| 2008-10-25 12:18:21 | REVIEW #: 1ST ***PLAN CHECK ONLY*** |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. PAGE A-3 INDICATES TWO 1,000 GALLON DIESEL FUEL |
| | STORAGE TANKS, ONE FOR EACH BUILDING. PAGE E-2 SHOWS |
| | ONLY ONE GENERATOR WITH DIESEL STORAGE TANK. WHICH IS |
| | CORRECT? NO INFORMATION WAS PROVIDED REGARDING THE |
| | DIESEL GENERATOR OR FUEL STORAGE SYSTEM TO BE USED. |
| | PROVIDE SUBMITTAL DOCUMENTATION FOR EACH TO DEMONSTRATE |
| | COMPLIANCE WITH FBCM SECTION 915. ALSO, ABOVE GROUND |
| | FUEL STORAGE TANKS GREATER THAN 550 GALLONS SHALL BE |
| | SUBMITTED TO PALM BEACH COUNTY DERM FOR APPROVAL PRIOR |
| | TO PERMIT ISSUANCE. INCORPORATE DERM APPROVED PLANS |
| | INTO THESE PERMIT DOCUMENTS. FOR MORE INFORMATION |
| | PLEASE CONTACT PBC DERM AT: 561-233-2400 OR |
| | HTTP://WWW.PBCGOV.COM/ERM/ |
| | |
| | 2. PAGE H-1 REFERS TO FORM 400A FOR ENERGY CODE |
| | COMPLIANCE. NO SUCH FORM WAS PROVIDED WITH THIS |
| | SUBMISSION. WITHOUT SUCH FORM, AN OVERALL ENERGY CODE |
| | COMPLIANCE REVIEW CAN NOT BE PERFORMED. PROVIDE A |
| | COMMERCIAL ENERGY CODE COMPLIANCE FORM IN ACCORDANCE |
| | WITH FBCB 13-400.0. ALSO, COOLING LOAD CALCULATIONS |
| | SHALL BE APPENDED TO THE ENERGY CODE COMPLIANCE FORM IN |
| | ACCORDANCE WITH FBCM 13-407.1.ABC.1. AS A RESULT OF |
| | THIS INFORMATION NOT BEING PROVIDED, RELATED ADDITIONAL |
| | COMMENTS ARE LIKELY IN SUBSEQUENT REVIEWS. |
| | |
| | 3. PAGE H-2: MULTIPLE DUCTS ON FLOOR PLAN DO NOT HAVE A |
| | SIZE DESIGNATION. EXAMPLES: OUTSIDE AIR DUCTS IN |
| | MECHANICAL ROOMS, RETURN TRUNK AND BRANCH LINES. PLEASE |
| | CHECK ALL DUCTS ON FLOOR PLAN AND PROVIDE MISSING SIZE |
| | INFORMATION. DUCTS SHALL BE DESIGNED AND INSTALLED TO |
| | PROVIDE THE REQUIRED DISTRIBUTION OF AIR IN ACCORDANCE |
| | WITH FBCM 603.1. |
| | |
| | 4. PAGE H-2: SEVERAL BRANCH DUCTS SHOW CONTROL DAMPERS |
| | ABOVE GYPSUM BOARD CEILINGS. SHOW HOW THESE DAMPERS ARE |
| | TO BE ACCESSED FOR TESTING AND BALANCING IN ACCORDANCE |
| | WITH FBCB 13-410.1.ABC.4. |
| | |
| | 5. PAGE H-2: THE OUTSIDE AIR INTAKE LOUVER FOR AHU-3 |
| | AND AHU-4 IS SHOWN TO BE APPROXIMATELY 5 FEET FROM THE |
| | PARKING LOT FOR THE OPERATIONS BUILDING. MECHANICAL |
| | OUTSIDE AIR INTAKE OPENINGS SHALL BE LOCATED A MINIMUM |
| | OF 10 FEET FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, |
| | SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, |
| | ALLEYS, PARKING LOTS AND LOADING DOCKS IN ACCORDANCE |
| | WITH FBCM 401.5.1. |
| | |
| | 6. PAGE H-2: THE RETURN DUCT PENETRATING A RATED WALL |
| | ASSEMBLY AT BREAK ROOM 106 SHOW NO FIRE DAMPER AT THE |
| | DUCT PENETRATION BUT SHOWS THE FIRE DAMPER AT ANOTHER |
| | LOCATION IN THE WALL, AWAY FROM THE DUCT. PLEASE SHOW |
| | THE DUCT PENETRATION TO BE PROTECTED IN ACCORDANCE WITH |
| | FBCM 607.5 AND SHOW THE CORRECT LOCATION OF THE DAMPER |
| | IN ACCORDANCE WITH FBCM 607.8. |
| | |
| | 7. PAGE HD-2: THERE IS NO DETAIL PROVIDED FOR |
| | INSTALLATION OF GRAVITY HOOD, ASSOCIATED ROOF CURB OR |
| | ROOF JACKS FOR WIND RESISTANCE. MECHANICAL EQUIPMENT |
| | SHALL BE DESIGNED AND INSTALLED TO RESIST WIND |
| | PRESSURES IN ACCORDANCE WITH FBCM 301.13. |
| | |
| | 8. PAGE HD-2: NO INFORMATION SHOWN ON PLANS OR IN |
| | DETAIL REGARDING AUXILIARY OR SECONDARY DRAIN |
| | PROTECTION FOR CONDENSATE DRAIN SYSTEMS. PROVIDE |
| | AUXILIARY OR SECONDARY DRAIN PROTECTION IN ACCORDANCE |
| | WITH FBCM 307.2.3. |
| | |
| | NOTE: THE 2007 FLORIDA BUILDING CODE IS SCHEDULED TO |
| | BECOME EFFECTIVE ON MARCH 1, 2009. IF A PERMIT |
| | APPLICATION FOR THIS PROJECT IS SUBMITTED AFTER THIS |
| | DATE, THESE PLANS WILL NEED TO BE REVIEWED FOR |
| | COMPLIANCE WITH THE NEW CODE PRIOR TO PERMIT ISSUANCE. |
| | |