| Plan Review Notes For Permit 08090562 |
| Permit Number |
08090562 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-10-23 10:39:39 | ***DENIED*** | | | | | | 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003. | | | | | | 2) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER AND FIRE ALARM REMODEL. | | | | | | 3) DAMPERS TO BE TESTED FOR CLOSURE PER REQUIREMENTS OF | | | UL 555 PRIOR TO FINAL INSPECTION. | | | | | | 4) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR | | | WALLS AND CEILING. | | | | | | 5) ONLY ONE EXIT SHOWN IN AREAS WITH OCCUPANT LOAD OF | | | (61) PERSONS. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|