| 2008-11-06 11:49:29 | |
| | |
| | |
| | ** DENIED 2ND REVIEW ** |
| | |
| | 1) NOTE: ELECTRICAL PLANS NEED TO SHOW THE CIRCUITING |
| | OF EMERGENCY AND EXIT LIGHTS PER 700.12F. RESPONSE |
| | MENTIONS TO SEE NOTES ON THE LIFE SAFETY PLANS HOWEVER |
| | AS THE PLANS NEED TO SHOW THE CIRCUITING YOU MAY NOT |
| | QUOTE THE CODE IN LIEU OF SPECIFIC DETAIL. |
| | |
| | 2) NOTE: PLEASE SEE THE PREVIOUS REVIEW WITH RESPECT TO |
| | THE LIGHTING PERFORMANCE CALCULATIONS. IN THE REVIEW |
| | COMMENTS IT STATED TO PLEASE CALL TO GO OVER HOW TO |
| | SHOW. THE PLANS SHOW CALCULATIONS BASED ON TABLE |
| | 13-415.2.C WHICH ARE OK HOWEVER THERE ARE ADDITIONAL |
| | FIXTURES ON PLANS NOT FIGURED INTO THE CALCULATIONS. |
| | (RECESSED FIXTURES). |
| | PLEASE SEE THE PACKAGE ALSO SUBMITTED A FORM B, WHICH |
| | BY DEFINITION THIS IS NOT A RENOVATION MEETING SECTION |
| | 202. THE COMPLIANCE METHOD SHOWN ON PLANS IS OK BUT |
| | PLEASE ADJUST THE NUMBER OF FIXTURES. |
| | |
| | 3) NOTE: PLEASE SEE SOME AREAS ARE STILL MISSING |
| | REQUIRED LIGHTING CONTROLS PER |
| | 13-415.1.ABC.1.1,.1.2,.1.3. SEE ROOM 117 FOR EXAMPLE |
| | WHICH STILL INDICATES STAND SWITCHES. |
| | PLEASE ALSO EXPLAIN THE NUMEROUS SWITCHES IN ROOM 100. |
| | AN OCCUPANT MUST BE ABLE TO SEE ALL LIGHTING WHICH IS |
| | BEING CONTROLLED OR MEET THE EXCEPTIONS IN THE SECTIONS |
| | GIVEN. |
| | PLEASE CALL TO GO OVER. |
| | |
| | 4) NOTE: PLEASE SEE 230.2,230.2E ETC. PLEASE IDENTIFY |
| | ALL SERVICE EQUIPMENT. THE RISER AND LAYOUT IS NOT |
| | INFORMATIVE ENOUGH TO GRANT AN ADDITIONAL MAIN TO THE |
| | TENANT SPACE WHICH ALREADY CONTAINS ELECTRICAL SERVICE. |
| | WHAT IS THE VOLTAGE OF NEW? |
| | 200,201 INDICATES 120/240V. |
| | FINAL DETERMINATION CAN NOT BE MADE AT THIS TIME. |
| | PLEASE SEE 220.87,215.5,215.3,230.42 ETC |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |