| Plan Review Notes For Permit 08090511 |
| Permit Number |
08090511 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-10-09 09:01:54 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR | | | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS | | | FAC61G15-23.002 (PROPANE TANK HOLDDOWN DETAIL). | | | | | | 2. THE PROPANE TANK HOLDDOWN DETAIL SHOULD INCLUDE WIND | | | DESIGN CRITERIA, FBC R 301 (WIND SPEED, EXPOSURE). | | | | | | 3. PROVIDE A STRUCTURAL DETAIL FOR THE GENERATOR SLAB, | | | FBC R 301. IF A PREFAB SLAB IS USED, | | | ENGINEERING/CALCULATIONS ARE REQUIRED TO SHOW THAT WIND | | | LOADS WILL BE RESISTED. | | | | | | | | | |
|