| 2008-09-30 14:33:19 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. PROVIDE A DETAIL OF THE BADU JET PUMP TWO 8" MAIN |
| | DRAINS AS INDICATED ON SHEET 1. PLEASE KNOW THAT SHEET |
| | 2 OF 2, PLUMBING DETAIL FOR BADU JET DOES NOT INDICATE |
| | THE REQUIRED DRAINS. PER R4101.6.6.4. |
| | |
| | 2. SHEET 1 OF 2, INDICATES "SEE MFGR'S SPECS" FOR THE |
| | BADU JET PUMP, HOWEVER NONE WERE PROVIDED. PLEASE |
| | PROVIDE TWO COPIES OF MANUFACTURE SPECFICATION FOR THE |
| | BADU JET PUMP CLEARLY INDICATING THE MAKE, MODEL NUMBER |
| | AND A LISTING FROM A NATIONALLY RECOGNIZED TESTING |
| | LABORATORY SUCH AS UL. PER (W.P.B. AS AMENDED) SECTION |
| | 106.1.2 ADDITIOAL DATA REQUIRED. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |