2008-09-26 15:35:39GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. PLEASE SUBMIT A DETAIL OF HOW THE 1000 GAL. A/G
 PROPANE TANK IS TO BE ANCHORED TO MEET 140 MPH WIND
 LOAD PER FBC-2004 BUILDING CHAPTER 16, SECTION 1603.1.4
 WIND DESIGN DATA AND SECTION 1609.1.3 ANCHORAGE AGAINST
 OVERTURNING, UPLIFT AND SLIDING.
 NOTE: PLEASE KNOW THAT THE INSTALLATION OF THE
 HORIZONTAL ABOVEGROUND ASME CONTAINER SHALL ALSO BE
 COMPLIANT WITH NFPA CHAPTER 58, SECTION
 6.6.3.1.(A),(B),(D),(E).
  
 2. PER THE SUBMITTED SITE PLAN THERE APPEARS TO BE 15
 CRASH POSTS BEING INSTALLED TO PROTECT THE 1000 GAL.
 A/G PROPANE TANK. PLEASE CLARIFY IF THIS IS CORRECT AND
 PROVIDE A DETAIL OF THE CRASH POSTS AND THEIR
 INSTALLATION. PER (W.P.B. AS AMENDED) SECTION 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]