Plan Review Notes
Plan Review Notes For Permit 08090459
Permit Number 08090459
Review Stop E
Sequence Number 2
Notes
Date Text
2008-11-06 10:39:58 
  
  
 ** DENIED 2ND REVIEW **
  
 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW WITH
 RESPECT TO LIGHTING PERFORMANCE CALCULATIONS. PLEASE
 SEE SECTIONS 13-415.2.ABC.1.1,.1.2. THE REQUIRED
 LIGHTING VA PER FIXTURE SHALL BE BASE DON THE MAXIMUM
 VA A FIXTURE IS RATED FOR NOT THE BULB WATTAGE. AN
 EXAMPLE IS THE FACT THE *C* FIXTURE AS LISTED IN
 ACTUALLY A FIXTURE WHICH IS RATED FOR TWICE THE WATTAGE
 THAN FIGURED IN THE CALCULATIONS SUBMITTED. MUST USE
 THE MAXIMUM VA OF FIXTURE OR BALLAST IF HID ETC. ( IF
 HID, FLUORESCENT ETC CHECK EFFICIENCY RATINGS OF
 BALLAST THIS MAY HELP).
  
 2) NOTE: PLEASE PROVIDE THE SELECTIVE COORDINATION OF
 NEW EQUIPMENT AND BREAKERS. 240.12,700.27, 701.18.
 PLEASE SEE 517.17 FOR REQUIRED GFI PROTECTION OF
 SYSTEMS.
 ** RESPONSE MENTIONS THIS ELECTRICAL IS ON THE NORMAL
 POWER. PLEASE INDICATE THIS INFORMATION ON THE SIGNED
 AND SEALED RECORD PLANS. THE RESPONSE LETTER HAS NO
 LEGEL RECORD PART OF THE PLANS.
  
 3) NOTE: PLEASE PROVIDE LOADS ON EXISTING SERVICE/MAIN
 IN WHICH THE NEW PANEL IS BEING FED FROM.
 NEC 220
 RESPONSE WRITES ABOUT LOADS REMOVED ETC HOWEVER THIS
 INFORMATION NEEDS TO BE ON THE PLANS.
 FBC 106.1.1 FOR ADDITIONAL INFORMATION.
  
 4) NOTE: PLEASE INDICATE THE LOCATIONS OF NEW
 HORNS/STROBES OR EXISTING WHICH MEET NFPA-72 AS WELL AS
 FBC 11-4.28.1, .2 AND .3 FOR ADA COMPLIANCE.
 THE PLANS NEED TO SHOWS THE LEVELS FOR MINIMUM
 COMPLIANCE. PLEASE KNOW THE FBC CAN BE MORE RESTRICTIVE
 IN SOME ASPECTS.
  
 5) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  