| Date |
Text |
| 2008-10-27 10:47:41 | GAS PLAN REVIEW: |
| | DENIED **2ND TIME: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | **THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND |
| | WITH THE PREVIOUS GAS REVIEW COMMENTS AS WELL AS THE |
| | DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW |
| | COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW |
| | COMMENTS. (RESUBMITTED GAS PLANS LOCATED IN THE |
| | SUPPLEMENTAL INFORMATION BOOK) |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE SECTION 401.1 SCOPE. |
| | *NOTE: THE SUBMITTED ISOMETRIC DOES NOT INDICATE |
| | CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE. |
| | PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT SECTIONS |
| | OF PIPE WITH NO CORRESPONDING LENGTHS. |
| | |
| | **RESPONSE NOTED, HOWEVER THE RESUBMITTED GAS ISOMETRIC |
| | STILL HAS CUT SECTIONS OF PIPE WITH NO CORRESPONDING |
| | LENGTHS. PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT |
| | SECTION OF PIPE WITH NO CORRESPONDING LENGTHS AND |
| | COMPLY ON THE NEXT RESUBMITTAL. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | PER FBC-2004 FUEL GAS CODE SECTION 401.1 SCOPE. |
| | *NOTE: THE SUBMITTED ISOMETRIC DOES NOT INDICATE ANY OF |
| | THE ABOVEGROUND PIPING MATERIAL AS WELL AS SOME CUT |
| | SECTIONS OF UNDERGROUND PIPING. THE ISOMETRIC ALSO DOES |
| | NOT INDICATE PIPE SIZES TO ALL CUT SECTIONS OF PIPE. |
| | |
| | **RESPONSE NOTED, HOWEVER THE RESUBMITTED GAS ISOMETRIC |
| | ONLY INDICATION OF ABOVE GROUND PIPING MATERIAL IS ONE |
| | CUT SECTION OF 3/4" GALV. PIPE TO ONE TANKLESS WATER |
| | HEATER. WHAT IS THE PIPING MATERIAL TO THE OTHER ABOVE |
| | GROUND CUT SECTIONS OF PIPE? THE RESUBMITTED GAS |
| | ISOMETRIC ALSO STILL DOES NOT INDICATE THE PIPING |
| | MATERIAL ABOVE/UNDERGROUND OR PIPE SIZES TO THE TWO GAS |
| | LAMPS ON THE OUTLET SIDE OF THE MP REGULATORS. THE |
| | UNDERGROUND PIPING MATERIAL TO THE TANKLESS WATER |
| | HEATERS IS NOT INDICATED. |
| | |
| | 3. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | *NOTE: THE ISOMETRIC INDICATES 97' D.L. (LONGEST |
| | LENGTH), HOWEVER NOT ALL CUT SECTIONS OF GAS PIPE HAVE |
| | CORRESPONDING LENGTHS. PLEASE REFERENCE COMMENT #1 AND |
| | COMPLY. |
| | |
| | **RESPONSE NOTED, HOWEVER THE RESUBMITTED GAS ISOMETRIC |
| | NOW INDICATES 108' D.L. (LONGEST LENGTH) AND STILL NOT |
| | ALL CUT SECTIONS OF GAS PIPE HAVE CORRESPONDING |
| | LENGTHS. AGAIN PLEASE REFERENCE COMMENT #1 AND COMPLY. |
| | UNTIL COMMENT #1 IS FULLY ADDRESSED AND THIS COMMENT IS |
| | CORRELATED WITH COMMENT #1, THE COMMENT SHALL REMAIN. |
| | |
| | 4. "OK" COMMENT WAS ADDRESSED> |
| | |
| | 5. CLEARLY INDICATE THE LOCATION OF THE MP REGULATORS |
| | (2 PSI TO 0.5 PSI REGULATORS) ON THE RESUBMITTED |
| | ISOMETRIC OR PROVIDE A LEGEND OF HOW THEY APPEAR ON THE |
| | PLANS. ALSO PROVIDE A DETAIL OF THE GAS LAMP VALVE BOX |
| | CLEARLY INDICATING THE LOCATION OF THE SHUT OFF VALVE |
| | AND MP REGULATOR. PLEASE CLARIFY THE LOCATION OF THE |
| | GAS LAMP VALVE BOXES. IT APPEARS TO BE LOCATED AT |
| | FINNISH GRADE LEVEL. PLEASE CLARIFY HOW THE MP |
| | REGULATORS WILL WORK IF VALVE BOX FILLS WITH WATER |
| | DURING A STORM. PER FBC-2004 FUEL GAS CODE SECTION |
| | 401.1 SCOPE. |
| | |
| | **RESPONSE NOTED, AND COMMENT WAS PARTIALLY ADDRESSED. |
| | THE RESUBMITTED GAS ISOMETRIC STILL DOES NOT CLEARLY |
| | INDICATE THE REQUIRED MP REGULATORS (2 PSI TO 0.5 PSI |
| | REGULATORS) ON THE PLANS OR PROVIDE A LEGEND OF HOW |
| | THEY APPEAR ON THE PLANS. |
| | |
| | 6. THE COOK TOP NEEDS A SHUT OFF VALVE BEFORE THE MP |
| | REGULATOR IF THE CIRCLE IS A MP REGULATOR (REFERENCE |
| | COMMENT #5). PER FBC-2004 FUEL GAS, SECTION 409.4 MP |
| | REGULATOR VALVES: A LISTED SHUTOFF VALVE SHALL BE |
| | INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR. |
| | |
| | **RESPONSE NOTED, HOWEVER UNTIL THE MP REGULATORS ARE |
| | CLEARLY IDENTIFIED ON THE PLANS AS ASKED FOR IN COMMENT |
| | #5 THIS COMMENT SHALL REMAIN. |
| | |
| | 7. SUBMIT MANUFACTURE SHEETS FOR THE MP REGULATORS |
| | (2/PSI TO 0.5/PSI REGULATORS) TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE FBC-2004 FUEL GAS |
| | CODE SEC 402.2. THE MANUFACTURER SHEETS SHOULD CLEARLY |
| | INDICATE THE MP REGULATOR MAKE, MODEL NUMBER, BTU LOAD |
| | CAPACITY, AND A LISTING FROM A NATIONALLY RECOGNIZED |
| | TESTING LABORATORY SUCH AS CSA, AGA, OR UL. |
| | |
| | **RESPONSE NOTED, HOWEVER THIS COMMENT WAS NOT |
| | ADDRESSED. THE REQUIRED MANUFACTURE SHEETS FOR THE MP |
| | REGULATORS WAS NOT IN THE RESUBMITTAL PACKAGE. |
| | |
| | 8. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| | SECTION *106.3.4.3. |
| | IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER, |
| | THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL, |
| | SIGNATURE AND DATE TO SAID DRAWINGS, PER FLORIDA |
| | STATUTES 481 AND 471 RESPECTIVELY. |
| | |
| | **RESPONSE NOTED, HOWEVER THE RESUBMITTED GAS |
| | ISOMETRICS DO NOT HAVE ORIGINAL SIGNATURES ON THEM OF |
| | THE PERSON TAKING THE RESPONSIBILITY FOR THEM. THE |
| | SIGNATURES ARE COPIED FROM A FAX. |
| | |
| | **THE FOLLOWING IS A NEW COMMENT DUE TO THE RESUMITTED |
| | GAS ISOMETRIC. |
| | |
| | 9. A MP REGULATOR (2 PSI TO 0.5 PSI REGULATOR) IS |
| | REQUIRED FOR THE FUTURE B.B.Q. AND SHALL BE INSTALLED |
| | BEFORE FINAL GAS INSPECTION. PER FBC-2004 FUEL GAS CODE |
| | SECTION 410.1 PRESSURE REGULATOR. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | **PLEASE CALL IF THERE ARE ANY QUESTIONS. |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |