Plan Review Notes
Plan Review Notes For Permit 08090577
Permit Number 08090577
Review Stop E
Sequence Number 1
Notes
Date Text
2008-10-09 08:39:41 
 ** DENIED **
  
 1) NOTE: PLEASE SEE THE SUBMITTED METHOD *A* ENERGY
 CALCULATIONS MAY NOT BE USED. THIS IS FOR A TENANT
 SPACE WITHIN A BUILDING. THE METHOD *A* BY DEFINITION
 IS FOR A *WHOLE BUILDING* WHICH THIS IS NOT.
 PLEASE SEE 13-101.1.
 PLEASE BE SURE TO SEE FBC 13-415.2,
 13-415.2.ABC.1.1,.1.2, TABLE 13-415.2.B., 13-415.2.C.
 PLEASE CALL TO GO OVER HOW PRESCRIPTIVE REQUIREMENTS
 CAN BE MET.
 THE SUBMITTED CALCULATIONS DO NOT CONTAIN ANY SEAL.
 THEY ALSO CONTAIN A PRINTED NAME OF THE PERSON
 PREPARING THE DOCUMENTS OTHER THAN THE LICENSED
 ARCHITECT OR ENGINEER.
  
 2) NOTE: PLEASE SEE MISSING TITLE BLOCK INFORMATION FOR
 GONZALES AND GONZALES ENGINEERS INC. PLEASE SEE THESE
 ARE MISSING THE REQUIRED ENGINEERING BUSINESS LICENSE
 NUMBER WHICH IS ALSO KNOWN AS A CERTIFICATE OF
 AUTHORIZATION NUMBER PER FS 471.023, FAC 61G15-23.002.
  
 3) NOTE: NEW SERVICE AS SHOWN NOT GRANTED PER 230.2.
 PLEASE RE-WORK RISER AND UPGRADE EXISTING AS NEEDED.
 AS PROPOSED SERVICE IS NOT GRANTED NO REVIEW FOR NEW
 SHOWN WAS DONE.
 PLEASE ALSO SEE THE CODE AS THE RISER DOES SHOW
 ELECTRICAL FROM SEPARATE SERVICES INTO THE SAME
 JUNCTION BOXES WHICH IS NOT PERMITTED.
  
 4) NOTE: ACCESS CONTROLS AS NOTED ON PLANS WILL BE
 REQUIRED TO BE UNDER A SEPARATE PERMIT APPLICATION
 ALONG WITH PLANS DETAILING ALL SYSTEM PER NFPA-101
 CHAPTER 7 FOR ACCESS CONTROLS, EGRESS ETC.
 EGRESS UNDER NORMAL OR EMERGENCY CONDITIONS SHALL NOT
 BE IMPEDED.
  
 5) NOTE: PLEASE SEE FBC 11-4.27.4
 CONTROLS AND OPERATING MECHANISMS SHALL BE OPERABLE
 WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE CONTROLS SHALL BE NO GREATER THAN 5 LBF
 (22.2 N).
  
 6) NOTE: PLEASE PROVIDE A BASE DESIGN DETAIL FOR
 OCCUPANCY SENSORS AND CONTROLS. WILL THIS BE A LOW
 VOLTAGE SYSTEM? LINE VOLTAGE SYSTEM? ETC
 PLEASE KNOW THE DEVICES USED IN AREAS SUCH AS THE
 MULTI-STALL RESTROOM SHALL BE ULTRASONIC/DUAL
 TECHNOLOGY.
 13-415.1.ABC.1.1,.1.2
  
 7) NOTE: PLEASE INDICATE ALL EMERGENCY AND EXIT
 LIGHTING TO THE LOCAL BRANCH CIRCUIT PER 700.12F.
  
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved