Plan Review Notes
Plan Review Notes For Permit 08090577
Permit Number 08090577
Review Stop E
Sequence Number 2
Notes
Date Text
2008-11-06 11:49:29 
  
  
 ** DENIED 2ND REVIEW **
  
 1) NOTE: ELECTRICAL PLANS NEED TO SHOW THE CIRCUITING
 OF EMERGENCY AND EXIT LIGHTS PER 700.12F. RESPONSE
 MENTIONS TO SEE NOTES ON THE LIFE SAFETY PLANS HOWEVER
 AS THE PLANS NEED TO SHOW THE CIRCUITING YOU MAY NOT
 QUOTE THE CODE IN LIEU OF SPECIFIC DETAIL.
  
 2) NOTE: PLEASE SEE THE PREVIOUS REVIEW WITH RESPECT TO
 THE LIGHTING PERFORMANCE CALCULATIONS. IN THE REVIEW
 COMMENTS IT STATED TO PLEASE CALL TO GO OVER HOW TO
 SHOW. THE PLANS SHOW CALCULATIONS BASED ON TABLE
 13-415.2.C WHICH ARE OK HOWEVER THERE ARE ADDITIONAL
 FIXTURES ON PLANS NOT FIGURED INTO THE CALCULATIONS.
 (RECESSED FIXTURES).
 PLEASE SEE THE PACKAGE ALSO SUBMITTED A FORM B, WHICH
 BY DEFINITION THIS IS NOT A RENOVATION MEETING SECTION
 202. THE COMPLIANCE METHOD SHOWN ON PLANS IS OK BUT
 PLEASE ADJUST THE NUMBER OF FIXTURES.
  
 3) NOTE: PLEASE SEE SOME AREAS ARE STILL MISSING
 REQUIRED LIGHTING CONTROLS PER
 13-415.1.ABC.1.1,.1.2,.1.3. SEE ROOM 117 FOR EXAMPLE
 WHICH STILL INDICATES STAND SWITCHES.
 PLEASE ALSO EXPLAIN THE NUMEROUS SWITCHES IN ROOM 100.
 AN OCCUPANT MUST BE ABLE TO SEE ALL LIGHTING WHICH IS
 BEING CONTROLLED OR MEET THE EXCEPTIONS IN THE SECTIONS
 GIVEN.
 PLEASE CALL TO GO OVER.
  
 4) NOTE: PLEASE SEE 230.2,230.2E ETC. PLEASE IDENTIFY
 ALL SERVICE EQUIPMENT. THE RISER AND LAYOUT IS NOT
 INFORMATIVE ENOUGH TO GRANT AN ADDITIONAL MAIN TO THE
 TENANT SPACE WHICH ALREADY CONTAINS ELECTRICAL SERVICE.
 WHAT IS THE VOLTAGE OF NEW?
 200,201 INDICATES 120/240V.
 FINAL DETERMINATION CAN NOT BE MADE AT THIS TIME.
 PLEASE SEE 220.87,215.5,215.3,230.42 ETC
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  