| 2009-02-06 15:17:09 | ** REDLINED PLANS | | | | | | 1) NOTE: FP SHEETS SEEM TO INDICATE NEW FIRE PUMP AND | | | JOCKEY PUMP HOWEVER ELECTRICAL RISER INDICATES BOTH AS | | | EXISTING. CALLED AND LEFT MESSAGE FOR THE ENGINEER TO | | | CONFIRM. FP SHEET WAS REDLINED TO STATE THESE ARE NOT | | | NEW AT THIS TIME AND ARE NOT INCLUDED IN THE SCOPE OF | | | WORK. | | | | | | 2) NOTE: TABLE FOR LPD CALCS SHOULD HAVE READ | | | 13-415.2.B | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|