| 2008-12-12 11:12:56 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. DECLARE WIND DESIGN CRITERIAL FBC1603.1.4 AND | | | GOVERNING CODE, INCLUDING 2007 REVISIONS/SUPPLEMENTS. | | | | | | 2. DECLARE LEVEL OF ALTERATION FBC EB301.5 ON THE PLAN. | | | | | | 3. PROVIDE A REVISED VALUATION FOR THIS JOB. | | | | | | 4. THE DETAILS SUBMITTED DO NOT CLEARLY SHOW SCOPE OF | | | WORK, FBC*106, FBC1609, FBC EB 507. FOR INSTANCE, 2X4 | | | KNEE WALL IS NOT NOTED AS EXISTING OR NEW. THIS APPLIES | | | TO ALL DETAILS. PLEASE CLARIFY, WHICH ELEMENTS ARE | | | BEING REPLACED? WHICH REMAIN AS EXISTING? | | | | | | 5. 7-D1, SPECIFY STRAP; BRAND AND SPECIFY STRAP OR | | | OPTIONS. FAC9B72. | | | | | | 6. CONCRETE TOPPING SHOWN, IS THIS NEW OR EXISTING? | | | | | | 7. NO ANCHORS SHOWN AT THE HEAD OF WALL (2X6 TO 2X6). | | | FBC EB 507. | | | | | | 8. PLEASE CONFIRM THAT NAILING SPECIFIED MEETS OR | | | EXCEEDS MANUFACTURER'S SPECIFICATIONS FOR ALL | | | CONNECTORS, FBC1609. | | | | | | |
|