| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 |
| | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} 106.1 SUBMITTABLE DOCUMENTS. CONSTRUCTION DOCUMENTS, |
| | SPECIAL INSPECTION AND STRUCTURAL OBSERVATION PROGRAMS, |
| | AND OTHER DATA SHALL BE SUBMITTED IN TWO OR MORE SETS |
| | WITH EACH APPLICATION FOR A PERMIT. *** ONE PLAN COPIED |
| | MARKED 1ST AND 2ND FLOOR WAS SUBMITTED FOR REVIEW. THE |
| | PENCIL SET MUST BE COPIED AS PENCIL IS NOT ACCEPTABLE |
| | FOR RETENTION. SUBMIT TWO SETS FOR EACH FLOOR. |
| | |
| | 2} VERIFY THAT THE A/C UNITS ARE RATED AT 1500 WATTS. |
| | |
| | 3} 220.84 MULTIFAMILY DWELLING |
| | (A) FEEDER OR SERVICE LOAD IT SHALL BE PERMISSIBLE TO |
| | CALCULATE THE LOAD OF A FEEDER OR SERVICE THAT SUPPLIES |
| | THREE OR MORE DWELLING UNITS OF A MULTIFAMILY DWELLING |
| | IN ACCORDANCE WITH TABLE 220.84 INSTEAD OF PART III OF |
| | THIS ARTICLE-----" THE CALCULATION GIVEN TOOK THE |
| | DEMAND FROM 220.42 AND THEN AN ADDITIONAL DEMAND FROM |
| | 220.84, ONLY ONE DEMAND CAN BE TAKEN.SEE "INSTEAD OF". |
| | |
| | 4} 220.84 (B) HOUSE LOADS HOUSE LOADS SHALL BE |
| | CALCULATED IN ACCORDANCE WITH PART III OF THIS ARTICLE |
| | AND SHALL BE IN ADDITION TO THE DWELLING UNIT LOADS |
| | CALCULATED IN ACCORDANCE WITH TABLE 220.84.*** NO LOAD |
| | FOR THE HOUSE WAS GIVEN. |
| | |
| | 5} 220.52(B) LAUNDRY CIRCUIT LOAD A LOAD OF NOT LESS |
| | THAN 1500 VOLT-AMPERES SHALL BE INCLUDED FOR EACH |
| | 2-WIRE LAUNDRY BRANCH CIRCUIT INSTALLED AS REQUIRED BY |
| | 210.11(C)(2). THIS LOAD SHALL BE PERMITTED TO BE |
| | INCLUDED WITH THE GENERAL LIGHTING LOAD AND SUBJECTED |
| | TO THE DEMAND FACTORS PROVIDED IN TABLE 220.42.*** THIS |
| | MAY BE WITH THE HOUSE CIRCUIT CALCULATION. |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | 6} 210.11(C)(2) LAUNDRY BRANCH CIRCUITS IN ADDITION TO |
| | THE NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS |
| | OF THIS SECTION, AT LEAST ONE ADDITIONAL 20-AMPERE |
| | BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY THE LAUNDRY |
| | RECEPTACLE OUTLET(S) REQUIRED BY 210.52(F).*** THE |
| | HOUSE PANEL HAS THE LAUNDRY ON A 15 AMP CIRCUIT. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | |