| 2008-09-25 16:01:23 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | NAPA 99C-99 |
| | FLORIDA ADMINISTRATIVE CODE |
| | |
| | 1. SHTS LS1.0 & LS1.1 CODE REFERENCE SHALL INCLUDE THE |
| | 2007 REVISIONS. |
| | |
| | 2. SHTS LS1.0 & LS1.1 OCCUPANCY STATES "SEE PLAN" |
| | PLEASE INDICATE WHERE ON THE PLANS THE OCCUPANCY OF THE |
| | STRUCTURE CAN BE LOCATED. |
| | |
| | 3. SHT A3.1 DETAIL 15 SHOWS THE FLUSH CONTROL FOR THE |
| | W/C TO THE WALL SIDE OF THE TANK. PER SECTION 11-4.16.5 |
| | THE FLUSH CONTROL SHALL BE ON THE WIDE SIDE. PLEASE |
| | SHOW THE FLUSH CONTROL WHERE REQUIRED. |
| | |
| | 4. SHT A3.1 DETAIL 15 CLEARANCE FOR THE LAV SHALL BE AT |
| | LEAST 29 INCHES PER SECTION 11-4.19.2. IT IS SHOWN AS |
| | 27 INCHES. |
| | |
| | 5. SHT A3.1 DETAIL 15 TUB CONTROLS SHALL BE LOCATED PER |
| | SECTION 11-4.20.5 & FIGURE 34. |
| | |
| | 6. SHT A3.1 DETAIL 21 SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | A. 11-4.24.3 KNEE CLEARANCE |
| | B. 11-4.24.4 SINK DEPTH |
| | C. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD APPROACH |
| | REQUIRED. CABINET DOORS NOT APPROVED IN THE CLEAR FLOOR |
| | SPACE. |
| | D. 11-4.24.6 EXPOSED PIPES & SURFACES |
| | |
| | 7. SHT P1.02 PER SECTION 406.3, THE AUTOMATIC CLOTHES |
| | WASHER FIXTURE DRAIN SHALL CONNECT TO A BRANCH DRAIN A |
| | MINIMUM OF 3 INCHES. 2 INCHES IS SHOWN. |
| | |
| | 8. A SEPARATE MED-GAS PERMIT IS REQUIRED. |
| | CERTIFICATIONS FOR THE QUALIFIER, THE INSTALLERS AND |
| | THE BRAZERS SHALL BE SUBMITTED WITH THE MED GAS PERMIT |
| | APPLICATION. FAC 61G4-15.031. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |