| 2008-10-01 13:24:28 | BUILDING PLAN REVIEW |
| | PERMIT: 08090571 |
| | ADD: 1600 FLORIDA MANGO RD |
| | CONT: SOUTHEAST CERTIFIED CONST. INC. |
| | TEL: (561)635-6935 NAT HEALY |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT, |
| | TO BE FILED WITH THE CLERK OF THE COURT. NOTE: |
| | 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 1C) PLEASE PROVIDE THE MINIMUM BUILDING TYPE TABLE 503, |
| | / 1407.10, / 1407.11. |
| | |
| | 1D) PLEASE PROVIDE IF THIS BUILDING IS FIRE SPRINKLERED |
| | AND OR HAS TAKEN AREA INCREASES FOR FIRE SPRINKLERS? |
| | TABLE 503. |
| | |
| | 1E) |
| | 2) SHEET S-14 WEST ELEVATION: |
| | |
| | 2A) WEST ELEVATION, UPPER WINDOWS 5'-0" X 12'-0" THERE |
| | ARE NO WINDOW DETAILS INDICATING IF THIS IS TO BE A |
| | SINGLE PAINE OF GLASS OR MULTIPLE WINDOW LIGHTS WITH |
| | MULLIONS? THIS WILL EFFECT THE DESIGN LOAD CAPACITY AND |
| | THE DESIGN WIDTH AND LENGTH OF THE WINDOW UNIT. |
| | 1609.6.2.2. |
| | |
| | 2B) THESE SAME WINDOWS INDICATE THE USE OF A BAHAMA |
| | TYPE SHUTTER WITH NOA TOP SHEET IS MISSING THE NOA |
| | NUMBER?, ALSO MISSING THE E1 SHEET, TECHNICAL SHEETS |
| | 1-4. MISSING PAGE 1 INDICATES SINGLE SPAN SHUTTER IS |
| | 28", AND THE MAXIMUM LENGTH IS 76INCHES NOT THE 12'-0" |
| | AS INDICATED ON THE PLAN. SHEET 9 OF THE NOA NOTE 1 |
| | ALSO INDICATES THERE TO BE A MINIMUM OF 2.25 DISTANCE |
| | FROM THE GLASS TO SHUTTER, PLEASE PROVIDE A CUT SECTION |
| | OF THIS WINDOW WITHIN THE WALL AND THE USE OF THIS |
| | SHUTTER ATTACHMENT WITH PROPER SPACING.1609.6.2.2, RULE |
| | 9B-72 (31) (B), RULE 9B-72(31)(E). |
| | |
| | 2C) WEST ELEVATION DIRECTLY OVER THE FRONT DOOR WHAT |
| | APPEARS TO BE EITHER A CANOPY OR WINDOWS. THE ELEVATION |
| | DOES SHOW SHADING MAKING IT APPEAR THIS AREA PROJECTS |
| | OUT FROM THE WALL LINE. |
| | SHEET S.06 THE UPPER VIEW INDICATES THIS TO BE OPENINGS |
| | AND DIRECTLY BENEATH THE DETAIL IT READS NEW RECESSED |
| | ENTRY, BUT THE HEIGHT IS NOT PROVIDED NOR IS THERE A |
| | CUT SECTION THROUGH THIS AREA |
| | TO INDICATE WHAT AREA IS ACTUALLY RECESSED, THE DOORS |
| | OR THE DOORS AND WINDOWS ABOVE. DETAIL "F" SHEET S1.0 |
| | IT APPEARS TO BE 1/2 OF THE WINDOWS THE PRODUCT |
| | APPROVAL SUBMITTED IS A NOA 07-0423.08 SMALL MISSLE |
| | IMPACT AND THE WINDOW HEIGHT LOCATION IS LESS THAN |
| | 30'-0" REQUIRING LARGE MISSLE IMPACT WINDOWS OR |
| | APPROVED STORM COVERINGS OF SOME FORM SHUTTERS, PANELS, |
| | ETC. PLEASE CORRDINATE THIS AREA .106.1.2 ADDITIONAL |
| | INFORMATION REQUIRED. 1609.1.4. |
| | |
| | 2D) WEST ELEVATION GLAZED FRONT DOORS: SUBMITTED NOA |
| | 04-1208.01 ARCH OUTSWING DOORS THE MAXIMUM DOOR HEIGHT |
| | IS 96" AND WIDTH OF 72" MAXIMUM, S.06 THE LOCATION ON |
| | THIS PLAN INDICATES THE OPENINGS TO BE 8'-0" WIDE AND |
| | 11'-0" TALL. SHEET S.06 DOES ALSO INDICATE OPENINGS OF |
| | 6'-6" ON EITHER SIDE OF THE 8'-0" OPENINGS IS THIS A |
| | DISCREPANCY IN THE PLANS AND IF SO WHAT IS TO ENFILL |
| | THE 8'-0"X 11'-0" OPENINGS. |
| | 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | EAST ELEVATION: |
| | |
| | 2E) PLANS INDICATE 2 DOUBLE DOORS THE PRDODUCT |
| | APPROVALS SUBMITTED FOR COMMERCIAL STEEL DOORS INDICATE |
| | DOOR NUMBERS 28, 33,34,35 & 36. NOWHERE ON THE |
| | STRUCTURAL PLANS ARE THESE OPENINGS PROVIDEED, ARE |
| | THERE ARCHITECTURAL PLANS THAT DO INDICATE WHERE THESE |
| | DOORS ARE LOCATED IN RELATIONSHIP TO THE PRODUCT |
| | APPROVALS? 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 2F) THE INGERSOLL-RAND NOA'S SUBMITTED 02-0712.01 & |
| | 02-0712.03 ARE EXPIRED AS OF MARCH 13, 2008. PLEASE |
| | PROVIDE CURRENT PRODUCT APPROVALS. 1609.1.4, RULE |
| | 9B-72-31. |
| | |
| | 2G) EAST ELEVATION, UPPER WINDOWS 5'-0" X 12'-0" THERE |
| | ARE NO WINDOW DETAILS INDICATING IF THIS IS TO BE A |
| | SINGLE PAINE OF GLASS OR MULTIPLE WINDOW LIGHTS WITH |
| | MULLIONS? THIS WILL EFFECT THE DESIGN LOAD CAPACITY AND |
| | THE DESIGN WIDTH AND LENGTH OF THE WINDOW UNIT. |
| | 1609.6.2.2. |
| | |
| | 2H) THESE SAME WINDOWS INDICATE THE USE OF A BAHAMA |
| | TYPE SHUTTER WITH NOA TOP SHEET IS MISSING THE NOA |
| | NUMBER?, ALSO MISSING THE E1 SHEET, TECHNICAL SHEETS |
| | 1-4. MISSING PAGE 1 INDICATES SINGLE SPAN SHUTTER IS |
| | 28", AND THE MAXIMUM LENGTH IS 76INCHES NOT THE 12'-0" |
| | AS INDICATED ON THE PLAN. SHEET 9 OF THE NOA NOTE 1 |
| | ALSO INDICATES THERE TO BE A MINIMUM OF 2.25 DISTANCE |
| | FROM THE GLASS TO SHUTTER, PLEASE PROVIDE A CUT SECTION |
| | OF THIS WINDOW WITHIN THE WALL AND THE USE OF THIS |
| | SHUTTER ATTACHMENT WITH PROPER SPACING.1609.6.2.2, RULE |
| | 9B-72 (31) (B), RULE 9B-72(31)(E). |
| | |
| | |
| | |
| | NORTH ELEVATION : |
| | 2I) 20 WINDOWS LOCATED BETWEEN 16' TO 22' FROM GRADE DO |
| | NOT INDICATE ANY TYPE OF STORM SHUTTERS OR PANELS AND |
| | THE ONLY PRODUCT APROVAL PROVIDED IS NOA 07-0423.08 |
| | SMALL MISSILE IMPACT. |
| | 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS |
| | REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| | SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| | GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| | ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| | AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| | OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE |
| | TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| | GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| | SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) |
| | ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL |
| | MISSILE TEST. PLEASE PROVIDE EITHER LARGE MISSILE |
| | IMPACT RATED GLAZING OR APPROVED STORM SHUTTERS OR |
| | PANELS. |
| | |
| | PLEASE NOTE: PLEASE NOTE: 104.6*/ 1609.1.4/ 1714.5 |
| | STANDARDS FOR WIND-BORNE DEBRIS IMPACT PROTECTION |
| | QUESTION# 13 RECOGNIZING SUCH CONCERNS AS ABSENTEE |
| | OWNERS, OR CASES WHERE LONGER TIME & EFFORT IS |
| | NECESSARY TO SECURE SHUTTERS ON LARGE OR MULTI-STORY |
| | BUILDINGS, WHAT MEASURES ARE BEING RECOMMENDED OR |
| | IMPLEMENTED TO ENSURE THAT COMPLETE INSTALLATION OR |
| | SECURING IS DONE SUFFICIENTLY IN ADVANCE OF THE |
| | HURRICANE? |
| | |
| | IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE |
| | GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE, |
| | SECTION 104.6 OF THE FLORIDA BUILDING CODE, BUILDING, |
| | CHAPTER 1, |
| | ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY |
| | OF WEST PALM BEACH, PROVIDES THE ABILITY FOR THE |
| | BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR |
| | ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION |
| | OF EXISTING BUILDINGS. |
| | |
| | IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR |
| | MULTI-STORY BUILDINGS, OR MULTIPLE |
| | ON THE SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST |
| | BE SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS |
| | FOR REVIEW BY THE CONSTRUCTION SERVICES DEPARTMENT. ANY |
| | SUCH PLAN SHALL INCLUDE, AT A MINIMUM, ON SITE LOCATION |
| | OF THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE |
| | SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH |
| | COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND |
| | THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS. |
| | PROTECTION OF OPENINGS SHALL BE ACCOMPLISHED WITHIN |
| | TWELVE (12) HOURS OR LESS OF THE |
| | OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER SERVICES |
| | OF A HURRICANE WATCH. |
| | |
| | PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD) |
| | ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE |
| | MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO |
| | REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN |
| | QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE, |
| | DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED |
| | UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE |
| | MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE |
| | BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO |
| | SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE. |
| | |
| | IN LEAU OF LARGE MISSLE IMPACT RATED WINDOWS, STORM |
| | SHUTTERS MAY BE USED ON THE FIRST FLOOR IF: 104.6*/ |
| | 1609.1.4/ 1714.5 STANDARDS FOR WIND-BORNE DEBRIS IMPACT |
| | PROTECTION. |
| | |
| | 3) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES, OF PRODUCT TESTING REPORTS, MISSING |
| | REPORTS ARE AS FOLLOWS: |
| | 3A) ROOFING ASSEMBLIES. RULE 9B-72(31)(D). |
| | |
| | 4) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 5) PLEASE COORDINATE THE ADDRESS ON THE PLANS 1590 TO |
| | THAT OF THE PERMIT APPLICATION AND THE PROPERTY CONTROL |
| | NUMBER TO 1600 FLORIDA MANGO ROAD. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |