| 2008-10-06 17:03:21 | RESIDENTIAL (R3) SHED, BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 |
| | REVISIONS. |
| | |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTES. |
| | ***NOTE: THIS MAY BE SUBMITTED LATER AT TIME OF PERMIT |
| | PICK UP. |
| | |
| | 2- ENGINEER WHO SEALED THE DRAWINGS NEEDS TO USE NEW |
| | SEAL (EFFECTIVE ON JANUARY OF 2002) THAT READS |
| | "LICENSE" INSTEAD OF "CERTIFICATE" AS REQUIRED BY SEC. |
| | 471.025 FLORIDA STATUTE AND SEC. 61G15-23.001 OF |
| | FLORIDA ENGINEERS ADMINISTRATIVE CODE. ENGINEER IS |
| | STILL USING THE SEAL THAT READS CERTIFICATE. |
| | |
| | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A)(1) EXTERIOR DOOR. PRODUCT APPROVAL FL10024 SUBMITTED |
| | DOESN'T MATCH TYPE OF DOOR TO BE INSTALLED. DRAWING #4 |
| | OF SHED DRAWINGS SHOW SINGLE DOOR, WHILE, DRAWINGS |
| | SUBMITTED WITH PRODUCT APPROVAL ARE FOR DOUBLE DOORS. |
| | PROVIDE CORRECT SET OF DRAWINGS. GO TO |
| | WWW.FLORIDABUILDING.ORG AND DOWNLOAD CORRECT DRAWINGS. |
| | |
| | A)(2) PROVIDE LEGIBLE DRAWINGS FOR EXTERIOR DOOR. |
| | DRAWINGS SUBMITTED ARE NOT LEGIBLE. |
| | |
| | B)(1) SINGLE HUNG WINDOWS: NEED TO PROVIDE DRAWINGS. |
| | NONE WERE SUBMITTED THIS TIME. |
| | |
| | B)(2) MAKE SURE WINDOW DRAWINGS SHOW THE DESIGN |
| | PRESSURES FOR WHICH IT WAS DESIGNED AND MAKE SURE THEY |
| | MEET THE DESIGN PRESSURES CALCULATED BY THE ENGINEER. |
| | (NOTE: COORDINATE WITH ITEM #4 BELOW). PRODUCT APPROVAL |
| | SUBMITTED DOESN'T SPECIFY ANY DESIGN PRESSURES. |
| | |
| | 4- ENGINEER TO REVISE THE DESIGN WIND LOAD REQUIREMENTS |
| | FOR COMPONENTS SHOWN ON DESIGN REQUIREMENTS SEC. 2. C |
| | OF DRAWINGS SUBMITTED. THE BASIC WIND SPEED IS 140MPH |
| | MIN. REVISE THE BASIC WIND SPEED AND THE COMPONENT |
| | DESIGN PRESSURES AS REQUIRED. SEC. R301.1 OF 2004 |
| | FLORIDA RESIDENTIAL CODE. ALL BUILDING AND STRUCTURES |
| | NEED TO BE DESIGNED FOR 140 MPH WIND LOAD. SEC. 117 OF |
| | CITY AMENDMENTS TO FBC 2004. |
| | |
| | 5- OWES $16.06 FOR PERMIT VALUATION UPDATE AS REQUIRED |
| | BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004. |
| | |