Plan Review Notes
Plan Review Notes For Permit 08090511
Permit Number 08090511
Review Stop G
Sequence Number 2
Notes
Date Text
2008-12-11 16:50:20GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 200R FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 SECOND REVIEW:
 ****FROM PREVIOUS REVIEW:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THE SUBMITTED GAS SITE AND ISOMETRIC RISER DIAGRAM
 ARE INDICATING THE PLAN SHEET TO BE COMPLIANT WITH THE
 "SOUTH FLORIDA BUILDING CODE 2004". PLEASE KNOW THAT
 THE SOUTH FLORIDA BUILDING CODE WAS FOR THE MIAMI-DADE
 AND BROWARD COUNTIES. ALSO PLEASE KNOW THAT THIS IS THE
 WRONG CODE CYCLE AND HAS NEVER BEEN ADOPTED BY THE CITY
 OF WEST PALM BEACH. PLEASE KNOW THAT AS OF JULY 1, 2001
 THE FLORIDA BUILDING CODE HAS BEEN ADOPTED BY THE STATE
 OF FLORIDA TO BE THE GOVERNING CODE AND THAT THE
 CORRECT CODE CYCLES THAT SHOULD BE ON ANY FUTURE PLAN
 SHEETS SHOULD BE "FBC-2004 WITH 2007 REVISIONS".
 ****NO WRITTEN COMMENT RESPONSE, BUT WORK IS NOW
 INDICATED AS COMPLIANT WITH NFPA #54 & #58. PLANS SHALL
 BE COMPLIANT WITH FBC-2004 FUEL GAS CODE. PLEASE
 INDICATE ON PLANS.
  
 2. THE SUBMITTED PROPANE TANK HOLD DOWN DETAIL HAS AN
 ENGINEER TITLE BLOCK (CARMO ENGINEERING ASSOCIATES,
 INC.) WITH A COPIED SIGNATURE AND DATE WITH NO
 EMBOSSING IMPRESSION SEAL WHICH IS UNACEPTABLE PER FAC
 61G15-23.001. PLEASE KNOW THAT THE FOLLOWING
 INFORMATION IS ALSO REQUIRED TO BE ON THE TITLE BLOCK.
 SEE FAC 61G15-23.002(2) A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
 NOTE: PER FS 471.003(2)(H) THE CONTRACTOR CAN DO THE
 DESIGN AS LONG AS HE/SHE TAKES THE RESPONSIBILITY FOR
 THE DESIGN BY PRINTING HIS/HER NAME WITH AN ORIGINAL
 SIGNATURE AND DATE.
 ****NO WRITTEN COMMENT RESPONSE AND NOW THE NEW TANK
 HOLD DOWN DETAIL IS FOR AN ABOVE GROUND TANK. THE
 APPLICATION INDICATES AN UNDERGROUND TANK. PLEASE
 CLARIFY.
  
 3. PLEASE CLEARLY INDICTE THE REQUIRED 1ST STAGE
 REGULATOR ON THE RESUBMITTED GAS ISOMETRIC RISER
 DIAGRAM. PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 4. PLEASE SUBMIT TWO COPIES OF MANUFACTURE SHEETS FOR
 THE 1ST AND 2ND STAGE REGULATORS COMPLIANT WITH
 STANDARDS NFPA 58 AND THE FBC-2004 FUEL GAS CODE
 SECTION 402.2. MANUFACTURE SHEETS MUST CLEARLY INDICATE
 THE MAKE, MODEL NUMBER, BTU LOAD CAPACITY, AND A
 LISTING FROM A NATIONALLY RECOGNIZED TESTING LABORATORY
 SUCH AS CSA, AGA, OR UL.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 5. PLEASE POVIDE MANUFACTURE SPECIFICATIONS FOR THE
 GENERATOR CLEARLY INDICATING THE RECOMMENDED SETBACKS
 FROM STRUCTURES.
 ****NO RESPONSE, COMMENT NOT ADDRESSED. -- SUBMIT
 INSTALLATION INSTRUCTIONS SHOWING ALL CLEARANCES FOR
 EACH SIDE OF THE GENERATOR.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  