| 2008-09-30 16:16:57 | |
| | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 |
| | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON |
| | A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE, |
| | DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH |
| | ARTICLES 225 AND 230 CAN BE REVIEWED. |
| | |
| | 2} THE RISER DIAGRAM INDICATES THE CONDUIT FROM THE |
| | METER TO THE ATS IS NOT USED. IT IS NOT CLEAR HOW THE |
| | ATS WILL RECEIVE NORMAL POWER. IF FROM THE 200 AMP |
| | PANEL, INDICATE THE NUMBER OF CONDUCTORS FROM THAT |
| | PANEL TO THE JUNCTION BOX (3 SHOWN) THEN THERE WOULD BE |
| | SIX , 3 TO AND 3 FROM (PLUS EQUIPMENT GROUND) THE |
| | ATS.215.5. |
| | |
| | 3} THE DIAGRAM ALSO INDICATES 3-#4 CONDUCTORS FEEDING |
| | THE 200 AMP PANEL FROM THE METER. INDICATE THE SIZE OF |
| | THE MAIN OCP IN THE 200 AMP PANEL. 215.5, 310.16. |
| | INDICATE IF THE SERVICE, OR WHICH PARTS, ARE NEW AND |
| | WHICH ARE EXISTING. |
| | |
| | 4} IF THE SERVICE IS 200 AMP THE GEC REQUIRED PER |
| | 250.66 DOES NOT COMPLY. |
| | |
| | 5} INDICATE THAT THE LOAD CALCULATION GIVEN IS FOR THE |
| | GENERATOR PANEL THE CALCULATION SHEET. LABEL PANELS |
| | ACCORDINGLY. |
| | |
| | 6} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE |
| | GENERATOR INDICATING RECOMMENDED SETBACKS FROM |
| | STRUCTURES. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | |