| 2008-09-29 15:50:57 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET P1.1, PLUMBING NOTES #2: PLUMBING NOTE #2 |
| | STATES "ALL SANITARY LINES SHALL HAVE A MINIMUM SLOPE |
| | OF 1/8" RISE PER ONE HORIZONTAL FOOT OF PIPE, UNLESS |
| | SPECIFICALLY INDICATED OTHERWISE". THIS IS NOT |
| | COMPLIANT WITH THE FBC-2004 PLUMBING TABLE 704.1 SLOPE |
| | OF HORIZONTAL DRAINAGE PIPE. TABLE 704.1 SPECIFICALLY |
| | INDICATES THE FOLLOWING MINIMUM SLOPE FOR THE FOLLOWING |
| | PIPE SIZES (2-1/2" OR LESS= 1/4" MINIMUM SLOPE PER |
| | FOOT) (3" TO 6"= 1/8" MINIMUM SLOPE PER FOOT) (8" OR |
| | LARGER= 1/16" MINIMUM SLOPE PER FOOT). PLEASE REVISE |
| | NOTE #2 PER THE FBC-2004 PLUMBING TABLE 704.1. |
| | |
| | 2. SHEET P1.1, SANITARY PLUMBING RISER DIAGRAM: |
| | CLEANOUTS ARE REQUIRED AT THE BASE OF THE FOLLOWING |
| | STACKS PER THE FBC-2004 PLUMBING SECTION 708.3.4 BASE |
| | OF STACK. |
| | |
| | A} HIS AND HER SANITARY STACK. |
| | |
| | B} BATH 2. |
| | |
| | C} BATH 3. |
| | |
| | D} BATH 4. |
| | |
| | 3. SHEET P1.1, SANITARY PLUMBING RISER DIAGRAM: THE |
| | AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL CONNECT TO |
| | A BRANCH DRAIN OR DRAINAGE STACK A MINIMUM OF 3 INCHES |
| | IN DIAMETER. PER FBC-2004 PLUMBING SECTION 406.3 WASTE |
| | CONNECTION. |
| | |
| | 4. SHEET P1.1, SANITARY PLUMBING RISER DIAGRAM: CLEARLY |
| | INDICATE THE SIZES OF ALL FIXTURE DRAINS AND WATER-SEAL |
| | TRAPS OR PROVIDE A FIXTURE SCHEDULE INDICATING THE |
| | REQUESTED SIZES. PER FBC-2004 PLUMBING SECTION 401.1 |
| | SCOPE AND (W.P.B. AS AMENDED) SECTION 106.3.5.4 (9) |
| | PLUMBING. |
| | |
| | 5. SHEET P1.1 WATER HEATER SCHEDULE: THE SCHEDULE |
| | INDICATES A RECIRCULATING PUMP FOR THE WATER HEATER |
| | SUPPLING HOT WATER TO HIS AND HER BATH, KITCHEN, AND |
| | POWDER ROOM. PLEASE CLEARLY INDICATE THAT THE HOT WATER |
| | RECIRCULATING PIPE WILL BE INSULATED WITH INSULATION OF |
| | AT LEAST 1/2 INCH MINIMUM THICKNESS. PER FBC-2004 |
| | CHAPTER 13, SECTION 13-612.ABC.5 PIPING INSULATION. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |