2008-10-27 10:47:41GAS PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 **THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND
 WITH THE PREVIOUS GAS REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW
 COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW
 COMMENTS. (RESUBMITTED GAS PLANS LOCATED IN THE
 SUPPLEMENTAL INFORMATION BOOK)
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE.
 *NOTE: THE SUBMITTED ISOMETRIC DOES NOT INDICATE
 CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE.
 PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT SECTIONS
 OF PIPE WITH NO CORRESPONDING LENGTHS.
  
 **RESPONSE NOTED, HOWEVER THE RESUBMITTED GAS ISOMETRIC
 STILL HAS CUT SECTIONS OF PIPE WITH NO CORRESPONDING
 LENGTHS. PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT
 SECTION OF PIPE WITH NO CORRESPONDING LENGTHS AND
 COMPLY ON THE NEXT RESUBMITTAL.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 PER FBC-2004 FUEL GAS CODE SECTION 401.1 SCOPE.
 *NOTE: THE SUBMITTED ISOMETRIC DOES NOT INDICATE ANY OF
 THE ABOVEGROUND PIPING MATERIAL AS WELL AS SOME CUT
 SECTIONS OF UNDERGROUND PIPING. THE ISOMETRIC ALSO DOES
 NOT INDICATE PIPE SIZES TO ALL CUT SECTIONS OF PIPE.
  
 **RESPONSE NOTED, HOWEVER THE RESUBMITTED GAS ISOMETRIC
 ONLY INDICATION OF ABOVE GROUND PIPING MATERIAL IS ONE
 CUT SECTION OF 3/4" GALV. PIPE TO ONE TANKLESS WATER
 HEATER. WHAT IS THE PIPING MATERIAL TO THE OTHER ABOVE
 GROUND CUT SECTIONS OF PIPE? THE RESUBMITTED GAS
 ISOMETRIC ALSO STILL DOES NOT INDICATE THE PIPING
 MATERIAL ABOVE/UNDERGROUND OR PIPE SIZES TO THE TWO GAS
 LAMPS ON THE OUTLET SIDE OF THE MP REGULATORS. THE
 UNDERGROUND PIPING MATERIAL TO THE TANKLESS WATER
 HEATERS IS NOT INDICATED.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 *NOTE: THE ISOMETRIC INDICATES 97' D.L. (LONGEST
 LENGTH), HOWEVER NOT ALL CUT SECTIONS OF GAS PIPE HAVE
 CORRESPONDING LENGTHS. PLEASE REFERENCE COMMENT #1 AND
 COMPLY.
  
 **RESPONSE NOTED, HOWEVER THE RESUBMITTED GAS ISOMETRIC
 NOW INDICATES 108' D.L. (LONGEST LENGTH) AND STILL NOT
 ALL CUT SECTIONS OF GAS PIPE HAVE CORRESPONDING
 LENGTHS. AGAIN PLEASE REFERENCE COMMENT #1 AND COMPLY.
 UNTIL COMMENT #1 IS FULLY ADDRESSED AND THIS COMMENT IS
 CORRELATED WITH COMMENT #1, THE COMMENT SHALL REMAIN.
  
 4. "OK" COMMENT WAS ADDRESSED>
  
 5. CLEARLY INDICATE THE LOCATION OF THE MP REGULATORS
 (2 PSI TO 0.5 PSI REGULATORS) ON THE RESUBMITTED
 ISOMETRIC OR PROVIDE A LEGEND OF HOW THEY APPEAR ON THE
 PLANS. ALSO PROVIDE A DETAIL OF THE GAS LAMP VALVE BOX
 CLEARLY INDICATING THE LOCATION OF THE SHUT OFF VALVE
 AND MP REGULATOR. PLEASE CLARIFY THE LOCATION OF THE
 GAS LAMP VALVE BOXES. IT APPEARS TO BE LOCATED AT
 FINNISH GRADE LEVEL. PLEASE CLARIFY HOW THE MP
 REGULATORS WILL WORK IF VALVE BOX FILLS WITH WATER
 DURING A STORM. PER FBC-2004 FUEL GAS CODE SECTION
 401.1 SCOPE.
  
 **RESPONSE NOTED, AND COMMENT WAS PARTIALLY ADDRESSED.
 THE RESUBMITTED GAS ISOMETRIC STILL DOES NOT CLEARLY
 INDICATE THE REQUIRED MP REGULATORS (2 PSI TO 0.5 PSI
 REGULATORS) ON THE PLANS OR PROVIDE A LEGEND OF HOW
 THEY APPEAR ON THE PLANS.
  
 6. THE COOK TOP NEEDS A SHUT OFF VALVE BEFORE THE MP
 REGULATOR IF THE CIRCLE IS A MP REGULATOR (REFERENCE
 COMMENT #5). PER FBC-2004 FUEL GAS, SECTION 409.4 MP
 REGULATOR VALVES: A LISTED SHUTOFF VALVE SHALL BE
 INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR.
  
 **RESPONSE NOTED, HOWEVER UNTIL THE MP REGULATORS ARE
 CLEARLY IDENTIFIED ON THE PLANS AS ASKED FOR IN COMMENT
 #5 THIS COMMENT SHALL REMAIN.
  
 7. SUBMIT MANUFACTURE SHEETS FOR THE MP REGULATORS
 (2/PSI TO 0.5/PSI REGULATORS) TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE FBC-2004 FUEL GAS
 CODE SEC 402.2. THE MANUFACTURER SHEETS SHOULD CLEARLY
 INDICATE THE MP REGULATOR MAKE, MODEL NUMBER, BTU LOAD
 CAPACITY, AND A LISTING FROM A NATIONALLY RECOGNIZED
 TESTING LABORATORY SUCH AS CSA, AGA, OR UL.
  
 **RESPONSE NOTED, HOWEVER THIS COMMENT WAS NOT
 ADDRESSED. THE REQUIRED MANUFACTURE SHEETS FOR THE MP
 REGULATORS WAS NOT IN THE RESUBMITTAL PACKAGE.
  
 8. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER,
 THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS, PER FLORIDA
 STATUTES 481 AND 471 RESPECTIVELY.
  
 **RESPONSE NOTED, HOWEVER THE RESUBMITTED GAS
 ISOMETRICS DO NOT HAVE ORIGINAL SIGNATURES ON THEM OF
 THE PERSON TAKING THE RESPONSIBILITY FOR THEM. THE
 SIGNATURES ARE COPIED FROM A FAX.
  
 **THE FOLLOWING IS A NEW COMMENT DUE TO THE RESUMITTED
 GAS ISOMETRIC.
  
 9. A MP REGULATOR (2 PSI TO 0.5 PSI REGULATOR) IS
 REQUIRED FOR THE FUTURE B.B.Q. AND SHALL BE INSTALLED
 BEFORE FINAL GAS INSPECTION. PER FBC-2004 FUEL GAS CODE
 SECTION 410.1 PRESSURE REGULATOR.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 **PLEASE CALL IF THERE ARE ANY QUESTIONS.
  