| 2008-10-29 11:07:15 | GAS PLAN REVIEW: |
| | DENIED **2ND TIME: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | **THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND |
| | WITH THE PREVIOUS GAS REVIEW COMMENTS AS WELL AS THE |
| | DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW |
| | COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW |
| | COMMENTS. |
| | |
| | 1. PLEASE SUBMIT A DETAIL OF HOW THE 1000 GAL. A/G |
| | PROPANE TANK IS TO BE ANCHORED TO MEET 140 MPH WIND |
| | LOAD PER FBC-2004 BUILDING CHAPTER 16, SECTION 1603.1.4 |
| | WIND DESIGN DATA AND SECTION 1609.1.3 ANCHORAGE AGAINST |
| | OVERTURNING, UPLIFT AND SLIDING. |
| | NOTE: PLEASE KNOW THAT THE INSTALLATION OF THE |
| | HORIZONTAL ABOVEGROUND ASME CONTAINER SHALL ALSO BE |
| | COMPLIANT WITH NFPA CHAPTER 58, SECTION |
| | 6.6.3.1.(A),(B),(D),(E). |
| | |
| | **RESPONSE NOTED, HOWEVER THE SUBMITTED TIE DOWN DETAIL |
| | IS HARD TO READ. PLEASE SUBMIT TWO COPIES OF A LEGIBLE |
| | DETAIL. |
| | |
| | 2. PER THE SUBMITTED SITE PLAN THERE APPEARS TO BE 15 |
| | CRASH POSTS BEING INSTALLED TO PROTECT THE 1000 GAL. |
| | A/G PROPANE TANK. PLEASE CLARIFY IF THIS IS CORRECT AND |
| | PROVIDE A DETAIL OF THE CRASH POSTS AND THEIR |
| | INSTALLATION. PER (W.P.B. AS AMENDED) SECTION 106.1.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | **NO RESPONSE ON THE RESUBMITTED SITE PLAN AND THE |
| | RESUBMITTED SITE PLAN STILL DOES NOT CLARIFY EXACTLY |
| | HOW MANY CRASH POSTS ARE BEING INSTALLED. RESPONSE |
| | NOTED ON THE CRASH POST DETAIL, HOWEVER THE WRITTING |
| | LOCATED AT THE TOP OF THE DETAIL IS NOT LEGIBLE. PLEASE |
| | SUBMIT TWO COPIES OF THE CRASH POST DETAIL THAT ARE |
| | LEGIBLE. |
| | |
| | **THE FOLLOWING IS A NEW COMMENT. |
| | |
| | 3. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| | SECTION *106.3.4.3. THE SUBMITTED TANK TIE DOWN DETAIL |
| | IS A COPIED SIGNATURE AND THERE IS NOBODY TAKING THE |
| | RESPONSIBILITY FOR THE SITE PLAN OR THE CRASH POST |
| | DETAIL. THE PERSON TAKING RESPOSOBILITY FOR THE PLANS |
| | AND DETAILS MUST PRINT NAME WITH ORIGINAL SIGNATURE AND |
| | DATE SAID INFORMATION. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |