| Date |
Text |
| 2008-09-19 14:39:51 | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. THE VALUE ON THE PERMIT APPLICATION APPEARS LOW. THE |
| | VALUE ON THE PERMIT APPLICATION MUST INCLUDE THE TOTAL |
| | COST OF LABOR AND MATERIALS (THIS INCLUDES THE COST OF |
| | THE FIRE PLACE EVEN IF OWNER SUPPLIED). VALUATION |
| | REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF A |
| | NATIONAL CONSTRUCTION COST ANALYSIS (MARSHALL-SWIFT, |
| | MEANS, ECT...) ADJUST THE VALUE AT THE PERMIT CLERK'S |
| | DESK AND PAY THE DIFFERENCE IN FEES PRIOR TO |
| | RESUBMITTING. PER (W.P.B. AS AMENDED) SECTION 108.3 |
| | BUILDING PERMIT VALUATION. |
| | |
| | 2. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE SECTION 401.1 SCOPE. |
| | *NOTE: SUBMITTED ISOMETRIC DOES NOT INDICATE |
| | CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE. |
| | |
| | 3. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE. |
| | *NOTE: NOT ALL CUT SECTIONS OF PIPE INDICATE PIPE |
| | MATERIAL. |
| | |
| | 4. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | *NOTE: THE EXISTING BTU LOAD NEEDS TO BE INDICATED ON |
| | THE PLANS. PLEASE REFERENCE THE PERMIT INFORMATION |
| | SHEET OF SAID ADDRESS ATTACHED TO THESE COMMENTS |
| | INDICATING EXISTING GAS AND COMPLY. |
| | |
| | 5. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | *NOTE: THE EXISTING SYSTEMS LONGEST LENGTH NEEDS TO BE |
| | INDICATED ON THE PLANS. |
| | |
| | 6. SUBMITTED PLANS ARE INDICATING A DELIVERY PRESSURE |
| | OF 5 PSI, HOWEVER PLANS ARE ALSO INDICATING TABLES |
| | 402.4(2) AND 402.4(14) WHICH ARE FOR 0.5 PSI DELIVERY |
| | PRESSURE. PLEASE CORRECT AND CORRELATE PLANS AND IF |
| | NEEDED CLEARLY INDICATE THE REQUIRED LINE PRESSURE |
| | REGULATORS LOCATION (MP REGULATOR) ON THE RESUBMITTAL. |
| | PLEASE KNOW THAT WITH ALL THE EXISTING APPLIANCES ON |
| | THE SYSTEM THE EXISTING METER MIGHT HAVE A 2 PSI |
| | DELIVERY PRESSURE. PER FBC-2004 FUEL GAS SECTION 410.1 |
| | PRESSURE REGULATORS AND SECTION 401.1 SCOPE. |
| | |
| | 7. SUBMIT CALCULATIONS FOR THE FIRE PLACE COMBUSTION |
| | AIR. PER FBC-2004 FUEL GAS CODE SECTION 304. |
| | |
| | 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | *NOTE: NEED MANUFACTURE SHEETS FOR THE FOLOWING |
| | APPLIANCES AND EQUIPMENT. |
| | |
| | A} FIRE PLACE: CLEARLY INDICATE THE MAKE, MODEL NUMBER, |
| | BTU LOAD CAPACITY, AND A LISTING FROM A NATIONALLY |
| | RECOGNIZED TESTING LABORATORY (LISTING EXAMPLES= CSA, |
| | AGA,UL) |
| | |
| | B} MP REGULATOR: (SAME REQUIREMENTS REQUIRED FOR MP |
| | REGULATORS AS WAS REQUESTED FOR THE FIRE PLACE). |
| | |
| | 9. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| | SECTION *106.3.4.3. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |