| Date |
Text |
| 2009-04-13 16:44:42 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | ******FROM PREVIOUS REVIEWS: |
| | |
| | ********FROM PREVIOUS REVIEWS: |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | 4. OK |
| | |
| | 5. OK |
| | |
| | ___FOR SINKS: |
| | A. OK |
| | B. OK |
| | C. 11-4.24.4 SINK DEPTH (PROVISO) |
| | D. OK |
| | E. OK |
| | F. OK |
| | G. OK |
| | |
| | 6. SHT P-3 MORE INFORMATION IS REQUIRED. PLEASE |
| | INDICATE WHAT THE HOSE REELS WILL BE WASHING OFF. WHAT |
| | WILL HAPPEN TO THE WATER USED TO WASH OFF WHATEVER IS |
| | BEING WASHED OFF? WILL THERE BE ANY CHANCE OF GREASE OR |
| | OIL WASHED OFF? PLEASE CLARIFY. SECTIONS 106.1.2 & |
| | 301.2. MORE COMMENTS MAY FOLLOW DEPENDING TO THE |
| | COMMENT RESPONSES TO THESE QUESTIONS. |
| | ****RESPONSE NOTED, COMMENT NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT THE SECTION OF THE COMMENT |
| | ABOUT WHAT WILL HAPPEN TO THE WATER, (AND NOW THE MUD), |
| | HAS NOT BEEN ADDRESSED. THERE IS NO INDICATION OF HOW |
| | THE WALLS WILL BE PROTECTED FROM THE STANDING WATER IN |
| | THE MAINTENANCE BUILDING, NO INDICATION OF SLOPING OF |
| | THE FLOORS AWAY FROM THE WALLS, NO WALL FINISH SCHEDULE |
| | INDICATING WATER PROOFING OF WALLS ETC. SECTION 301.2 |
| | SYSTEM INSTALLATION. PLUMBING SHALL BE INSTALLED WITH |
| | DUE REGARD TO PRESERVATION OF THE STRENGHT OF |
| | STRUCTURAL MEMBERS AND PREVENTION OF DAMAGE TO WALLS |
| | AND OTHER SURFACES THROUGH FIXTURE USAGE. PLEASE |
| | CLARIFY. |
| | ********NO WRITTEN RESPONSE. COMMENT TO BE ADDRESSED |
| | WITH A SIGNED, SEALED COMMENT RESPONSE TO THE ABOVE |
| | COMMENT. THE FINISH SCHEDULE FOR THE MAINTENANCE |
| | BUILDING INDICATE P-1 FININSH. PLEASE INDICATE WHAT P-1 |
| | FINISH IS AND WHERE IN THE PLANS THIS CAN BE FOUND. THE |
| | ARCHITECT OR ENGINEER OF RECORD WILL BE REQUIRED TO |
| | TAKE RESPONSIBILITY FOR THE CODE SECTION 301.2. |
| | |
| | 7. OK |
| | |
| | 8. SHT P-4 WATER RISER DIAGRAM. WATER HAMMER ARRESTORS |
| | SHALL BE LOCATED NEAR THE FIXTURE IN AN "EFFECTIVE |
| | RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH 201. WATER |
| | HAMMER ARRESTORS ARE REQUIRED AT THE REFRIGERATOR ICE |
| | MAKER LINES. SECTION 604.9. -- A SHUT OFF VALVE IS |
| | REQUIRED ON THE SUPPLY LINE TO THE WALL HYDRANT NEAR |
| | OFFICE ROOM 102. SECTION 606.2(2). |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. MOST |
| | WATER HAMMER ARRESTORS DO NOT REQUIRE ACCESS AND THE |
| | PDI-WH 201 GUIDLINES SHOW THE WATER HAMMER ARRESTORS |
| | NEAR THE FIXTURES, NOT IN THE CEILING. |
| | ******RESPONSE NOTED, BUT THE WATER HAMMER ARRESTORS |
| | ARE STILL SHOWN IN THE CEILING AND NOT DOWN NEAR THE |
| | FIXTURES IN AN "EFFECTIVE RANGE" AS REQUIRED. |
| | ********NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 9. OK |
| | 10. OK |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |
| | |