| 2008-10-10 14:37:36 | BUILDING PLAN REVIEW |
| | PERMIT: 08090562 |
| | ADD: 4847 FRED GLADSTONE DR. |
| | CONT: PRETI CONSTRUCTION INC. |
| | TEL: (561)840-9949 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 10-9-08 |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. INDICATE THIS |
| | INFORMATION ON THE PLANS. |
| | |
| | 4) SHEET LS1.0 INDICATES THE OCCUPANT LOAD OF THE |
| | BUILDING PER TABLE 1004.1.2. |
| | |
| | 5) SHEET A1.1 DOORS #14 AND #16 SHALL MEET THE |
| | REQUIREMENTS OF FBC 11-4.13.6 AND FIGURE 25. SHOW |
| | COMPLIANCE. 11-4.2.3 THE SPACE REQUIRED FOR A |
| | WHEELCHAIR TO MAKE A 180-DEGREE TURN IS A CLEAR SPACE |
| | OF 60 INCHES DIAMETER. SHOW THE WHEELCHAIR TURNING |
| | SPACE IN THE AREAS OF THE DOORS MENTIONED ABOVE. |
| | INDICATE THE WIDTH OF THE CORRIDOR AFTER THE NEW WALLS |
| | ARE CONSTRUCTED IN THIS AREA. |
| | |
| | 6) THE FLOOR PLAN ON SHEET A1.1 AND SHEET FP1.02 DO NOT |
| | CORRESPOND WITH EACH OTHER. THE NEW WALLS CONSTRUCTED |
| | AROUND DOORS #10 #11 AND #14 ARE NOT SHOWN ON SHEET |
| | FP1.02. THIS IS CRITICAL FOR THE LAYOUT OF THE NEW FIRE |
| | SPRINKLER HEADS. THE DOOR SCHEDULE INDICATES THE DOOR |
| | AS TEMPORARY BUT THE PLANS DO NOT STATE THE WALLS AS |
| | TEMPORARY WALLS. IF BOTH THE WALLS AND DOORS IN THESE |
| | AREAS ARE TEMPORARY STRUCTURES BUILT TO CONTROL THE |
| | DUST FROM TRAVELING INTO OTHER AREAS BEING OCCUPIED |
| | PLEASE INDICATE THIS INFORMATION ON THE PLANS. |
| | |
| | 7) SHEET LS1.1 INDICATES DOOR #10 AS AN EGRESS DOOR |
| | HOWEVER, SHEET A1.1 SHOWS A NEW WALL CLOSING OFF THIS |
| | DOOR. PLEASE MAKE SURE THE FLOOR PLAN ON THE |
| | ARCHITECTURAL SHEETS CORRESPOND WITH THE ?MEP AND FS |
| | SHEETS. CLARIFY. |
| | |
| | 8) THE OCCUPANT LOAD FOR ROOM #111-#113 IS A TOTAL OF |
| | 61 OCCUPANTS, THEREFORE, TWO EXITS SHALL BE PROVIDED |
| | FOR THAT ROOM. FBC 1014 AND TABLE 1014.1 AND 1018 AND |
| | TABLE 108.1 IF ANY EQUIPMENT WILL BE PLACED IN THIS |
| | ROOM PLEASE SHOW THE LOCATIONS. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |