2008-11-03 10:05:12PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) THE RESPONSE TO REVIEW NOTES FROM 10-1-08 SYSTEM
 SIZING, ADDRESSES SENSIBLE LOADS. THE 2004 FBC DOES NOT
 ADDRESS SENSIBLE LOAD ONLY TOTAL LOADS, AS THE COOLING
 LOAD CALCULATIONS SUBMITTED SHOWS TOTAL COOLING
 REQUIRED IS BASED ON TOTAL LOAD. IF YOU WISH TO
 ENGINEER THE A/C SYSTEMS TO YOUR REQUIREMENTS PLEASE
 COMPLY WITH 2004 FBC 13-407.1.ABC.1 " EXCEPTIONS" A
 SUMMARY SHEET MAY BE SUBMITTED WHEN SIGNED AND SEALED
 BY THE ENGINEER AND HAS THE MINIMUM INFORMATION ON IT.
 **PROJECT NAME/OWNER... **PROJECT ADDRESS... **SIZING
 METHOD USED... **AREA IN SQUARE FEET... **OUTDOOR DRY
 BULB USED... **OUTDOOR WET BULB USED... **RELATIVE
 HUMIDITY... **INDOOR DRY BULB.... **TOTAL HEATING
 REQUIRED WITH OUTSIDE AIR... **TOTAL SENSIBLE GAIN...
 **TOTAL LATENT GAIN... **GRAINS WATER (DIFFERENCE)...
 **TOTAL COOLING REQUIRED WITH OUTSIDE AIR. (PLEASE HAVE
 THE TOTAL COOLING OF THE SUMMARY ADDRESS THE TOTAL
 COOLING OF THE SYSTEMS ON THE PLANS).
  
 2) SYSTEMS 1, 2, 3, 4, 6, 7, 8, AND 9 ARE OVER SIZED
 PER COOLING LOAD CALCULATIONS SUBMITTED. PER 2004 FBC
 13-407.1.ABC.1.1 HVAC SYSTEMS AND EQUIPMENT SHALL BE
 SIZED TO PROVIDE NO MORE THAN THE SPACE AND SYSTEM
 LOADS CALCULATED IN ACCORDANCE WITH SECTION
 407.1.ABC.1. A SINGLE PIECE OF EQUIPMENT PROVIDING BOTH
 COOLING AND HEATING SHALL SATISFY THIS PROVISION WHEN
 THE COOLING FUNCTION MEETS THE PROVISIONS OF SECTION
 407.1.ABC.1, AND THE HEATING FUNCTION IS SIZED AS SMALL
 AS POSSIBLE TO MEET THE LOAD WITHIN AVAILABLE EQUIPMENT
 OPTIONS.
  
 3) REVISED ENERGY CALCULATIONS SUBMITTED ARE NOT
 LISTING SYSTEMS 1, 2, 3, 4, AND 9. ALSO THE INPUT DATA
 REPORT SUBMITTED IS MISSING SYSTEMS 1, 2, 8, AND 9.
 PLEASE CORRECT PER 2004 FBC 13-103.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]