| 2008-10-27 09:38:25 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED |
| | PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD. PLEASE CALL |
| | 561-233-5025 FOR MORE INFORMATION. THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE |
| | PERMIT APPLICATION. |
| | |
| | 2. FBC EB301.5, A DESIGN PROFESSIONAL MUST ELECT ONE OR |
| | A COMBINATION OF LEVELS OF ALTERATION. |
| | |
| | 3. NOTE ANY CHANGE OF OCCUPANCY ON THE PLAN IF |
| | APPLICABLE, FBC EB CHAPTER 8. DECLARE CURRENT |
| | (EXISTING) AND PROPOSED OCCUPANCY AND HAZARD CATEGORY |
| | FOR LIFE SAFETY AND EXITS, HEIGHT AND AREA, EXPOSURE OF |
| | EXTERIOR WALLS FBC EB TABLES 812.4.1, 812.4.2, 812.4.3. |
| | REQUIREMENTS CANNOT BE DETERMINED DUE TO INSUFFICIENT |
| | INFORMATION PROVIDED. |
| | |
| | 4. ADDITIONS ARE TO COMPLY WITH FBC EB 9. PLEASE NOTE |
| | ON PLAN CV01. |
| | |
| | 5. SHOW THE DISTANCE FROM THE PROPERTY LINE TO THE |
| | BUILDING(S), FBC 507, FBC 6, FBC EB 8. PLEASE REVISE |
| | THE SITE PLAN SP01 TO INCLUDE THE REQUIRED INFORMATION. |
| | |
| | 6. A01 SPECIFIES WP1200 WALL; PROVIDE A DETAIL FBC 7, |
| | FBC*106. |
| | |
| | 7. CV01 STATES THAT OFFICES, STORAGE, AND MERCANTILE |
| | AREAS ARE ACCESSORY. DECLARE TOTAL SQUARE FOOT AREA FOR |
| | EACH FBC 5. |
| | |
| | 8. CV01 STATES THAT THIS BUILDING IS TYPE IIIB, 1 HOUR |
| | FOR EXTERIOR BEARING WALLS. SEE FBC TABLE 601, 2 HOUR |
| | REQUIRED FOR EXTERIOR BEARING WALLS TYPE IIIB. PLEASE |
| | CLARIFY BUILDING TYPE. PROVIDE A DETAIL FOR THE |
| | EXISTING EXTERIOR BEARING WALLS TO CLARIFY BUILDING |
| | TYPE. |
| | |
| | 9. NOTE ALL REQUIRED FIRE RATED WALLS ON THE PLAN. |
| | OPENING AND PENETRATION PROTECTION REQUIREMENTS, ETC. |
| | ARE NOT READILY APPARENT WITHOUT THIS INFORMATION FBC7. |
| | |
| | 10. DECLARE OCCUPANT LOAD FBC 1004. |
| | |
| | 11. FBC1004.3, OCCUPANT LOAD TO BE POSTED. PROVIDE A |
| | DETAIL AND LOCATION ON THE PLAN. |
| | |
| | 12. SP01 SHOWS THREE DIFFERENT BUILDINGS. PLEASE SEE |
| | FBC TABLE 503, FBC TABLE 601, FBC TABLE 602. DO FIRE |
| | WALLS EXIST SEPARATING THESE BUILDINGS OR ARE THEY ONE |
| | BUILDING FOR PURPOSES OF FBC CHAPTERS 5 AND 6? AN |
| | OPENING IS SHOWN BETWEEN THE NORTH AND CENTER |
| | BUILDINGS; SEE FBC TABLE 704.8, NO OPENINGS PERMITTED |
| | WITH A SEPARATION OF 0 TO 3 FEET. |
| | |
| | 13. A.01 SHOWS A NEW DEMISING WALL ADJACENT TO AN |
| | EXISTING WALL. DOESN?T THIS CREATE A LARGE CONCEALED |
| | SPACE? |
| | |
| | 14. CV01, DECLARE TOTAL SQUARE FOOT AREA FOR THE |
| | BUILDING OR BUILDINGS (SEE OTHER COMMENTS), FBC5, FBC6, |
| | FBC EB8. |
| | |
| | 15. CV01, PROVIDE TOTAL SQUARE FOOT AREAS FOR THE |
| | PROPOSED MEZZANINES AS WELL AS OCCUPANCY CLASSIFICATION |
| | FOR THE USE OF THESE SPACES, FBC 3, FBC10, FBC11. |
| | |
| | 16. THE MEZZANINE AREAS MUST MEET THE DEFINITION |
| | FBC502. PLEASE DEMONSTRATE COMPLIANCE ON THE PLAN. |
| | |
| | 17. THERE IS A STATEMENT, UPPER LEVEL FLOOR PLAN, A.03, |
| | TOP LEFT, ?COORDINATE EXTENTS WITH FIRST FLOOR PLAN.? |
| | WHAT DOES THIS MEAN? WHAT ARE EXTENTS? |
| | |
| | 18. AS THIS IS A THRESHOLD BUILDING AS DEFINED IN |
| | FS553.71(7), PLEASE ARRANGE WITH KEN CONRAD, CHIEF |
| | BUILDING INSPECTOR, 561-805-6666, A MEETING INVOLVING |
| | THE OWNER, SPECIAL INSPECTOR, JOB INSPECTOR, CONTRACTOR |
| | AND ENGINEER. THIS MUST BE DONE PRIOR TO PERMIT |
| | ISSUANCE. THREE ORIGINAL SETS OF ALL DOCUMENTS ARE |
| | REQUIRED FOR PERMITTING AND FOR ALL SUBSEQUENT |
| | SUBMITTALS. SEE FBC*109.3.6, FS553.79(5)(A). |
| | |
| | 19. PROVIDE A STRUCTURAL INSPECTION PLAN FOR THIS |
| | THRESHOLD BUILDING, FBC*109.3.6, FS553.79(5)(A). |
| | |
| | 20. SEE FBC*109.3.6.4.4, FS553.79(7)(D) AND INCLUDE THE |
| | STATEMENT ATTESTING TO COMPLIANCE. |
| | |
| | 21. FBC*109.3.6.4, THRESHOLD INSPECTOR IS TO BE |
| | APPROVED BY KEN CONRAD, CHIEF BUILDING INSPECTOR. A |
| | COPY OF THE CONTRACT IS TO BE INCLUDED IN THE PERMIT |
| | PACKAGE. THIS IS REQUIRED PRIOR TO PERMIT ISSUANCE, |
| | FS553.79. |
| | |
| | 22. PLANS ARE TO BE SIGNED, SEALED, AND DATED FS481. |
| | PLEASE INCLUDE A DATE ON THE SEAL. |
| | |
| | 23. SEE FP1, FBC 35, INCORRECT NFPA13 VERSION |
| | REFERENCED; PLEASE REVISE. |
| | |
| | 24. SEE FP1, INCORRECT BUILDING CODE DECLARED. PLEASE |
| | REVISE. |
| | |
| | 25. FP SHEETS DO NOT HAVE A FIRE SPRINKLER PLAN FOR THE |
| | MEZZANINE AREAS. |
| | |
| | 26. A01. SPECIFY FIRE RATING (TIME) REQUIRED FOR THE |
| | WP1200 WALL, SOUTH SIDE. |
| | |
| | 27. FBC13-101.3, BUILDING SHALL COMPLY WITH FBC13-4. |
| | |
| | 28. WALL TYPE W4B IS NOT INCLUDED IN THE LEGEND A01. |
| | SEE FBC TABLE 1016.1, MINIMUM OF 1 HOUR REQUIRED FOR |
| | THIS CORRIDOR. |
| | |
| | 29. WALL TYPE NOT SPECIFIED FOR THE WALL AT DOORS 3A |
| | AND 3B. |
| | |
| | 30. A03, EGRESS NOT CLEAR FOR THE UPPER LEVEL, WEST |
| | SIDE. PROVIDE A LIFE SAFETY PLAN. |
| | |
| | 31. SHOW VERTICAL ACCESSIBILITY, UPPER LEVEL. IF AN |
| | EXCEPTION APPLIES, COMPLIANCE MUST BE SHOWN ON THE |
| | PLAN. |
| | |
| | 32. C A08, EXTENSION SHOWN AT THE BOTTOM OF THE STAIR |
| | WHICH IS NOT SHOWN ON THE DETAIL 5 A08. PLEASE REVISE 5 |
| | A08, FBC 11 4.9.4(2). |
| | |
| | 33. A03, AS CANOPY INFORMATION WAS NOT PROVIDED, A |
| | SEPARATE PERMIT WILL BE REQUIRED (INFORMATIONAL ONLY). |
| | |
| | 34. PROVIDE MORE INFORMATION REGARDING THE UPPER LEVEL |
| | AREAS. SEE FBC505.5, INDUSTRIAL EQUIPMENT PLATFORMS ARE |
| | NOT TO BE A PART OF ANY MEZZANINE. ALSO DECLARE |
| | OCCUPANCY CLASSIFICATION FOR THESE AREAS, FBC CHAPTER |
| | 3. |
| | |
| | 35. A10, THE SPECIFY FIRE DOOR RATING IN TIME RATHER |
| | THAN LETTER, FBC TABLE 715.3. |
| | |
| | 36. SOILS REPORT, ALL INFORMATION REQUIRED BY |
| | FAC61G15-23.002(2) REQUIRED (CERTIFICATE OF |
| | AUTHORIZATION). PLEASE NOTE THAT THIS REQUIREMENT HAS |
| | RECENTLY BEEN REVISED. |
| | |
| | 37. SEE ENERGY CALCS; NO DOORS SHOWN, ICE RINK FLOOR IS |
| | SHOWN AS CARPET. PLEASE REVISE THESE ITEMS AND CHECK |
| | ALL INFORMATION ON THE ENERGY CALC INPUT DATA REPORT. |
| | |
| | 38. PLEASE HAVE THE ARCHITECT SIGN THE ENERGY CALC, |
| | FBC103.1.1.1. IF A TYPED NAME IS PROVIDED IN LIEU OF A |
| | SIGNATURE, PLEASE CONFIRM THAT ALL RELEVANT INFORMATION |
| | (INCLUDE THE EXISTING COMPONENTS, SUCH AS EXISTING |
| | INSULATION) IS INCLUDED. |
| | |
| | |
| | |
| | |