| Date |
Text |
| 2008-10-06 09:11:58 | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET P-2 GAS ISOMETRIC RISER DIAGRAM: SUBMIT AN |
| | ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL CUT SECTIONS |
| | OF PIPE AND CORRESPONDING LENGTHS PER FBC-2004 FUEL GAS |
| | CODE SECTION 401.1 SCOPE AND THE CITY OF WEST PALM |
| | BEACH GAS PERMIT APPLICATION REQUIREMENTS. |
| | *NOTE: THE SUBMITTED GAS ISOMETRIC ON SHEET P-2, DOES |
| | NOT INDICATE CORRESPONDING LENGTHS TO ALL CUT SECTION |
| | OF PIPE. PLEASE KNOW THE THE INDICATED LONGEST RUN FOR |
| | THE 0.5 PSI SYSTEM IS 70' HOWEVER THE ADDED SUM OF THE |
| | INDICATED CORRESPONDING LENGTHS IS 64' AND THAT NOT ALL |
| | CORRESPONDING LENGTHS ARE BEING INDICATED. THIS IS ALSO |
| | TRUE FOR THE 2 PSI SYSTEM, THE ADDED SUM OF THE |
| | INDICATED CORRESPONDING LENGTHS IS 125' AND THIS ALSO |
| | DOES NOT HAVE ALL CORRESPONDING LENGTHS BEING |
| | INDICATED. PLEASE KNOW IF THERE IS A CUT SECTION OF |
| | PIPE IT MUST HAVE A CORRESPONDING LENGTH INDICATED FOR |
| | IT. PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT |
| | SECTIONS WITH NO CORRESPONDING LENGTH BEING INDICATED |
| | FOR THEM. |
| | |
| | 2. SHEET P-2 GAS RISER DIAGRAM: PLEASE KNOW THAT TABLE |
| | 402.4 (4) IS THE WRONG TABLE FOR A 0.5 PSI NATURAL GAS |
| | DELIVERY PRESSURE. PLEASE KNOW THAT GAS TABLE 402.4 (4) |
| | IS FOR A 5 PSI NATURAL GAS DELIVERY PRESSURE NOT A 0.5 |
| | PSI NATURAL GAS DELIVERY PRESSURE. PLEASE KNOW THAT THE |
| | CORRECT TABLE FOR A 0.5 NATURAL GAS DELIVERY PRESSURE |
| | THAT NEEDS TO BE INDICATED ON THE RESUBMITTAL IS TABLE |
| | 402.4 (2). |
| | |
| | 3. SHEET A-2 PROPOSED FIRST FLOOR PLAN: THE 48" GAS |
| | RANGE IS INCORRECTLY BEING INDICATED AS A 48" REF. |
| | PLEASE CORRECT THIS ON THE RESUBMITTAL PER FBC-2004 |
| | FUEL GAS SECTION 401.1 SCOPE. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |