2008-10-21 14:39:34***DENIED***
  
 1) CLASSIFICATION OF RATED DOORS SHALL BE EXPRESSED IN
 HOURS OR FRACTIONS PER NFPA 80, SEC. 4.1.1.
  
 2) DUCT SMOKE DETECTORS SHALL INITATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 3) IN ADDITION TO SHOP DRAWINGS AND PERMIT, FIRE
 SPRINKLER HEAD LAYOUT FOR COMMERCIAL PROJECTS SHALL BE
 PROVIDED PER FBC 106. HEAD LAYOUT MAY BE SHOWN ON
 REFLECTED CEILING PLAN.
  
 4) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR
 ACCESS CONTROL SYSTEM THAT SHALL COMPLY WITH NFPA 101,
 SEC. 7.2.1.6.2.
  
  