| 2008-11-06 10:39:58 | |
| | |
| | |
| | ** DENIED 2ND REVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW WITH |
| | RESPECT TO LIGHTING PERFORMANCE CALCULATIONS. PLEASE |
| | SEE SECTIONS 13-415.2.ABC.1.1,.1.2. THE REQUIRED |
| | LIGHTING VA PER FIXTURE SHALL BE BASE DON THE MAXIMUM |
| | VA A FIXTURE IS RATED FOR NOT THE BULB WATTAGE. AN |
| | EXAMPLE IS THE FACT THE *C* FIXTURE AS LISTED IN |
| | ACTUALLY A FIXTURE WHICH IS RATED FOR TWICE THE WATTAGE |
| | THAN FIGURED IN THE CALCULATIONS SUBMITTED. MUST USE |
| | THE MAXIMUM VA OF FIXTURE OR BALLAST IF HID ETC. ( IF |
| | HID, FLUORESCENT ETC CHECK EFFICIENCY RATINGS OF |
| | BALLAST THIS MAY HELP). |
| | |
| | 2) NOTE: PLEASE PROVIDE THE SELECTIVE COORDINATION OF |
| | NEW EQUIPMENT AND BREAKERS. 240.12,700.27, 701.18. |
| | PLEASE SEE 517.17 FOR REQUIRED GFI PROTECTION OF |
| | SYSTEMS. |
| | ** RESPONSE MENTIONS THIS ELECTRICAL IS ON THE NORMAL |
| | POWER. PLEASE INDICATE THIS INFORMATION ON THE SIGNED |
| | AND SEALED RECORD PLANS. THE RESPONSE LETTER HAS NO |
| | LEGEL RECORD PART OF THE PLANS. |
| | |
| | 3) NOTE: PLEASE PROVIDE LOADS ON EXISTING SERVICE/MAIN |
| | IN WHICH THE NEW PANEL IS BEING FED FROM. |
| | NEC 220 |
| | RESPONSE WRITES ABOUT LOADS REMOVED ETC HOWEVER THIS |
| | INFORMATION NEEDS TO BE ON THE PLANS. |
| | FBC 106.1.1 FOR ADDITIONAL INFORMATION. |
| | |
| | 4) NOTE: PLEASE INDICATE THE LOCATIONS OF NEW |
| | HORNS/STROBES OR EXISTING WHICH MEET NFPA-72 AS WELL AS |
| | FBC 11-4.28.1, .2 AND .3 FOR ADA COMPLIANCE. |
| | THE PLANS NEED TO SHOWS THE LEVELS FOR MINIMUM |
| | COMPLIANCE. PLEASE KNOW THE FBC CAN BE MORE RESTRICTIVE |
| | IN SOME ASPECTS. |
| | |
| | 5) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |