2008-09-30 09:48:47GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.(GAS PLANS
 LOCATED IN SUPPLEMENTAL INFORMATION BOOK)
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE.
 *NOTE: THE SUBMITTED ISOMETRIC DOES NOT INDICATE
 CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE.
 PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT SECTIONS
 OF PIPE WITH NO CORRESPONDING LENGTHS.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 PER FBC-2004 FUEL GAS CODE SECTION 401.1 SCOPE.
 *NOTE: THE SUBMITTED ISOMETRIC DOES NOT INDICATE ANY OF
 THE ABOVEGROUND PIPING MATERIAL AS WELL AS SOME CUT
 SECTIONS OF UNDERGROUND PIPING. THE ISOMETRIC ALSO DOES
 NOT INDICATE PIPE SIZES TO ALL CUT SECTIONS OF PIPE.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 *NOTE: THE ISOMETRIC INDICATES 97' D.L. (LONGEST
 LENGTH), HOWEVER NOT ALL CUT SECTIONS OF GAS PIPE HAVE
 CORRESPONDING LENGTHS. PLEASE REFERENCE COMMENT #1 AND
 COMPLY.
  
 4. THE FUTURE B.B.Q. NEEDS TO BE CAPPED GAS TIGHT. PER
 FBC-2004 FUEL GAS SEC. 404.12 OUTLET CLOSURES: GAS
 OUTLETS THAT DO NOT CONNECT TO APPLIANCES SHALL BE
 CAPPED GAS TIGHT.
  
 5. CLEARLY INDICATE THE LOCATION OF THE MP REGULATORS
 (2/PSI TO 0.5/PSI REGULATORS) ON THE RESUBMITTED
 ISOMETRIC OR PROVIDE A LEGEND OF HOW THEY APPEAR ON THE
 PLANS. ALSO PROVIDE A DETAIL OF THE GAS LAMP VALVE BOX
 CLEARLY INDICATING THE LOCATION OF THE SHUT OFF VALVE
 AND MP REGULATOR. PLEASE CLARIFY THE LOCATION OF THE
 GAS LAMP VALVE BOXES. IT APPEARS TO BE LOCATED AT
 FINNISH GRADE LEVEL. PLEASE CLARIFY HOW THE MP
 REGULATORS WILL WORK IF VALVE BOX FILLS WITH WATER
 DURING A STORM. PER FBC-2004 FUEL GAS CODE SECTION
 401.1 SCOPE.
  
 6. THE COOK TOP NEEDS A SHUT OFF VALVE BEFORE THE MP
 REGULATOR IF THE CIRCLE IS A MP REGULATOR (REFERENCE
 COMMENT #5). PER FBC-2004 FUEL GAS, SECTION 409.4 MP
 REGULATOR VALVES: A LISTED SHUTOFF VALVE SHALL BE
 INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR.
  
 7. SUBMIT MANUFACTURE SHEETS FOR THE MP REGULATORS
 (2/PSI TO 0.5/PSI REGULATORS) TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE FBC-2004 FUEL GAS
 CODE SEC 402.2. THE MANUFACTURER SHEETS SHOULD CLEARLY
 INDICATE THE MP REGULATOR MAKE, MODEL NUMBER, BTU LOAD
 CAPACITY, AND A LISTING FROM A NATIONALLY RECOGNIZED
 TESTING LABORATORY SUCH AS CSA, AGA, OR UL.
  
 8. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER,
 THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS, PER FLORIDA
 STATUTES 481 AND 471 RESPECTIVELY.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  