Plan Review Notes
Plan Review Notes For Permit 08090577
Permit Number 08090577
Review Stop M
Sequence Number 1
Notes
Date Text
2008-10-01 16:28:06PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) COOLING LOAD CALCULATIONS SHOW ZONE #5 NEEDS 8,876
 TOTAL COOLING BTU'S, MECHANICAL PLAN M-1 IS SHOWING
 SYSTEM #5 AS 24,500 (2 TON) TOTAL COOLING BTU'S. A 1.5
 TON SYSTEM WOULD MEET THE COOLING LOAD REQUIREMENTS,
 SEE 2004 FBC 13-407.1.ABC.1.1. PLEASE COMPLY.
  
 2) COOLING LOAD CALCULATIONS SHOW ZONE #6 NEEDS 15,670
 TOTAL COOLING BTU'S, MECHANICAL PLAN M-1 IS SHOWING
 SYSTEM #6 AS 59,700 (5 TON) TOTAL COOLING BTU'S. A 1.5
 TON SYSTEM WOULD MEET THE COOLING LOAD REQUIREMENTS,
 SEE 2004 FBC 13-407.1.ABC.1.1. PLEASE COMPLY.
  
 3) ONLY ONE SET OF THE COOLING LOAD CALCULATIONS WERE
 SUBMITTED, PLEASE SUBMIT TWO SETS, PER 2004 WPB AMEND.
 106.1.
  
 4) PLAN M-3 RETURN AIR DUCTS (FLEX) NEEDS TO BE SIZED
 IN ROOMS 117, 116, 113.112 AND 102. A SUPPLY AIR DUCT
 IN FILE AREA 111 NEEDS TO BE SIZED ALSO (SEE YELLOW
 HIGH LIGHT ON PLAN). PLEASE CORRECT PER 2004 FBC/M
 603.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]