2008-10-09 13:52:49BUILDING PLAN REVIEW
 PERMIT: 08090577
 ADD: 5500 VILLAGE BLVD
 CONT: PRESIDENTIAL CONSTRUCTION
 TEL: (561)723-3370
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
  
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 2) 61G1-16.004 FL. ADMIN. CODE. PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH
 MUST:
 - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEALED
 INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING THE
 PLANS
  
 3) SHEET A-2 DOOR B IS MISSING THE REQUIRED 18" ON THE
 PULL SIDE OF THE PULL SIDE OF DOOR. 11-4.13.6
 MANEUVERING CLEARENCES, AT DOORS. MINIMUM MANEUVERING
 CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL
 BE AS SHOWN IN FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL.
  
 4) SHEET A-4 DETAIL BREAK ROOM ELEVATION INDICATES
 DOORS ON THE SINK BASE UNIT. SINKS:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE MOUNTED WITH
 THE COUNTER NO HIGHER THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH
 SECTION 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A SINK
 TO ALLOW FORWARD APPROACH.
 THE CLEAR FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE
 AND SHALL EXTEND A MAXIMUM OF 19 INCHES (485 MM)
 UNDERNEATH THE SINK.
  
 5) THE COVERSHEET LIST THIS AS A TYPE III-B FULLY
 SPRINKLERED BUILDING WHERE AS THE LS -1 INDICATES THE
 BUILDING TO BE A V-B FULLY SPRINKLERED BUILDING. PLEASE
 COORDINATE PLANS TO A MINIMUM
 BUILDING TYPE. TABLE 503 & TABLE 601.
  
 6) GONZALEZ & GONZALEZ ENGINEERING, INC IS MISSING
 THEIR CERTIFICATE OF AUTHORIZATION.
 471.023 F.S. CERTIFICATE OF AUTHORIZATION. THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD
 THE NUMBER TO EACH SHEET. THIS MAY BE ADDED BY HAND.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.