2008-10-09 09:01:54****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FAC61G15-23.002 (PROPANE TANK HOLDDOWN DETAIL).
  
 2. THE PROPANE TANK HOLDDOWN DETAIL SHOULD INCLUDE WIND
 DESIGN CRITERIA, FBC R 301 (WIND SPEED, EXPOSURE).
  
 3. PROVIDE A STRUCTURAL DETAIL FOR THE GENERATOR SLAB,
 FBC R 301. IF A PREFAB SLAB IS USED,
 ENGINEERING/CALCULATIONS ARE REQUIRED TO SHOW THAT WIND
 LOADS WILL BE RESISTED.
  
  
  