| 2008-10-09 13:52:49 | BUILDING PLAN REVIEW |
| | PERMIT: 08090577 |
| | ADD: 5500 VILLAGE BLVD |
| | CONT: PRESIDENTIAL CONSTRUCTION |
| | TEL: (561)723-3370 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | |
| | |
| | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT, |
| | TO BE FILED WITH THE CLERK OF THE COURT. NOTE: |
| | 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 2) 61G1-16.004 FL. ADMIN. CODE. PLANS PREPARED BY A |
| | REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH |
| | MUST: |
| | - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEALED |
| | INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING THE |
| | PLANS |
| | |
| | 3) SHEET A-2 DOOR B IS MISSING THE REQUIRED 18" ON THE |
| | PULL SIDE OF THE PULL SIDE OF DOOR. 11-4.13.6 |
| | MANEUVERING CLEARENCES, AT DOORS. MINIMUM MANEUVERING |
| | CLEARANCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL |
| | BE AS SHOWN IN FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL. |
| | |
| | 4) SHEET A-4 DETAIL BREAK ROOM ELEVATION INDICATES |
| | DOORS ON THE SINK BASE UNIT. SINKS: |
| | 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE MOUNTED WITH |
| | THE COUNTER NO HIGHER THAN 34" ABOVE THE FINISH FLOOR. |
| | 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30" |
| | WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS. |
| | 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT |
| | LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) |
| | COMPLYING WITH |
| | SECTION 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A SINK |
| | TO ALLOW FORWARD APPROACH. |
| | THE CLEAR FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE |
| | AND SHALL EXTEND A MAXIMUM OF 19 INCHES (485 MM) |
| | UNDERNEATH THE SINK. |
| | |
| | 5) THE COVERSHEET LIST THIS AS A TYPE III-B FULLY |
| | SPRINKLERED BUILDING WHERE AS THE LS -1 INDICATES THE |
| | BUILDING TO BE A V-B FULLY SPRINKLERED BUILDING. PLEASE |
| | COORDINATE PLANS TO A MINIMUM |
| | BUILDING TYPE. TABLE 503 & TABLE 601. |
| | |
| | 6) GONZALEZ & GONZALEZ ENGINEERING, INC IS MISSING |
| | THEIR CERTIFICATE OF AUTHORIZATION. |
| | 471.023 F.S. CERTIFICATE OF AUTHORIZATION. THE TITLE |
| | BLOCK FOR ANY SHEET BEARING THE NAME OF AN ENGINEER |
| | PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A |
| | PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL |
| | INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD |
| | THE NUMBER TO EACH SHEET. THIS MAY BE ADDED BY HAND. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |