| 2008-10-02 14:10:52 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 |
| | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} AN EQUIPMENT GROUNDING CONDUCTOR MUST BE INSTALLED |
| | FROM THE FIRST MEANS OF DISCONNECT TO THE PANEL PER |
| | 250.118, SIZED PER 250.122. |
| | |
| | 2} PER 210.52(B)(2) NO OTHER OUTLETS THE TWO OR MORE |
| | SMALL-APPLIANCE BRANCH CIRCUITS SPECIFIED IN |
| | 210.52(B)(1) SHALL HAVE NO OTHER OUTLETS. PER |
| | 210.52(B)(1) CIRCUIT 35 PANEL "A", DINING ROOM IS |
| | REQUIRED TO BE A SMALL APPLIANCE CIRCUIT AND THEREFORE |
| | IS REQUIRED TO BE A 20 AMP AND THE LIGHTS CANNOT BE ON |
| | THAT CIRCUIT. |
| | |
| | 3} CIRCUITS 37,39 PANEL "A" AH #1, 10.5KW DOES NOT |
| | CORRELATE WITH SHEET M-1 SCHEDULES INDICATING THAT UNIT |
| | TO HAVE 8KW HEAT. THE OCP IS TOO LARGE TO PROTECT THE |
| | UNIT- 8000/240=33.33X125%=41.6 AMPS. |
| | |
| | 4} THE DISCONNECTS FOR THE CONDENSING UNITS AND POOL |
| | EQUIPMENT ARE IN VIOLATION OF 110.26 CLEARANCE |
| | REQUIREMENTS. |
| | |
| | 5} RECEPTACLES NEED TO BE ADDED OR RELOCATED IN THE |
| | STUDY, DINING ROOM, GUEST ROOM, BEDROOMS 2 & 3, TO |
| | COMPLY WITH 210.52(A)(1) AND 210.52(A)(2). 2005 NEC. |
| | SEE REVIEWED PLAN FOR DEFICIENCIES. |
| | |
| | 6} 210.52(H) HALLWAYS IN DWELLING UNITS, HALLWAYS OF |
| | 3.0 M (10 FT) OR MORE IN LENGTH SHALL HAVE AT LEAST ONE |
| | RECEPTACLE OUTLET. SEE "M HALL", SHEET E-2. |
| | |
| | 7} THERE IS A SYMBOL IN THE LEGEND FOR A COMBINATION |
| | SMOKE/CARBON MONOXIDE DETECTOR, BUT IT APPEARS THE |
| | SPEAKER SYMBOL WAS USED IN ERROR. CHECK REQUIRED SMOKE |
| | ALARM AND CARBON MONOXIDE ALARM LOCATIONS AND CORRECT |
| | THE SYMBOLS. |
| | NOTE: 9B-3.0472 CARBON MONOXIDE PROTECTION. |
| | (1) EVERY BUILDING FOR WHICH A PERMIT FOR NEW |
| | CONSTRUCTION IS ISSUED ON OR AFTER 7/1/08 AND HAVING A |
| | FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE, |
| | OR AN ATTACHED GARAGE SHALL HAVE AN OPERATIONAL CARBON |
| | MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM |
| | USED FOR SLEEPING PURPOSES. |
| | (2) IN NEW CONSTRUCTION, ALARMS SHALL RECEIVE THEIR |
| | PRIMARY POWER FROM THE BUILDING WIRING WHEN SUCH WIRING |
| | IS SERVED FROM THE LOCAL POWER UTILITY. SUCH ALARMS |
| | SHALL HAVE BATTERY BACK UP. |
| | (3) COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE |
| | LISTED OR LABELED BY A NATIONALLY RECOGNIZED TESTING |
| | LABORATORY. |
| | SPECIFIC AUTHORITY 553.885(2) FS. LAW IMPLEMENTED |
| | 553.72, 553.73(2), (3), (7), (9), 553.885(2) FS. |
| | HISTORY?NEW 11-18-07 LOCATE DETECTORS ON THE PLAN. |
| | NOTE: MAY BE COMBINATION SMOKE/CARBON MONOXIDE. |
| | |
| | 8} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN |
| | THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE |
| | INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS |
| | DESIGNED.SHEET A-0 LISTS OUT OF DATE CODES. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |