2008-12-23 15:21:01** DENIED REVIEW**
  
  
 1) NOTE: PLEASE SEE THAT THE ORIGINAL PERMIT
 APPLICATION WAS NOT BROUGHT BACK IN WHEN PLANS WERE
 RESUBMITTED. IN FACT THE APPLICATION IN PACKAGE IS A
 PHOTO-COPY OF THE ORIGINAL.
 PLEASE BRING BACK THE ORIGINAL SIGNED PERMIT
 APPLICATION WHEN RE-SUBMITTING.
 NO SUB CONTRACTORS ARE SIGNED ON.
  
 2) NOTE: PLEASE SEE FBC 13-415.1.ABC.1, .1.1, .1.2,
 .1.3. LIGHTING CONTROLS AS SHOWN DO NOT COMPLY FOR
 AUTOMATED LIGHTING CONTROLS. THIS IS LIGHTING CONTROLS
 IN A BUILDING GREATER THAN 5000 SQ FT. ALL NEW LIGHTING
 CONTROLS BEING INSTALLED SHALL BE AUTOMATED OF SOME
 SORT. A MANUAL SWITCH DOES NOT MEET THE CODE.
 A MANUAL OVER RIDE OF A SYSTEM, IF A SYSTEM IS PROPOSED
 IS PERMITTED HOWEVER THERE IS DOZENS OF WAYS TO COMPLY
 WITH THE MINIMUM PRESCRIPTIVE REQUIREMENTS.
 13-
  
  
 3) NOTE: PLEASE SUBMIT AND SHOW MINIMUM CODE COMPLIANCE
 FOR LIGHTING PERFORMANCE CALCULATIONS AS PART OF THE
 RECORD PLANS. THE SEPARATE SUBMITTED SHEET DOES NOT
 CONTAIN ANY INFORMATION FROM THE ELECTRICAL DESIGNER OF
 RECORD. NO TITLE BLOCKS, NOT SIGNED AND SEALED ETC.
 PLEASE SEE THE ALLOWANCES ON THIS SHEET ALSO NEED TO BE
 ADJUSTED FOR CODE COMPLIANCE. ONE EXAMPLE WOULD BE
 STORAGE ROOM WHICH INDICATES AN ALLOWANCE FROM FBC OF
 1.1. HOWEVER NO STORAGE ROOMS LISTED IN TABLE FBC
 13-415.2.B ALLOWS A 1.1 FOR STORAGE. IN FACT HOSPITAL
 STORAGE AREAS IS ACTUALLY THE HIGHEST WHICH IS .09.
 PLEASE COMPLETE FIXTURE LEGEND FOR ALL FIXTURES.
 EXAMPLE OF ONE IS *G* WHICH IS BLANK.
 PLEASE ADJUST FBC ALLOWANCES, PLEASE PLACE ON PLANS,
 PLEASE COMPLETE TITLE BLOCKS, SIGNED, DATED SEALED ETC.
 13-415.2, 13-415.2.ABC.1.1, .1.2, FS 471.025, FAC
 61G15-23.002.
  
  
 4) NOTE: PLEASE SEE 410.5 AND 410.6 FOR LIGHT FIXTURE
 IN CLOSET AREA #104. AS SHOWN THIS APPEARS TO BE OVER
 SHELVING AREAS WHICH IS A FIRE HAZARD.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  