| Date |
Text |
| 2008-12-11 16:50:20 | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 200R FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | SECOND REVIEW: |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. THE SUBMITTED GAS SITE AND ISOMETRIC RISER DIAGRAM |
| | ARE INDICATING THE PLAN SHEET TO BE COMPLIANT WITH THE |
| | "SOUTH FLORIDA BUILDING CODE 2004". PLEASE KNOW THAT |
| | THE SOUTH FLORIDA BUILDING CODE WAS FOR THE MIAMI-DADE |
| | AND BROWARD COUNTIES. ALSO PLEASE KNOW THAT THIS IS THE |
| | WRONG CODE CYCLE AND HAS NEVER BEEN ADOPTED BY THE CITY |
| | OF WEST PALM BEACH. PLEASE KNOW THAT AS OF JULY 1, 2001 |
| | THE FLORIDA BUILDING CODE HAS BEEN ADOPTED BY THE STATE |
| | OF FLORIDA TO BE THE GOVERNING CODE AND THAT THE |
| | CORRECT CODE CYCLES THAT SHOULD BE ON ANY FUTURE PLAN |
| | SHEETS SHOULD BE "FBC-2004 WITH 2007 REVISIONS". |
| | ****NO WRITTEN COMMENT RESPONSE, BUT WORK IS NOW |
| | INDICATED AS COMPLIANT WITH NFPA #54 & #58. PLANS SHALL |
| | BE COMPLIANT WITH FBC-2004 FUEL GAS CODE. PLEASE |
| | INDICATE ON PLANS. |
| | |
| | 2. THE SUBMITTED PROPANE TANK HOLD DOWN DETAIL HAS AN |
| | ENGINEER TITLE BLOCK (CARMO ENGINEERING ASSOCIATES, |
| | INC.) WITH A COPIED SIGNATURE AND DATE WITH NO |
| | EMBOSSING IMPRESSION SEAL WHICH IS UNACEPTABLE PER FAC |
| | 61G15-23.001. PLEASE KNOW THAT THE FOLLOWING |
| | INFORMATION IS ALSO REQUIRED TO BE ON THE TITLE BLOCK. |
| | SEE FAC 61G15-23.002(2) A TITLE BLOCK ON EACH SHEET |
| | CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE |
| | NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND |
| | LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS |
| | AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE |
| | ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT. |
| | NOTE: PER FS 471.003(2)(H) THE CONTRACTOR CAN DO THE |
| | DESIGN AS LONG AS HE/SHE TAKES THE RESPONSIBILITY FOR |
| | THE DESIGN BY PRINTING HIS/HER NAME WITH AN ORIGINAL |
| | SIGNATURE AND DATE. |
| | ****NO WRITTEN COMMENT RESPONSE AND NOW THE NEW TANK |
| | HOLD DOWN DETAIL IS FOR AN ABOVE GROUND TANK. THE |
| | APPLICATION INDICATES AN UNDERGROUND TANK. PLEASE |
| | CLARIFY. |
| | |
| | 3. PLEASE CLEARLY INDICTE THE REQUIRED 1ST STAGE |
| | REGULATOR ON THE RESUBMITTED GAS ISOMETRIC RISER |
| | DIAGRAM. PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 4. PLEASE SUBMIT TWO COPIES OF MANUFACTURE SHEETS FOR |
| | THE 1ST AND 2ND STAGE REGULATORS COMPLIANT WITH |
| | STANDARDS NFPA 58 AND THE FBC-2004 FUEL GAS CODE |
| | SECTION 402.2. MANUFACTURE SHEETS MUST CLEARLY INDICATE |
| | THE MAKE, MODEL NUMBER, BTU LOAD CAPACITY, AND A |
| | LISTING FROM A NATIONALLY RECOGNIZED TESTING LABORATORY |
| | SUCH AS CSA, AGA, OR UL. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 5. PLEASE POVIDE MANUFACTURE SPECIFICATIONS FOR THE |
| | GENERATOR CLEARLY INDICATING THE RECOMMENDED SETBACKS |
| | FROM STRUCTURES. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. -- SUBMIT |
| | INSTALLATION INSTRUCTIONS SHOWING ALL CLEARANCES FOR |
| | EACH SIDE OF THE GENERATOR. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |