2009-07-27 18:01:36M1.03 DELTA 2 REVISION DENIED
  
 DETAIL #5 SHOWS AN INSTALLATION DETAIL FOR A SLEEVE TO
 BE USED WHERE DUCTS PENETRATE RATED WALL ASSEMBLIES
 WITHOUT FIRE DAMPERS. ALL DUCT PENETRATIONS OF RATED
 WALL ASSEMBLIES WHICH ARE ALLOWED WITHOUT FIRE DAMPERS
 SHALL BE PROTECTED WITH A LISTED THROUGH-PENETRATION
 FIRESTOP SYSTEM IN ACCORDANCE WITH RBC-M 607.1.1 AND
 FBC-B SECTION 712. INDICATE ON PLANS EACH LOCATION
 WHERE A FIRE DAMPER IS INSTALLED AND WHERE A
 THROUGH-PENETRATION FIRESTOP SYSTEM IS TO BE USED IN
 ACCORDANCE WITH FBC-M 607.8.
  