Plan Review Notes
Plan Review Notes For Permit 08090611
Permit Number 08090611
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-10-28 19:47:34*****DENIED*****
  
 01. THE ADDRESS NUMBER (1590) SHOWN IN THE THE TILE
 BLOCK OF EACH SUBMITTED PLAN SHEET DOES NOT CORRELATE
 WITH THE ADDRESS NUMBER (1600) AS LISTED ON YOUR
 APPLICATION OR IN OUR SYSTEM.
  
 02. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03. THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY ACCESS TO THE SAID PROPERTY OR THE
 VIOCINITY THEREOF INCLUDING STREETS, ALLEYS, FIRE
 LANES, ETC.
  
 04. ONLY ONE FIRE HYDRANT IS SHOWN ON SHEET LP-1, SRE
 ANY ADDITIONAL FIRE HYDRANTS PROPOSED ON THIS
 CAMPUS/SITE? IF NOT, EXPLAIN RATIONALE.
  
 05. IS THIS PROPOSED STRUCTURE A CHANGE OF OCCUPANCY?
  
 06. IT APPEARS THAT THE BUILDING IS SET OFF OF THE
 ADDRESSED NORTH FLORIDA MANGO ROAD. HOW WILL EMERGENCY
 RESPONDERS AND/OR THE PUBLIC LOCATE THIS STRUCTURE?
  
 07. SHOW/DISPLAY THE APPROPIATE EXTERIOR ELEVATION THE
 NUMERICAL ADDRESS ON THE STRUCTURE OF THE BUILDING. AS
 PER WEST PALM BEACH CODE, THE NUMBERS SHALL BE NO LESS
 THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH/STROKE.
  
 08. PROVIDE THE PRESCRIPTIVE STRENGHTS FOR THE STAIRS'
 HANDRAILS/GUARDRAILS.
  
 09. SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIAL IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 10. FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA 80.
  
 11. WHAT IS THE OCCUPANT LOAD FOR THE PROPOSED
 STRUCTURE?
  
 12. NFPA 13 2002 EDITION SHALL BE REFERENCED. REVISE
 NOTE 21 ON SHEET FP-1 TO REFLECT AS SUCH.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722