| Date |
Text |
| 2008-10-09 08:39:41 | |
| | ** DENIED ** |
| | |
| | 1) NOTE: PLEASE SEE THE SUBMITTED METHOD *A* ENERGY |
| | CALCULATIONS MAY NOT BE USED. THIS IS FOR A TENANT |
| | SPACE WITHIN A BUILDING. THE METHOD *A* BY DEFINITION |
| | IS FOR A *WHOLE BUILDING* WHICH THIS IS NOT. |
| | PLEASE SEE 13-101.1. |
| | PLEASE BE SURE TO SEE FBC 13-415.2, |
| | 13-415.2.ABC.1.1,.1.2, TABLE 13-415.2.B., 13-415.2.C. |
| | PLEASE CALL TO GO OVER HOW PRESCRIPTIVE REQUIREMENTS |
| | CAN BE MET. |
| | THE SUBMITTED CALCULATIONS DO NOT CONTAIN ANY SEAL. |
| | THEY ALSO CONTAIN A PRINTED NAME OF THE PERSON |
| | PREPARING THE DOCUMENTS OTHER THAN THE LICENSED |
| | ARCHITECT OR ENGINEER. |
| | |
| | 2) NOTE: PLEASE SEE MISSING TITLE BLOCK INFORMATION FOR |
| | GONZALES AND GONZALES ENGINEERS INC. PLEASE SEE THESE |
| | ARE MISSING THE REQUIRED ENGINEERING BUSINESS LICENSE |
| | NUMBER WHICH IS ALSO KNOWN AS A CERTIFICATE OF |
| | AUTHORIZATION NUMBER PER FS 471.023, FAC 61G15-23.002. |
| | |
| | 3) NOTE: NEW SERVICE AS SHOWN NOT GRANTED PER 230.2. |
| | PLEASE RE-WORK RISER AND UPGRADE EXISTING AS NEEDED. |
| | AS PROPOSED SERVICE IS NOT GRANTED NO REVIEW FOR NEW |
| | SHOWN WAS DONE. |
| | PLEASE ALSO SEE THE CODE AS THE RISER DOES SHOW |
| | ELECTRICAL FROM SEPARATE SERVICES INTO THE SAME |
| | JUNCTION BOXES WHICH IS NOT PERMITTED. |
| | |
| | 4) NOTE: ACCESS CONTROLS AS NOTED ON PLANS WILL BE |
| | REQUIRED TO BE UNDER A SEPARATE PERMIT APPLICATION |
| | ALONG WITH PLANS DETAILING ALL SYSTEM PER NFPA-101 |
| | CHAPTER 7 FOR ACCESS CONTROLS, EGRESS ETC. |
| | EGRESS UNDER NORMAL OR EMERGENCY CONDITIONS SHALL NOT |
| | BE IMPEDED. |
| | |
| | 5) NOTE: PLEASE SEE FBC 11-4.27.4 |
| | CONTROLS AND OPERATING MECHANISMS SHALL BE OPERABLE |
| | WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, |
| | PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED |
| | TO ACTIVATE CONTROLS SHALL BE NO GREATER THAN 5 LBF |
| | (22.2 N). |
| | |
| | 6) NOTE: PLEASE PROVIDE A BASE DESIGN DETAIL FOR |
| | OCCUPANCY SENSORS AND CONTROLS. WILL THIS BE A LOW |
| | VOLTAGE SYSTEM? LINE VOLTAGE SYSTEM? ETC |
| | PLEASE KNOW THE DEVICES USED IN AREAS SUCH AS THE |
| | MULTI-STALL RESTROOM SHALL BE ULTRASONIC/DUAL |
| | TECHNOLOGY. |
| | 13-415.1.ABC.1.1,.1.2 |
| | |
| | 7) NOTE: PLEASE INDICATE ALL EMERGENCY AND EXIT |
| | LIGHTING TO THE LOCAL BRANCH CIRCUIT PER 700.12F. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |