
| | ANY ADDITIONAL FIRE HYDRANTS PROPOSED ON THIS |
| | CAMPUS/SITE? IF NOT, EXPLAIN RATIONALE. |
| | |
| | 05. IS THIS PROPOSED STRUCTURE A CHANGE OF OCCUPANCY? |
| | |
| | 06. IT APPEARS THAT THE BUILDING IS SET OFF OF THE |
| | ADDRESSED NORTH FLORIDA MANGO ROAD. HOW WILL EMERGENCY |
| | RESPONDERS AND/OR THE PUBLIC LOCATE THIS STRUCTURE? |
| | |
| | 07. SHOW/DISPLAY THE APPROPIATE EXTERIOR ELEVATION THE |
| | NUMERICAL ADDRESS ON THE STRUCTURE OF THE BUILDING. AS |
| | PER WEST PALM BEACH CODE, THE NUMBERS SHALL BE NO LESS |
| | THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH/STROKE. |
| | |
| | 08. PROVIDE THE PRESCRIPTIVE STRENGHTS FOR THE STAIRS' |
| | HANDRAILS/GUARDRAILS. |
| | |
| | 09. SPECIFY THE INTERIOR WALL AND CEILING FINISH |
| | MATERIAL IN TERMS OF CLASS A, CLASS B, OR CLASS C. |
| | |
| | 10. FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA 80. |
| | |
| | 11. WHAT IS THE OCCUPANT LOAD FOR THE PROPOSED |
| | STRUCTURE? |
| | |
| | 12. NFPA 13 2002 EDITION SHALL BE REFERENCED. REVISE |
| | NOTE 21 ON SHEET FP-1 TO REFLECT AS SUCH. |
| | |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |