2008-12-13 15:33:42REVIEW #: 2ND
 ACTION: PASS W/ PROVISO
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 COMMENTS 1,3,4 AND NOTE HAVE BEEN ADEQUATELY ADDRESSED.
 PERMIT MAY BE ISSUED WITH THE FOLLOWING PROVISO:
  
 *******************PROVISO*********************
 EXHAUST FAN EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED TO RESIST WIND PRESSURES IN ACCORDANCE WITH
 FBCM 301.13 AND FBCB 1609.
 PROVIDE MANUFACTURER'S DATA FOR WIND RESISTANCE OR A
 RATIONAL ANALYSIS FROM A FLORIDA LICENSED STRUCTURAL
 ENGINEER CERTIFYING THE PROPOSED FAN IS DESIGNED FOR
 WIND RESISTANCE BASED ON THE LOCATION INSTALLED
 (ELEVATION, EXPOSURE CATEGORY AND WIND IMPORTANCE
 FACTOR) AS DETERMINED BY FBCB SECTION 1609.
  
 NOTE: DESIGNER'S WRITTEN RESPONSE INDICATES NO FAN
 WHICH IS DESIGNED FOR WIND RESISTANCE COULD BE FOUND.
 THERE IS AT LEAST ONE AND POSSIBLY MORE EXHAUST FAN
 MANUFACTURERS WITH A LINE OF FANS DESIGNED FOR WIND
 RESISTANCE. THIS OFFICE IS PROHIBITED BY POLICY FROM
 RECOMMENDING SPECIFIC BRANDS OR MANUFACTURERS. A SEARCH
 OF MIAMI-DADE'S NOA DATABASE MAY PROVIDE ADDITIONAL
 GUIDANCE IN YOUR SEARCH FOR A CODE COMPLAINT OUTDOOR
 APPLIANCE. AN NOA IS NOT SPECIFICALLY REQUIRED FOR
 OUTDOOR APPLIANCES. HOWEVER, THE DATA PROVIDED IN A
 CURRENT NOA MAY BE USED AND WOULD BE ACCEPTED BY THIS
 AHJ AS A DEMONSTRATION OF CODE COMPLIANCE.
  