2008-10-01 15:01:41GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THE SUBMITTED GAS SITE AND ISOMETRIC RISER DIAGRAM
 ARE INDICATING THE PLAN SHEETS TO BE COMPLIANT WITH THE
 "SOUTH FLORIDA BUILDING CODE 2004". PLEASE KNOW THAT
 THE SOUTH FLORIDA BUILDING CODE WAS FOR THE MIAMI-DADE
 AND BROWARD COUNTIES. ALSO PLEASE KNOW THAT THIS IS THE
 WRONG CODE CYCLE AND HAS NEVER BEEN ADOPTED BY THE CITY
 OF WEST PALM BEACH. PLEASE KNOW THAT AS OF JULY 1, 2001
 THE FLORIDA BUILDING CODE HAS BEEN ADOPTED BY THE STATE
 OF FLORIDA TO BE THE GOVERNING CODE AND THAT THE
 CORRECT CODE CYCLES THAT SHOULD BE ON ANY FUTURE PLAN
 SHEETS SHOULD BE "FBC-2004 WITH 2007 REVISIONS".
  
 2. THE SUBMITTED PROPANE TANK HOLDOWN DETAIL HAS AN
 ENGINEER TITLE BLOCK (CARMO ENGINEERING ASSOCIATES,
 INC.) WITH A COPIED SIGNATURE AND DATE WITH NO
 EMBOSSING IMPRESSION SEAL WHICH IS UNACCEPTABLE PER FAC
 61G15-23.001. PLEASE KNOW THAT THE FOLLOWING
 INFORMATION IS ALSO REQUIRED TO BE ON THE TITLE BLOCK.
 SEE FAC 61G15-23.002 (2) A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
 NOTE: PER FS 471.003(2)(H) THE CONTRACTOR CAN DO THE
 DESIGN AS LONG AS HE/SHE TAKES THE RESPOSIBILITY FOR
 THE DESIGN BY PRINTING HIS/HER NAME WITH ORIGINAL
 SIGNATURE AND DATE.
  
 3. PLEASE CLEARLY INDICATE THE REQUIRED 1ST STAGE
 REGULATOR ON THE RESUBMITTED GAS ISOMETRIC RISER
 DIAGRAM. PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE.
  
 4. PLEASE SUBMIT TWO COPIES OF MANUFACTURE SHEETS FOR
 THE 1ST AND 2ND STAGE REGULATORS COMPLIANT WITH
 STANDARDS NFPA 58, AND THE FBC-2004 FUEL GAS CODE SEC
 402.2. MANUFACTURE SHEETS MUST CLEARLY INDICATE THE
 MAKE, MODEL NUMBER, BTU LOAD CAPACITY, AND A LISTING
 FROM A NATIONALLY RECOGNIZED TESTING LABORATORY SUCH AS
 CAS, AGA, OR UL.
  
 5. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS FOR THE
 GENERATOR CLEARLY INDICATING THE RECOMMENDED SETBACKS
 FROM STRUCTURES.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  