| 2009-01-06 09:03:04 | BUILDING PLAN REVIEW |
| | PERMIT: 08090593 |
| | ADD: 6880 N JOG RD |
| | CONT:MAJOR WORKING DRAWING REVIEW |
| | TEL: (772)231-4301 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | OFFICE BUILDING TYPE II-B 1,800 SQ FT |
| | S-2 MAINTENANCE BUILDING TYPE II-B 1,000 SQ FT |
| | |
| | JAN 06/2009 |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | |
| | 1B) PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| | REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A |
| | RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD |
| | BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE |
| | SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT |
| | ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS WEST PALM |
| | BEACH ADMINISTRATIVE CODE. |
| | |
| | 1C-1E) COMPLIED. |
| | |
| | 2) 2ND REQUEST, COMMENT RESPONSE SHEET INDICATES SOILS |
| | REPORTS WERE SUBMITTED, NOT IN THIS REVIEW. 1802.2.1 |
| | QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING POWER OF |
| | THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE |
| | SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE |
| | BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY |
| | INVESTIGATION BE MADE. SUCH INVESTIGATION SHALL COMPLY |
| | WITH THE PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 . |
| | |
| | 3) COMPLIED, BUILDING PROVISO: 109.3.10* IMPACT OF |
| | CONSTRUCTION. |
| | |
| | 4) COMPLIED, BUILDING PROVISO: 109.3.10.1 HURRICANE |
| | PROTECTION. |
| | |
| | 5) COMPLIED. |
| | |
| | 6) ENERGY CALCULATION ARE IN THIS SUBMITTAL, BUT ARE |
| | THE WRONG VERSION . PLEASE REVIEW SECTION 13-400.3..A. |
| | |
| | 7-10) THE COUNTY DOES NOT REQUIRE PRODUCT APPROVALS AT |
| | TIME OF PERMIT SUBMISSION. THE CITY OF WEST PALM DOES |
| | REQUIRE THE FULL PRODUCT APPROVAL PACKAGE, THERE ARE |
| | OLD MIAMI-DADE REPORTS THAT STILL HAVE NOT HAD THEIR |
| | ANCHOR CALCULATION UPDATED TO THE 2004 FBC, WHICH MEANS |
| | UNDER THE 2001 FBC 1.33 INCREASES WERE TAKEN IN STEEL |
| | FASTENERS, 1605.3.1.1. AS STATED IN COMMENT (1B) |
| | PRODUCT APPROVAL REPORTS ARE REQUIRED AT TIME OF |
| | APPLICATION. HIGHLIGHT GLAZING SYSTEM TO BE USED IF |
| | THERE IS MULTIPLE GLAZING UNIT TYPES. |
| | |
| | 7) 2ND REQUEST,1609.1.4 PROTECTION OF OPENINGS IN |
| | WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING THAT |
| | RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET (18.3 |
| | M) IN BUILDINGS SHALL BE ASSUMED TO BE OPENINGS AND THE |
| | BALANCE OF GLAZED OPENINGS IN THE REST OF THE BUILDING |
| | SHALL BE ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT |
| | RECEIVES POSITIVE PRESSURE IS IMPACT RESISTANT OR |
| | PROTECTED WITH AN IMPACT RESISTANT COVERING MEETING THE |
| | REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM E 1996, |
| | OR MIAMI-DADE TAS 201, 202 AND 203 REFERENCED THEREIN |
| | AS FOLLOWS: 1. GLAZED OPENINGS LOCATED WITHIN 30 FEET |
| | (9.1 M) OF GRADE SHALL MEET THE REQUIREMENTS OF THE |
| | LARGE MISSILE TEST. 2. GLAZED OPENINGS LOCATED MORE |
| | THAN 30 FEET (9.1 M) ABOVE GRADE SHALL MEET THE |
| | PROVISIONS OF THE SMALL MISSILE TEST. |
| | |
| | 8)2ND REQUEST, FL BLD CODE 1609.6.2.2 COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, |
| | MISSING REPORTS ARE AS FOLLOWS: |
| | 8A) FIXED WINDOWS |
| | 8B) MULLIONS |
| | 8C) EXTERIOR GLAZED DOORS |
| | 8D) EXTERIOR METAL DOORS |
| | 8E) ROLL UP DOORS |
| | 8F) WALL LOUVERS |
| | 8G) TRUSS ANCHORS |
| | 8H) ROOF ASSEMBLIES |
| | 8I) SOFFITS |
| | |
| | 9) 2ND REQUEST, PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO |
| | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| | SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 10) 2ND EQUEST, WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY DCA |
| | RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | OFFICE BUILDING TYPEII-B |
| | |
| | 11A) COMPLIED. |
| | |
| | 11B) 2ND REQUEST, SHEET A-11 & SHEET A-14 APPEAR TO |
| | HAVE A 2'X2' LAY IN TILE CEILING, PLANS DO NOT PROVIDE |
| | HOW THE 1 HOUR RATING OF WALLS IS TO OCCUR, THROUGH TO |
| | THE ROOF DECK OR A 1HR RATED CEILING. 708.1. |
| | A) YOUR RESPONCE IS CONFUSING, SHEET AD-3, THE NOTE |
| | ADDED TO EXTEND DRYWALL AND INSULATION TO THE UNDER |
| | SIDE OF THE ROOF DECK DOES NOT TIE TO A WALL TYPE. A |
| | GENERIC WALL TYPE IS DEPICTED AND THE |
| | NOTE IS NOT LOCATED NEXT TO WALL TYPE 2A A NONRATED |
| | WALL NOR NEXT TO 2-1 A 1 HR RATED WALL ASSEMBLY. |
| | |
| | B) PLEASE PROVIDE THE DETAIL OF HOW THE RATED WALL WILL |
| | FASTEN INTO THE ROOF DECK ASSEMLBY, ALSO NOTE WHAT TYPE |
| | OF FLEXIBLE SEALENT SHALL BE USED.713.1 FIRE RESISTANT |
| | JOINT SYSTEMS. |
| | |
| | C) THIS SAME CORRIDOR 111 HAS A DOOR# 107 WHICH IS PART |
| | OF THE RATED CORRIDOR THE DOOR SCHEDULE DOES NOT |
| | INDICATE AS SUCH TABLE 1016.1. |
| | |
| | D) AD-3 LIFE SAFETY SHEET WILL ALSO NEED TO BE UPDATED |
| | FOR A RATED LOBBY WALL AND DOOR 107. |
| | |
| | E) THE RATING OF CORRIDOR 111 FOR 1 HOUR IS REQUIRED |
| | BECAUSE OF THE OCCUPANT LOAD BEING GREATER THAN 30 FOR |
| | TRAINING ROOM AND BREAK ROOM WHEN THE FOLDING PARTITION |
| | IS NOT USED. IT BECOMES AN |
| | ASSEMBLY OCCUPANCY REQUIRING THE CORRIDOR 111TO BE |
| | RATED FOR 1 HR. THIS RATING WILL CONTINUE THROUGH TO |
| | THE EXIT. THE LOBBY AREA WALL IS NOT INDICATED AS A |
| | FIRE RATED WALL. 1016.5CORRIDOR CONTINUITY |
| | FIRE-RESISTANCE-RATED CORRIDORS SHALL BE CONTINUOUS |
| | FROM THE POINT OF ENTRY TO AN EXIT, AND SHALL NOT BE |
| | INTERRUPTED BY INTERVENING ROOMS. EXCEPTION: FOYERS, |
| | LOBBIES OR RECEPTION ROOMS CONSTRUCTED |
| | AS REQUIRED FOR CORRIDORS SHALL NOT BE CONSTRUED AS |
| | INTERVENING ROOMS. THE LOBBY CAN BE USED AS PART OF THE |
| | MEANS OF EGRESS BUT THE WALL LABELED 2A WILL NEED TO BE |
| | RATED ONE HOUR. |
| | |
| | F) CORRIDOR 101 IS WITHIN A BUSINESS OCCUPANCY AND WILL |
| | NOT BE REQUIRED TO BE 1 HR RATED, IF THE DESIGNER |
| | WISHES TO RATE THIS CORRIDOR YOU MAY DO THAT. |
| | |
| | 11C-D) COMPLIED. |
| | |
| | 12)2ND REQUEST SHEET A-8 PLEASE PROVIDE COMPLIANCE WITH |
| | 11-4.22.2 DOORS. ALL DOORS TO ACCESSIBLE TOILET ROOMS |
| | SHALL COMPLY WITH 11-4.13. DOORS SHALL NOT SWING INTO |
| | CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE. SEE ROOMS |
| | 120,& 121. |
| | 11-4.1.3(11) TOILET FACILITIES. IF TOILET ROOMS ARE |
| | PROVIDED, THEN EACH PUBLIC AND COMMON USE TOILET ROOM |
| | SHALL COMPLY WITH SECTION 11-4.22. OTHER TOILET ROOMS |
| | PROVIDED FOR THE USE OF OCCUPANTS OF SPECIFIC SPACES |
| | (I.E., A PRIVATE TOILET ROOM FOR THE OCCUPANT OF A |
| | PRIVATE OFFICE) SHALL BE ADAPTABLE. IF BATHING ROOMS |
| | ARE PROVIDED, THEN EACH PUBLIC AND COMMON USE BATHROOM |
| | SHALL COMPLY WITH SECTION 11-4.23. ACCESSIBLE TOILET |
| | ROOMS AND BATHING FACILITIES SHALL BE ON AN ACCESSIBLE |
| | ROUTE. |
| | |
| | 13) 2ND REQUEST, THE RESPONSE COMMENTS INDICATE THIS TO |
| | BE A PAVILION, TO BE PART OF THIS PERMIT WE DO NEED |
| | INFORMATION AS FAR AS COMPONENTS AND CLADDING YOU |
| | INDICATE THIS IS A PRE-ENGINEERED CANOPY, EITHER IT HAS |
| | GONE THROUGH THE MANUFACTURED BUILDING PROGRAM WITH THE |
| | STATE AND IS APPROVED AS A MANUFACTURED MODULAR |
| | BUILDING PROGRAM WITH STATE APPROVED PLANS OR IT WILL |
| | NEED |
| | PRODUCT APPROVALS FOR THE ROOFING ASSEMBLY. WITHOUT |
| | PLANS THIS AREA WILL BE EXEMPTED FROM THE PERMIT AND |
| | PLANS TO BE SUBMITTED UNDER A SEPERATE PERMIT. |
| | 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | |
| | 15-17) COMPLIED. |
| | T THE CONNECTION STATES THAT WELDING OF CONNECTIONS IS |
| | PROHIBITED, PLEASE PROVIDE MANUFACTURERS APPROVAL FOR |
| | WELDING OF THIS TYPE OF CONNECTION. 106.1.2 ADDITIONAL |
| | INFORMATION REQUIRED. |
| | |
| | 18) 2ND REQUEST. SHEET S-4 INDICATES A FOOTING TYPE A |
| | BUT THE PLANS ARE LACKING COLUMN AND BEAM INFORMATION, |
| | 1609.2.1 PART OFTHE MAIN WIND FORCE-RESISTING SYSTEM. |
| | PLEASE PROVIDE ADDITONAL INFORMATION, 106.1..2. 106.3.5 |
| | MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | |
| | 19) 2ND REQUEST, SHEET A-4 ALSO INDICATES THE ROOFING |
| | ASSEMBLY TO BE A PREMANUFACTRED CANOPY, PLEASE PROVIDE |
| | PRODUCT INFORMATION, TO BE PART OF THIS PERMIT WE DO |
| | NEED INFORMATION AS FAR AS COMPONENTS AND CLADDING YOU |
| | INDICATE THIS IS A PRE-ENGINEERED CANOPY, EITHER IT HAS |
| | GONE THROUGH THE MANUFACTURED BUILDING PROGRAM WITH THE |
| | STATE AND IS APPROVED AS A MANUFACTURED MODULAR |
| | BUILDING PROGRAM WITH STATE APPROVED PLANS OR IT WILL |
| | NEED PRODUCT APPROVALS FOR THE ROOFING ASSEMBLY. |
| | WITHOUT PLANS THIS AREA WILL BE EXEMPTED FROM THE |
| | PERMIT AND PLANS TO BE SUBMITTED UNDER A SEPERATE |
| | PERMIT. 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| | BUILDINGS. |
| | |
| | 20)2ND REQUEST, STRUCTURAL SHEETS S-4, S-6 AND S-8 ROOF |
| | PRESSURE ZONES FAIL TO INDICATE PRESSURE ZONE 3 FAIL TO |
| | INDICATE CORNER ZONE# 3 AND THE ASSOCIATED PRESSURES, |
| | PLEASE REVIEW FIGURE 1609.6.2.2 COMPONENTS AND |
| | CLADDING. WITH THE RESPONSE FOR THIS COMMENT IT APPEARS |
| | THAT YOUR CODE BOOK HAS NOT BEEN UPDATED. IN 2006 |
| | SUPPLEMENTS( BLUE PAGES) THE TABLE 1609.6C HAS BEEN |
| | ELIMINATED. PLEASE REVISE SHEET S-6 FOR PRESSURES IN |
| | ZONE 3. |
| | |
| | 21) 2ND REQUEST, GENERATOR PAD IS SHOWN ON SHEET SD-1, |
| | IS THIS PAD GOING TO BE PART OF THIS PERMIT OR JUST |
| | INFORMATIONAL, THE GENERATOR AND ATTACHMENT TO SLAB |
| | WILL BE REVIEWED UNDER A SEPERATE PERMIT. PLEASE |
| | PROVIDE SIZE OF GENERATOR PAD, IF STELL REINFORCEMENT |
| | IS TO BE INSTALLED AND ANCHORS TO RESIST THE MOMENT OF |
| | OVER TURNING. 1609.1.3 ANCHORAGE AGAINST OVERTURNING, |
| | UPLIFT AND SLIDDING. |
| | |
| | 22) STAIR DELETED, COMPLIED. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |