| 2008-10-06 14:01:03 | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE AND THE CITY OF |
| | WEST PALM BEACH GAS PERMIT APPLICATION REQUIREMENTS. |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE SECTION 401.1 SCOPE. |
| | *NOTE: THE SUBMITTED GAS ISOMETRIC DOES NOT INDICATE |
| | CORRESPONDING LENGTHS TO ALL CUT SECTION OF PROPOSED |
| | PIPE. PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT |
| | SECTIONS WITH NO CORRESPONDING LENGTHS AND COMPLY WITH |
| | THE REQUIRED INFORMATION ON THE RESUBMITTAL. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. PER FBC-2004 FUEL |
| | GAS CODE SECTION 401.1 SCOPE. |
| | *NOTE: THE SUBMITTED GAS ISOMETRIC IS ONLY INDICATING |
| | 3/4" PE UNDERGROUND PIPING FOR THE PROPOSED GENERATOR. |
| | WHAT IS THE ABOVEGROUND PIPING MATERIAIL AND SIZE FOR |
| | THE PROPOSED GENERATOR AND AT THE METER LOCATION? |
| | |
| | 3. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | *NOTE: THE BTU LOAD FOR THE PROPOSED GENERATOR IS BEING |
| | INDICATED AS BEING 698,000, HOWEVER THE GENERATOR |
| | MANUFACTURER'S SPECIFICATION SHEETS ARE INDICATING THE |
| | BTU'S FOR THE PROPOSED GENERATOR AS BEING 485,000. |
| | PLEASE CORRELATE THE PLANS WITH THE GENERATOR |
| | SUBMITTAL. ALSO CLEARLY INDICATE THE TOTAL BTU"S FOR |
| | THE SYSTEM ON THE RESUBMITTED ISOMETRIC. PLANS ARE |
| | INDICATING SEE PERMIT #08040470, HOWEVER THAT GAS |
| | PERMIT IS CLOSED AND THAT INFORMATION IS NO LONGER |
| | AVAILABLE. |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | *NOTE: CLEARLY INDICTAE THE LONGEST LENGTH OF THE |
| | SYSTEM ON THE RESUBMITTED GAS ISOMETRIC. PLEASE KNOW |
| | THAT THIS INCLUDES THE EXISTING GAS SYSTEM. |
| | |
| | 5. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| | FBC-2004 CHAPTER 1, (W.P.B. AS AMENDED) SECTION |
| | *106.3.4.3. |
| | *NOTE: THE PRINTED AND ORIGINAL SIGNATURE OF THE PERSON |
| | TAKING RESPONSIBILITY FOR THE GAS ISOMETRIC IS REQUIRED |
| | ON THE RESUBMITTAL. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |