| Notes |
| Date |
Text |
| 2009-01-24 13:57:15 | REVISED M2.1 DENIED: | | | | | | FLOOR PLAN SHOWS NEW AND EXISTING DUCTS PENETRATING | | | FIRE RESISTANT RATED WALL WITHOUT PROTECTION. SHOW HOW | | | THESE PENETRATIONS ARE TO BE PROTECTED IN ACCORDANCE | | | WITH FBCM 607.5. ALSO, SHOW THE LOCATION OF EACH FIRE | | | DAMPER ON THE PLANS IN ACCORDANCE WITH FBCM 607.8. | | | | | | NOTE: ARCHITECTURAL PLAN NOTE CALLSL FOR CONTRACTOR TO | | | INSPECT AND REPAIR RATED WALLS TO MAINTAIN INTEGRITY OF | | | SAME. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|