| 2008-10-01 10:40:35 | *** PROVISO *** |
| | 1) PER 2004 FBC, FUEL GAS - POWERED EQUIPMENT |
| | PERMANENTLY INSTALLED EQUIPMENT POWERED BY INTERNAL |
| | COMBUSTION ENGINES SHALL BE INSTALLED IN ACCORDANCE |
| | WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS AND NFPA |
| | 37. |
| | NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION |
| | ENGINES & GAS TURBINES: 4.1.4 ENGINES (GENERATORS) |
| | LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT FROM OPENINGS |
| | IN WALLS & AT LEAST 5 FT FROM STRUCTURES HAVING |
| | COMBUSTIBLE WALLS. A MINIMUM CLEARANCE IS NOT REQUIRED |
| | WHEN (1) THE ADJACENT WALL HAS A MINIMUM FIRE |
| | RESISTANCE RATING OF 1 HOUR OR (2) THE WEATHERPROOF |
| | ENCLOSURE IS CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, |
| | AND IT HAS BEEN DEMONSTRATED THAT A FIRE WITHIN THE |
| | ENCLOSURE WILL NOT IGNITE COMBUSTIBLE MATERIALS OUTSIDE |
| | THE ENCLOSURE. INFORMATIVE: A.8.2.3.1 EXHAUST SYSTEMS |
| | SHOULD NOT TERMINATE UNDER STRUCTURES OR WHERE THE |
| | EXHAUST MIGHT BE DRAWN INTO THE VENTILATION INTAKES. |
| | 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS LOCATED |
| | BELOW AN ADJACENT ROOF STRUCTURE, THE TERMINATION POINT |
| | SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF STRUCTURE. |
| | PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL EQUIPMENT |
| | TO ENCROACH 4 FT INTO THE REQUIRED SETBACK, GENERATORS |
| | SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED CLEARANCES |
| | TO THE ADJACENT PROPERTY STRUCTURES, I.E. FENCE, |
| | BUILDING, WINDOWS, DOORS, OR OPENINGS. FOLLOW |
| | MANUFACTURER'S RECOMMENDED CLEARANCES AROUND EQUIPMENT |
| | FOR SERVICING,AND PROVIDE MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS AT THE JOBSITE FOR THE FIELD INSPECTOR. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729 |