| 2008-10-03 10:34:47 | |
| | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, |
| | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK |
| | MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002 |
| | FAC. |
| | |
| | 2} THIS PROJECT MUST COMPLY WITH CHAPTER 13 FBC. SEE |
| | 13-415.1ABC.1.1FOR TIME CLOCK REQUIREMENTS AND FOR |
| | LIGHTING DENSITIES. ALL THAT IS REQUIRED FOR THE |
| | ELECTRICAL REVIEW IS THE BASIC PRESCRIPTIVE |
| | REQUIREMENTS. SEE 13-415.2.ABC.1 PERFORMANCE |
| | CALCULATION PROCEDURES, GENERAL. |
| | THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR |
| | A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING |
| | SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD |
| | DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE |
| | METHOD DESCRIBED IN SECTION 415.2.B.1. THE INSTALLED |
| | INTERIOR LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH |
| | SECTION 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR |
| | LIGHTING POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH |
| | SECTION 415.2.C.1 OR 415.2.B.1. THIS CAN BE |
| | DEMONSTRATED ON THE PLANS INDICATING THE WATTAGES OF |
| | THE LUMINAIRES CHOSEN FOR THE PROJECT CONFORM TO THE |
| | DENSITY REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE |
| | SCHEDULE TO CORRELATE WITH THE ONES IN THE |
| | CALCULATIONS.THE PLAN INDICATES NEW LIGHTING. |
| | |
| | 3} THE PANEL SCHEDULE SCHEDULE MUST COMPLY WITH 408.4 |
| | AND BE ROOM SPECIFIC. |
| | |
| | 4} THE EMERGENCY LIGHTING MUST COMPLY WITH 700.12(F)-" |
| | THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE |
| | THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| | SWITCHES." A NOTE ON THE PLAN WILL SATISFY THIS |
| | REQUIREMENT. |
| | |
| | 5} THERE IS A RECEPTACLE SHOWN AT THE NEW WATER HEATER |
| | LOCATION. SEE 422.16 FLEXIBLE CORDS |
| | (A) GENERAL FLEXIBLE CORD SHALL BE PERMITTED (1) FOR |
| | THE CONNECTION OF APPLIANCES TO FACILITATE THEIR |
| | FREQUENT INTERCHANGE OR TO PREVENT THE TRANSMISSION OF |
| | NOISE OR VIBRATION OR (2) TO FACILITATE THE REMOVAL OR |
| | DISCONNECTION OF APPLIANCES THAT ARE FASTENED IN PLACE, |
| | WHERE THE FASTENING MEANS AND MECHANICAL CONNECTIONS |
| | ARE SPECIFICALLY DESIGNED TO PERMIT READY REMOVAL FOR |
| | MAINTENANCE OR REPAIR AND THE APPLIANCE IS INTENDED OR |
| | IDENTIFIED FOR FLEXIBLE CORD CONNECTION. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |