| Plan Review Notes For Permit 08090596 |
| Permit Number |
08090596 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2009-01-10 10:13:17 | REVISED M1. NOTE: TRANSFER DUCTS IN SOME AREAS ARE NOT | | | SIZED TO MEET THE EXCEPTIONS UNDER FBCM 601.4. THESE | | | AREAS WILL REQUIRE A FIELD TEST TO VERIFY PRESSURE | | | DIFFERENCES ACROSS CLOSED DOORS ARE LESS THAN 0.01" WC | | | IN ACCORDANCE WITH THIS SECTION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|