Plan Review Notes For Permit 08090511
Permit Number 08090511
Review Stop M
Sequence Number 1
Notes
Date Text
2008-10-01 10:40:35*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED EQUIPMENT
 PERMANENTLY INSTALLED EQUIPMENT POWERED BY INTERNAL
 COMBUSTION ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS AND NFPA
 37.
 NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION
 ENGINES & GAS TURBINES: 4.1.4 ENGINES (GENERATORS)
 LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT FROM OPENINGS
 IN WALLS & AT LEAST 5 FT FROM STRUCTURES HAVING
 COMBUSTIBLE WALLS. A MINIMUM CLEARANCE IS NOT REQUIRED
 WHEN (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE WEATHERPROOF
 ENCLOSURE IS CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS,
 AND IT HAS BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE MATERIALS OUTSIDE
 THE ENCLOSURE. INFORMATIVE: A.8.2.3.1 EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR WHERE THE
 EXHAUST MIGHT BE DRAWN INTO THE VENTILATION INTAKES.
 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS LOCATED
 BELOW AN ADJACENT ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF STRUCTURE.
 PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL EQUIPMENT
 TO ENCROACH 4 FT INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED CLEARANCES
 TO THE ADJACENT PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS. FOLLOW
 MANUFACTURER'S RECOMMENDED CLEARANCES AROUND EQUIPMENT
 FOR SERVICING,AND PROVIDE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AT THE JOBSITE FOR THE FIELD INSPECTOR.
  
 MECHANICAL PLAN REVIEW BY;