Plan Review Notes
Plan Review Notes For Permit 08090562
Permit Number 08090562
Review Stop E
Sequence Number 1
Notes
Date Text
2008-10-14 14:39:32 
 ** DENIED REVIEW**
  
  
 1) NOTE: THE SCOPE OF WORK FOR WHAT APPEARS TO BE A
 RESIDENTIAL UNIT HAS CREATED SEVERAL COMMENTS FROM
 MULTIPLE TRADES INCLUDING ZONING. IF THIS IS A SEPARATE
 RESIDENTIAL DWELLING/APARTMENT THE WIRING METHODS
 REQUIRED IN NEC 210.52, 2108 NEED TO BE MET.
 AN EXAMPLE OF THIS WOULD BE 210.52(D)3 FOR CIRCUITING
 OF THE BATH GFI WHICH IS SHOWN ON OTHER THAN THE
 BATHROOM WHICH IS NOT PERMITTED PER SECTION GIVEN.
 ANOTHER WOULD BE THE REQUIRED CIRCUITING FOR ARC FAULT
 PER 210.12. SPACING PER 210.52, SPACING ALONG KITCHEN
 COUNTER SPACE AREAS PER 210.52(C) 1-5 ETC
 AS THE SCOPE OF THIS UNCLEAR AT THIS TIME FOR THIS
 RESIDENTIAL UNIT, WIRING ETC CAN NOT BE CONFIRMED AS
 COMPLIANT. IF RESIDENTIAL THE WIRING AS SHOWN DOES NOT
 MEET THE NEC.
  
 2) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE FOR NEW
 AREAS WHERE LIGHTING IS BEING INSTALLED. 13-415.2,
 13-415.2.ABC.1.1, .1.2, TABLES 13-415.2.B, 13-415.2.C
  
 3) NOTE: PLEASE INDICATE LIGHTING CONTROL DEVICES PER
 13-415.1.ABC.1.1, .1.2, .1.3 FOR NEW BEING INSTALLED.
  
 4) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR ADA
 COMPLIANCE PER FBC 11-4.28.1, .2 AND .3.
  
 5) NOTE: THE LIGHTNING PROTECTION SYSTEM AS NOTED SHALL
 BE UNDER SEPARATE PERMIT AS WELL AS LOW VOLTAGE
 SYSTEMS. THE LOW VOLTAGE SYSTEM MAY REMAIN ON PLANS AND
 THESE PLANS MAY BE REFERENCED FOR A TURNAROUND PERMIT
 ONCE MAIN PERMIT IS ISSUED.
 SEPARATE FEES ETC WILL BE APPLIED FOR VALUE OF SCOPE.
  
 6) NOTE: THE PERMIT PACKAGE CONTAINS A RESPONSE LETTER
 FROM THE ENGINEER TO ELECTRICAL COMMENTS AS WELL AS
 RESPONSES TO OTHER TRADES. THIS IS THE FIRST TIME THIS
 IS IN FOR PERMITTING AND IT IS UNCLEAR WHERE THESE
 RESPONSES COME FROM. THE ELECTRICAL NOTES WHICH WERE
 RESPONDED TO WERE NOT FROM THIS OFFICE.
 A CALL WAS PLACED TO THE ELECTRICAL ENGINEER OF RECORD
 TO CLARIFY WHERE THESE NOTES CAME FROM HOWEVER WAS OUT
 OF THE OFFICE AT THE TIME OF THE REVIEW.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved