| 2008-09-26 09:00:55 | BUILDING PLAN REVIEW |
| | PERMIT: 08090563 |
| | ADD: 700 S. ROSEMARY AVE #130 |
| | CONT: SCHIAPPA CONST. CORP. |
| | TEL: (561)482-9324 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | NOTE: THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION |
| | SHALL BE INDICATED ON THE PLANS. |
| | |
| | 3) PROVIDE A DETAIL DRAWING SHOWING HOW THE NEW |
| | METALLIC VENEER WILL BE ATTACHED TO THE EXISTING |
| | STRUCTURE. THE DETAIL SHALL INCLUDE WEATHER PROTECTION |
| | OF THE EXTERIOR WALL IN COMPLIANCE WITH SECTION 1403.2, |
| | VAPOR RETARDER PER SECTION 1403.3, THE ATTACHMENT |
| | DETAIL INCLUDING THE FASTENERS SPACING AND THE TYPE OF |
| | FASTENERS PER 1405.10.1 THE ATTACHMENTS AND SUPPORTS |
| | SHALL BE CAPABLE TO RESIST WINDS UP TO 140 MPH AND THE |
| | WIND LOADS AS SPECIFIED IN 1609, BUT IN NO CASE LESS |
| | THAN 20 PSF. PROVIDE THE MANUFACTURE SPECS FOR THE |
| | ?CHEMETAL? PRODUCT. PLEASE HI-LIGHT OR CIRCLE THE |
| | THICKNESS OF THE METAL VENEER FROM THE PRODUCT |
| | INFORMATION SHOWING COMPLIANCE WITH 1405.10. |
| | |
| | 4) 1405.10.2 WOOD STUDS, FURRING STRIPS OR OTHER WOOD |
| | SUPPORTS FOR EXTERIOR METAL VENEER SHALL BE APPROVED |
| | PRESSURE-TREATED WOOD OR PROTECTED AS REQUIRED IN |
| | SECTION 1403.2. JOINTS AND EDGES EXPOSED TO THE WEATHER |
| | SHALL BE CALKED WITH APPROVED DURABLE WATERPROOFING |
| | MATERIAL OR BY OTHER APPROVED MEANS TO PREVENT |
| | PENETRATION OF MOISTURE. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |
| | |