Plan Review Notes
Plan Review Notes For Permit 08090562
Permit Number 08090562
Review Stop B
Sequence Number 1
Notes
Date Text
2008-10-10 14:37:36BUILDING PLAN REVIEW
 PERMIT: 08090562
 ADD: 4847 FRED GLADSTONE DR.
 CONT: PRETI CONSTRUCTION INC.
 TEL: (561)840-9949
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 10-9-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. INDICATE THIS
 INFORMATION ON THE PLANS.
  
 4) SHEET LS1.0 INDICATES THE OCCUPANT LOAD OF THE
 BUILDING PER TABLE 1004.1.2.
  
 5) SHEET A1.1 DOORS #14 AND #16 SHALL MEET THE
 REQUIREMENTS OF FBC 11-4.13.6 AND FIGURE 25. SHOW
 COMPLIANCE. 11-4.2.3 THE SPACE REQUIRED FOR A
 WHEELCHAIR TO MAKE A 180-DEGREE TURN IS A CLEAR SPACE
 OF 60 INCHES DIAMETER. SHOW THE WHEELCHAIR TURNING
 SPACE IN THE AREAS OF THE DOORS MENTIONED ABOVE.
 INDICATE THE WIDTH OF THE CORRIDOR AFTER THE NEW WALLS
 ARE CONSTRUCTED IN THIS AREA.
  
 6) THE FLOOR PLAN ON SHEET A1.1 AND SHEET FP1.02 DO NOT
 CORRESPOND WITH EACH OTHER. THE NEW WALLS CONSTRUCTED
 AROUND DOORS #10 #11 AND #14 ARE NOT SHOWN ON SHEET
 FP1.02. THIS IS CRITICAL FOR THE LAYOUT OF THE NEW FIRE
 SPRINKLER HEADS. THE DOOR SCHEDULE INDICATES THE DOOR
 AS TEMPORARY BUT THE PLANS DO NOT STATE THE WALLS AS
 TEMPORARY WALLS. IF BOTH THE WALLS AND DOORS IN THESE
 AREAS ARE TEMPORARY STRUCTURES BUILT TO CONTROL THE
 DUST FROM TRAVELING INTO OTHER AREAS BEING OCCUPIED
 PLEASE INDICATE THIS INFORMATION ON THE PLANS.
  
 7) SHEET LS1.1 INDICATES DOOR #10 AS AN EGRESS DOOR
 HOWEVER, SHEET A1.1 SHOWS A NEW WALL CLOSING OFF THIS
 DOOR. PLEASE MAKE SURE THE FLOOR PLAN ON THE
 ARCHITECTURAL SHEETS CORRESPOND WITH THE ?MEP AND FS
 SHEETS. CLARIFY.
  
 8) THE OCCUPANT LOAD FOR ROOM #111-#113 IS A TOTAL OF
 61 OCCUPANTS, THEREFORE, TWO EXITS SHALL BE PROVIDED
 FOR THAT ROOM. FBC 1014 AND TABLE 1014.1 AND 1018 AND
 TABLE 108.1 IF ANY EQUIPMENT WILL BE PLACED IN THIS
 ROOM PLEASE SHOW THE LOCATIONS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  