Plan Review Notes
Plan Review Notes For Permit 08090511
Permit Number 08090511
Review Stop E
Sequence Number 1
Notes
Date Text
2008-09-30 16:16:57 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE,
 DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 2} THE RISER DIAGRAM INDICATES THE CONDUIT FROM THE
 METER TO THE ATS IS NOT USED. IT IS NOT CLEAR HOW THE
 ATS WILL RECEIVE NORMAL POWER. IF FROM THE 200 AMP
 PANEL, INDICATE THE NUMBER OF CONDUCTORS FROM THAT
 PANEL TO THE JUNCTION BOX (3 SHOWN) THEN THERE WOULD BE
 SIX , 3 TO AND 3 FROM (PLUS EQUIPMENT GROUND) THE
 ATS.215.5.
  
 3} THE DIAGRAM ALSO INDICATES 3-#4 CONDUCTORS FEEDING
 THE 200 AMP PANEL FROM THE METER. INDICATE THE SIZE OF
 THE MAIN OCP IN THE 200 AMP PANEL. 215.5, 310.16.
 INDICATE IF THE SERVICE, OR WHICH PARTS, ARE NEW AND
 WHICH ARE EXISTING.
  
 4} IF THE SERVICE IS 200 AMP THE GEC REQUIRED PER
 250.66 DOES NOT COMPLY.
  
 5} INDICATE THAT THE LOAD CALCULATION GIVEN IS FOR THE
 GENERATOR PANEL THE CALCULATION SHEET. LABEL PANELS
 ACCORDINGLY.
  
 6} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE
 GENERATOR INDICATING RECOMMENDED SETBACKS FROM
 STRUCTURES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  