| 2008-11-03 10:05:12 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | |
| | 1) THE RESPONSE TO REVIEW NOTES FROM 10-1-08 SYSTEM |
| | SIZING, ADDRESSES SENSIBLE LOADS. THE 2004 FBC DOES NOT |
| | ADDRESS SENSIBLE LOAD ONLY TOTAL LOADS, AS THE COOLING |
| | LOAD CALCULATIONS SUBMITTED SHOWS TOTAL COOLING |
| | REQUIRED IS BASED ON TOTAL LOAD. IF YOU WISH TO |
| | ENGINEER THE A/C SYSTEMS TO YOUR REQUIREMENTS PLEASE |
| | COMPLY WITH 2004 FBC 13-407.1.ABC.1 " EXCEPTIONS" A |
| | SUMMARY SHEET MAY BE SUBMITTED WHEN SIGNED AND SEALED |
| | BY THE ENGINEER AND HAS THE MINIMUM INFORMATION ON IT. |
| | **PROJECT NAME/OWNER... **PROJECT ADDRESS... **SIZING |
| | METHOD USED... **AREA IN SQUARE FEET... **OUTDOOR DRY |
| | BULB USED... **OUTDOOR WET BULB USED... **RELATIVE |
| | HUMIDITY... **INDOOR DRY BULB.... **TOTAL HEATING |
| | REQUIRED WITH OUTSIDE AIR... **TOTAL SENSIBLE GAIN... |
| | **TOTAL LATENT GAIN... **GRAINS WATER (DIFFERENCE)... |
| | **TOTAL COOLING REQUIRED WITH OUTSIDE AIR. (PLEASE HAVE |
| | THE TOTAL COOLING OF THE SUMMARY ADDRESS THE TOTAL |
| | COOLING OF THE SYSTEMS ON THE PLANS). |
| | |
| | 2) SYSTEMS 1, 2, 3, 4, 6, 7, 8, AND 9 ARE OVER SIZED |
| | PER COOLING LOAD CALCULATIONS SUBMITTED. PER 2004 FBC |
| | 13-407.1.ABC.1.1 HVAC SYSTEMS AND EQUIPMENT SHALL BE |
| | SIZED TO PROVIDE NO MORE THAN THE SPACE AND SYSTEM |
| | LOADS CALCULATED IN ACCORDANCE WITH SECTION |
| | 407.1.ABC.1. A SINGLE PIECE OF EQUIPMENT PROVIDING BOTH |
| | COOLING AND HEATING SHALL SATISFY THIS PROVISION WHEN |
| | THE COOLING FUNCTION MEETS THE PROVISIONS OF SECTION |
| | 407.1.ABC.1, AND THE HEATING FUNCTION IS SIZED AS SMALL |
| | AS POSSIBLE TO MEET THE LOAD WITHIN AVAILABLE EQUIPMENT |
| | OPTIONS. |
| | |
| | 3) REVISED ENERGY CALCULATIONS SUBMITTED ARE NOT |
| | LISTING SYSTEMS 1, 2, 3, 4, AND 9. ALSO THE INPUT DATA |
| | REPORT SUBMITTED IS MISSING SYSTEMS 1, 2, 8, AND 9. |
| | PLEASE CORRECT PER 2004 FBC 13-103.3. |
| | |