| Plan Review Notes For Permit 08090562 |
| Permit Number |
08090562 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2009-07-27 18:01:36 | M1.03 DELTA 2 REVISION DENIED | | | | | | DETAIL #5 SHOWS AN INSTALLATION DETAIL FOR A SLEEVE TO | | | BE USED WHERE DUCTS PENETRATE RATED WALL ASSEMBLIES | | | WITHOUT FIRE DAMPERS. ALL DUCT PENETRATIONS OF RATED | | | WALL ASSEMBLIES WHICH ARE ALLOWED WITHOUT FIRE DAMPERS | | | SHALL BE PROTECTED WITH A LISTED THROUGH-PENETRATION | | | FIRESTOP SYSTEM IN ACCORDANCE WITH RBC-M 607.1.1 AND | | | FBC-B SECTION 712. INDICATE ON PLANS EACH LOCATION | | | WHERE A FIRE DAMPER IS INSTALLED AND WHERE A | | | THROUGH-PENETRATION FIRESTOP SYSTEM IS TO BE USED IN | | | ACCORDANCE WITH FBC-M 607.8. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] | | | | | | DENIED REVISION PAGES FILED IN SMALL PLAN CABINET UNDER | | | "P" |
|