| Date |
Text |
| 2008-10-07 11:41:13 | |
| | ** DENIED ** |
| | |
| | 1) NOTE: PLANS INDICATE SOME OF NOTES FOR A LIGHTING |
| | CONTROL PANEL HOWEVER SPACE CONTROLS PER FBC |
| | 13-415.1.ABC.1.1 ARE NOT MET BASED ON THE SYMBOL LEGEND |
| | ONLY CALLING FOR A STANDARD SINGLE POLE SWITCH DEVICE. |
| | |
| | |
| | 2) NOTE: PLEASE INDICATE THE LIGHTING PERFORMANCE |
| | CALCULATIONS PER 13-415.2,13-415.2.ABC.1.1,.1.2. PLEASE |
| | CALL TO GO OVER HOW PRESCRIPTIVE REQUIREMENTS CAN BE |
| | MET. |
| | |
| | 3) NOTE: PLEASE PROVIDE THE SELECTIVE COORDINATION OF |
| | NEW EQUIPMENT AND BREAKERS. 240.12,700.27, 701.18. |
| | PLEASE SEE 517.17 FOR REQUIRED GFI PROTECTION OF |
| | SYSTEMS. |
| | |
| | 4) NOTE: PLEASE PROVIDE LOADS ON EXISTING SERVICE/MAIN |
| | IN WHICH THE NEW PANEL IS BEING FED FROM. |
| | NEC 220 |
| | FBC 106.1.1 FOR ADDITIONAL INFORMATION. |
| | |
| | 5) NOTE: PLEASE INDICATE THE LOCATIONS OF NEW |
| | HORNS/STROBES OR EXISTING WHICH MEET NFPA-72 AS WELL AS |
| | FBC 11-4.28.1, .2 AND .3 FOR ADA COMPLIANCE. |
| | THE PLANS NEED TO SHOWS THE LEVELS FOR MINIMUM |
| | COMPLIANCE. PLEASE KNOW THE FBC CAN BE MORE RESTRICTIVE |
| | IN SOME ASPECTS. |
| | |
| | |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |