| 2009-01-05 13:55:32 | ** DENIED 2ND REVIEW ** |
| | |
| | ** SOME NOTES FROM PREVIOUS REVIEW STILL NEED TO BE |
| | ADDRESSED. |
| | |
| | 1) NOTE: PLANS STILL ONLY SUBMITTED FOR PLAN REVIEW AND |
| | PERMIT APPLICATION HAS YET TO BE MADE. PLEASE KEEP IN |
| | MIND THE NEW FLORIDA BUILDING CODE IS SET TO GO INTO |
| | EFFECT ON MARCH 1ST, 2009. |
| | VERIFICATION OF SEVERAL ITEMS INCLUDING LICENSING WILL |
| | BE DONE ONCE PERMIT APPLICATION IS MADE. |
| | *** PLEASE BE SURE ALL DOCUMENTATION CONTAINS THE |
| | CORRECT ADDRESS. |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT WITH |
| | RESPECT TO LIGHTING CONTROLS. ROOMS/AREAS 114 AND 115 |
| | SHOW SWITCHES HOWEVER THESE ARE NOT THE SAME SYMBOLS AS |
| | USED IN THE OTHER ROOMS. THERE IS A NOTE #2 WHICH LENDS |
| | TO POSSIBLE USE OF A SINGLE OCCUPANCY SENSOR TYPE |
| | DEVICE HOWEVER THIS IS NOT CLEAR AT THIS TIME. |
| | PLEASE SHOW THE SAME SYMBOL AS USED ON OTHER LOCATIONS. |
| | 13-415.1.ABC.1.1,.1.2 AND .1.3. |
| | |
| | 3) NOTE: THE PREVIOUS SUBMITTED WERE NOT SUBMITTED WITH |
| | THE REQUIRED ENERGY CALCULATIONS PER FBC 13-101, |
| | 13-400, 13-415.2 ETC |
| | THE SPECIFIC SECTIONS WERE GIVEN HOWEVER THESE WILL BE |
| | NOTED ONCE MORE. PLEASE SEE 13-400.3.A FOR VERSION |
| | WHICH WAS ADOPTED ON DECEMBER 8TH, 2006. THE CURRENT |
| | FLA COM VERSION AS NOTED IN THIS SECTION TO BE USED AT |
| | A MINIMUM IS VERSION 2.5. THE SUBMITTED CALCULATIONS |
| | ARE VERSION 2.11 WHICH IS NO LONGER AN ADOPTED VERSION |
| | IN THE STATE OF FLORIDA. |
| | PLEASE BE SURE ALL ITEMS ON PLANS COORDINATES WITH THE |
| | SUBMITTED INPUT DATA REPORT. THIS INCLUDES OTHER TRADES |
| | AS WELL. |
| | 13-415.2,13-415.2.ABC.1.1,.1.2 AND .1.3 FOR LIGHTING. |
| | SEE THE EXTERIOR LIGHTING ON THE IDR ONLY INDICATES 4 |
| | FIXTURES. THIS IS NOT POSSIBLE WHEN THE PLANS SHOW A |
| | CONSIDERABLE AMOUNT OF MORE FIXTURES THAN THE FOUR |
| | NOTED. |
| | PLEASE SEE 13-401- 13-412 FOR OTHERS. |
| | ITEMS SUCH AS FLOORS WHICH ARE ALL SHOWN AS |
| | CARPET/RUBBER PADDING IS NOT CORRECT AS THERE ARE |
| | SEVERAL AREAS WHICH ARE NOT THIS FINISH ARE SOME WHICH |
| | ARE NOT PERMITTED TO CONTAIN THIS TYPE OF FINISH. (ELEC |
| | ROOM, MECH ROOM ETC). |
| | SEE COMMENTS FROM OTHER TRADES. |
| | |
| | ** PLEASE SEE THE COVER SHEET FOR THE PLANS INDICATES |
| | THE ADDRESS AS 7501 N JOG RD ALTHOUGH THE APPLIED |
| | LOCATION IS 6880. PLEASE COORDINATE ALL PLANS AND |
| | SUPPORTING DOCUMENTATION. |
| | |
| | 4) NOTE: ON THE PREVIOUS REVIEW THE PHOTO-METRIC LEVELS |
| | FOR THE LIFE SAFETY EGRESS WERE REQUESTED. THE RESPONSE |
| | MENTIONS TO SEE ENCLOSED PLANS. THIS INFORMATION NEEDS |
| | TO BE PART OF THE PLANS, WITH TITLE BLOCKS ALONG WITH |
| | BEING SIGNED, DATED AND SEALED BY THE RESPONSIBLE |
| | DESIGNER. |
| | NFPA-101 7.8, 7.9. |
| | FS471.003, 471.025, FAC 61G15-23.002 |
| | FBC 106.1.1, 106.5. ADDITIONAL INFORMATION, CLARITY ON |
| | RECORD PLANS. |
| | |
| | 5) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS ON THE GENERATOR, ATS ETC. THE ATS IS AN |
| | INTEGRAL PART OF THE ELECTRICAL RISER AND COULD NOT BE |
| | UNDER A SEPARATE PERMIT. |
| | 110.3,90.7 |
| | |
| | 6) NOTE: NOW THAT THE LOADS FOR MDP-OP ARE SHOWN PLEASE |
| | PROVIDE A GENERATOR WHICH WILL SERVE THE CAPACITY OR |
| | PLEASE PROVIDE ALL LOAD SHEDDING WHICH WOULD BE NEEDED |
| | TO DECREASE LOAD ON SYSTEM. AS SHOWN AT THIS TIME THE |
| | GENERATOR WILL FEED ALL LOADS. |
| | 220, 215.3, 702.5 ETC |
| | |
| | 7) NOTE: PLEASE PROVIDE WIND LOADS FOR LIGHT POLES PER |
| | FBC TABLE 1609. RESPONSE MENTIONS THE INFORMATION WAS |
| | ADDED TO SHEET E-10. HOWEVER THIS INFORMATION AS SHOWN |
| | IS NOT CORRECT AND HAS BEEN CONFIRMED WITH THE BUILDING |
| | REVIEWER. |
| | |
| | 8) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS FOR ALL |
| | ITEMS. PLEASE SEE SHEET E-7, ROLL UP DOOR FOR EXAMPLE: |
| | 408.4. |
| | |
| | 9) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO LOAD |
| | CALCULATIONS. PLEASE SUBMIT THE LOAD CALCULATIONS |
| | SHOWING HOW THE LOADS WERE DERIVED. THERE ARE NO NOTES |
| | ON WHETHER OR NOT THE CONTINUOUS LOADS SUCH AS THE |
| | LIGHTING AND WATER HEATER WAS ALREADY FIGURED AT 125% |
| | OR IF THEY STILL NEED TO BE. |
| | THE TYPICAL WATER HEATER SHOWN ON PLANS INDICATE 4500 |
| | VA HOWEVER NO INDICATE OF THE 125% COULD BE LOCATED. |
| | 220.12,220.14,220.42,220.44, ETC CONTINUOUS LOADS PER |
| | 215.3,230.42. SEE 422.13 FOR STORAGE TYPE WATER |
| | HEATERS. THIS WAS A CHANGE IN THE 2005 NEC. |
| | |
| | 10) NOTE: PLEASE CLARIFY THE FOUNDATION STEEL BEING |
| | PART OF THE GROUNDING ELECTRICAL SYSTEMS AT BOTH |
| | STRUCTURES. THE PLANS NOTES *BUILDING STEEL* HOWEVER IT |
| | IS NOT CLEAR IF THIS IS FOR *FOUNDATION STEEL*. |
| | 250.50 |
| | THIS COMMENT WAS NOT MADE ON THE PREVIOUS REVIEW. |
| | |
| | ** AS NOTED ON PREVIOUS REVIEW AS THERE IS SOME |
| | INFORMATION NOT YET SUBMITTED A COMPLETE REVIEW FOR |
| | CODE COMPLIANCE CAN NOT BE DONE AT THIS TIME. |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |