| Plan Review Notes For Permit 08090577 |
| Permit Number |
08090577 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-10-21 14:39:34 | ***DENIED*** | | | | | | 1) CLASSIFICATION OF RATED DOORS SHALL BE EXPRESSED IN | | | HOURS OR FRACTIONS PER NFPA 80, SEC. 4.1.1. | | | | | | 2) DUCT SMOKE DETECTORS SHALL INITATE A GENERAL FIRE | | | ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. | | | | | | 3) IN ADDITION TO SHOP DRAWINGS AND PERMIT, FIRE | | | SPRINKLER HEAD LAYOUT FOR COMMERCIAL PROJECTS SHALL BE | | | PROVIDED PER FBC 106. HEAD LAYOUT MAY BE SHOWN ON | | | REFLECTED CEILING PLAN. | | | | | | 4) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR | | | ACCESS CONTROL SYSTEM THAT SHALL COMPLY WITH NFPA 101, | | | SEC. 7.2.1.6.2. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|