2008-10-09 15:35:33*****DENIED*****
  
  
 1. THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK OF
 THE SUBMITTED PLAN SHEET(S).
  
 2. SHOW THE LOCATION OF THE PORTABLE FIRE
 EXTINGUISHER(S) HAVING A MINIMUM CAPACITY OF 18 LBS DRY
 CHEMICAL WITH B-C RATING LOCATED NO MORE THAN 50 FEET
 FROM THE STORAGE LOCATION.
  
 3. PROVIDE SPECIFICATIONS/DOCUMENTS TO VERIFY THAT THE
 CONTAINER IS DESIGNED, FABRICATED, TESTED, AND MARKED
 (OR STAMPED) IN ACCORDANCE WITH DOT AND/OR ASME.
  
 4. PLEASE SHOW/DISPLAY HOW THE CONTAINER(CYLINDER SHALL
 BE MARKED AS PROVIDED IN THE REGULATIONS AND CODES OF
 WHICH IT IS FABRICATED.
  
 5. PLEASE EXPLAIN HOW VENTING OF THE TANK WILL BE
 ACCOMPLISHED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  