| Plan Review Notes For Permit 08090607 |
| Permit Number |
08090607 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-10-29 12:06:37 | *****DENIED***** | | | | | | PLEASE BE ADVISED THAT THE UPDATED PLANS/SHOP DRAWINGS | | | ARE TO BE SUBMITTED WITH NO INK, PENCIL, OR ANY OTHER | | | HAND-DRAWN MARKINGS | | | | | | | | | 1. THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK OF | | | THE SUBMITTED PLAN SHEET(S). | | | | | | 2. SHOW THE LOCATION OF THE PORTABLE FIRE | | | EXTINGUISHER(S) HAVING A MINIMUM CAPACITY OF 18 LBS DRY | | | CHEMICAL WITH B-C RATING LOCATED NO MORE THAN 50 FEET | | | FROM THE STORAGE LOCATION. | | | | | | 3. PROVIDE SPECIFICATIONS/DOCUMENTS TO VERIFY THAT THE | | | CONTAINER IS DESIGNED, FABRICATED, TESTED, AND MARKED | | | (OR STAMPED) IN ACCORDANCE WITH DOT AND/OR ASME. | | | | | | 4. PLEASE SHOW/DISPLAY HOW THE CONTAINER(CYLINDER SHALL | | | BE MARKED AS PROVIDED IN THE REGULATIONS AND CODES OF | | | WHICH IT IS FABRICATED. | | | | | | 5. PLEASE EXPLAIN HOW VENTING OF THE TANK WILL BE | | | ACCOMPLISHED. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET | | | EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | |
|