| Date |
Text |
| 2008-10-14 14:39:32 | |
| | ** DENIED REVIEW** |
| | |
| | |
| | 1) NOTE: THE SCOPE OF WORK FOR WHAT APPEARS TO BE A |
| | RESIDENTIAL UNIT HAS CREATED SEVERAL COMMENTS FROM |
| | MULTIPLE TRADES INCLUDING ZONING. IF THIS IS A SEPARATE |
| | RESIDENTIAL DWELLING/APARTMENT THE WIRING METHODS |
| | REQUIRED IN NEC 210.52, 2108 NEED TO BE MET. |
| | AN EXAMPLE OF THIS WOULD BE 210.52(D)3 FOR CIRCUITING |
| | OF THE BATH GFI WHICH IS SHOWN ON OTHER THAN THE |
| | BATHROOM WHICH IS NOT PERMITTED PER SECTION GIVEN. |
| | ANOTHER WOULD BE THE REQUIRED CIRCUITING FOR ARC FAULT |
| | PER 210.12. SPACING PER 210.52, SPACING ALONG KITCHEN |
| | COUNTER SPACE AREAS PER 210.52(C) 1-5 ETC |
| | AS THE SCOPE OF THIS UNCLEAR AT THIS TIME FOR THIS |
| | RESIDENTIAL UNIT, WIRING ETC CAN NOT BE CONFIRMED AS |
| | COMPLIANT. IF RESIDENTIAL THE WIRING AS SHOWN DOES NOT |
| | MEET THE NEC. |
| | |
| | 2) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE FOR NEW |
| | AREAS WHERE LIGHTING IS BEING INSTALLED. 13-415.2, |
| | 13-415.2.ABC.1.1, .1.2, TABLES 13-415.2.B, 13-415.2.C |
| | |
| | 3) NOTE: PLEASE INDICATE LIGHTING CONTROL DEVICES PER |
| | 13-415.1.ABC.1.1, .1.2, .1.3 FOR NEW BEING INSTALLED. |
| | |
| | 4) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR ADA |
| | COMPLIANCE PER FBC 11-4.28.1, .2 AND .3. |
| | |
| | 5) NOTE: THE LIGHTNING PROTECTION SYSTEM AS NOTED SHALL |
| | BE UNDER SEPARATE PERMIT AS WELL AS LOW VOLTAGE |
| | SYSTEMS. THE LOW VOLTAGE SYSTEM MAY REMAIN ON PLANS AND |
| | THESE PLANS MAY BE REFERENCED FOR A TURNAROUND PERMIT |
| | ONCE MAIN PERMIT IS ISSUED. |
| | SEPARATE FEES ETC WILL BE APPLIED FOR VALUE OF SCOPE. |
| | |
| | 6) NOTE: THE PERMIT PACKAGE CONTAINS A RESPONSE LETTER |
| | FROM THE ENGINEER TO ELECTRICAL COMMENTS AS WELL AS |
| | RESPONSES TO OTHER TRADES. THIS IS THE FIRST TIME THIS |
| | IS IN FOR PERMITTING AND IT IS UNCLEAR WHERE THESE |
| | RESPONSES COME FROM. THE ELECTRICAL NOTES WHICH WERE |
| | RESPONDED TO WERE NOT FROM THIS OFFICE. |
| | A CALL WAS PLACED TO THE ELECTRICAL ENGINEER OF RECORD |
| | TO CLARIFY WHERE THESE NOTES CAME FROM HOWEVER WAS OUT |
| | OF THE OFFICE AT THE TIME OF THE REVIEW. |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |